Huawei DPU40D-N06A3 Quick Manual

Distributed power
Hide thumbs Also See for DPU40D-N06A3:

Quick Links

DPU40D-N06A3, DBU20B-N12A3, and DBU50B-N12A1 Distributed
Power Quick Guide
Issue: 05
Date: 2020-02-29
1
Overview
Power supply unit (PSU):
DPU40D-N06A3 (≈ 7.5 kg)
(Unit: mm)
PSU Indicator Color
Status
Off
Steady on
Run indicator
Green
Blinking slowly (0.5 Hz) The PSU communicating with the host properly
Blinking fast (4 Hz)
Off
Steady on
Fault indicator
Red
Blinking slowly (0.5 Hz)
Lithium
Battery
Color
Status
Indicator
Off
Steady on
Run indicator
Green
(RUN)
Blinking slowly (0.5 Hz) The lithium battery is communicating properly with monitoring equipment
Blinking fast (4 Hz)
Off
Steady on
Alarm
Red
indicator (ALM)
Blinking slowly (0.5 Hz)
2
Installation Scenarios
NOTE
There are two pole-mounting scenarios. In the large pole scenario, the pole diameter is 114 mm to 400 mm. In the small pole scenario, the pole
diameter is 60 mm to 114 mm. Select an appropriate pole based on site requirements. The following uses the small pole scenario as an
example.
If multiple PSUs are configured, they can be cascaded by connecting BAT and LOAD ports or by interconnecting LOAD ports. It is
recommended that DC loads be equally distributed on the PSUs.
This section uses a maximum of two lithium batteries as an example.
Lithium
DBU20B-N12A3 (≈ 20 kg)
battery:
DBU50B-N12A1 (≈ 26 kg)
(Unit: mm)
Meaning
The PSU has no power input (no AC input and no battery input)
Start / Self-check / Load (instantaneous status during startup or upgrade)
The PSU is not communicating with the host properly
The PSU is proper
The PSU is faulty: Rectifier Fault/Monitoring Address Conflict/Monitoring Unit Fault
An alarm that can be cleared is generated on the PSU: Rectifier Protection/Power off/
Communication Failure/Rectifier Power Failure/Parallel Fail/AC Overvoltage/AC Undervoltage
Meaning
The lithium battery has no power input or is faulty
Board startup / self-check / loading / activation / board power-on when no software is loaded
The lithium battery fails to communicate with monitoring equipment
The lithium battery is proper
The lithium battery has alarms that cannot be cleared: Board Hardware Fault/Heater
Fault/Electrochemical cell fault/Duplicate address
The lithium battery has alarms that can be cleared: Discharge Overcurrent Protection/Charge
Overcurrent Protection/High Temperature protection/Low Temperature Protection/Abnormal
shutdown/Charge Overcurrent Protection/Discharge Overcurrent Protection
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
Installation
Installation
Max.
Scenario
Method
Capacity/Layer
2 PSUs +2 lithium
batteries (Install
the first battery
Side
exactly on the pole,
Small pole
mounting
the second battery
on its left side, or
two PSUs on its
right side.)
Small pole,
wall,
Flush
1 PSU + 1 lithium
large pole,
mounting
battery or 2 PSUs
channel steel,
angle steel
1
Max. System
Configuration
4 DC PSUs (DPU40D)
+ 8 lithium batteries
(DBU20B/DBU50B)
If the system
configuration
exceeds the
maximum
capacity/layer,
install the
modules on
different layers.
loading

Summary of Contents for Huawei DPU40D-N06A3

  • Page 1 DPU40D-N06A3, DBU20B-N12A3, and DBU50B-N12A1 Distributed Power Quick Guide Issue: 05 Date: 2020-02-29 Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved. Overview Lithium Power supply unit (PSU): DBU20B-N12A3 (≈ 20 kg) Installation Installation Max. Max. System battery: DPU40D-N06A3 (≈ 7.5 kg) DBU50B-N12A1 (≈...
  • Page 2: Installation Preparations

    1 Sector/1 Frequency + 1 PSU 1 Sector/1 Frequency + 2 PSU (Unit: mm) (Unit: mm) Lithium Battery Lithium Battery (Unit: mm) 1 Frequency + 3 PSU 4 PSU + 8 Lithium Battery (Unit: mm) Lithium Battery Lithium Battery Installation Preparations Wear gloves during installation.
  • Page 3 Installing PSUs and Lithium Batteries Installing the RJ45 Communications Cable for a Lithium Battery Flush Mounting on a Small Pole: 1 PSU as an Example (Pole Diameter: 60–114 mm) Required Accessories Installation Procedure Pole mounting kit Install the pole mounting kits. Install the PSU hanging kit.
  • Page 4 Flush Mounting on a Small Pole: 1 PSU + 1 Lithium Battery as an Example (Pole Diameter: 60–114 mm) Required Accessories Installation Procedure Install the attachment Install the attachment kit and Pole mounting kit Install the pole mounting C x 1 kit on lithium battery connecting kit to the lithium battery.
  • Page 5 Flush Mounting on a Wall (Mode 1): 1 PSU + 1 Lithium Battery as an Example The wall must be able to bear a weight four times the weight of all PSUs and lithium batteries and the bolts' pulling force of 1.25 kN vertical to the wall.
  • Page 6: Installing Cables

    Flush Mounting on Channel or Angle Steel Channel steel  As shown in the left figures, when size and the narrow edge size of channel installation steel is less than 40 mm, only method installation methods a and b are supported.
  • Page 7 • If the cable diameter is > 6 mm , prepare cables as follows: Scale line Crimping tool Bare crimp (Unit: mm) terminal Heat shrink Heat gun tubing Installing Ground Clips for DC Load Cables Cable binding hole (≥ 6 mm Cable binding hole (4 mm Cable tie Waterproof tape...
  • Page 8: Verifying The Installation

    • Huawei will not be liable for any security issues caused by your failure to change the default password in time or password loss after changing. (The password cannot be retrieved if it is lost.) Password Change: System Settings >...
  • Page 9 2. Ensure that the paint on the module exterior is intact. If paint has flaked off, repaint the area to avoid corrosion. 3. Clean the site and leave. FAQ:How Do I Expand the Capacity of DC Loads? LIE APP DC load Four-way connector Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China e.huawei.com...

This manual is also suitable for:

Dbu20b-n12a3Dbu50b-n12a1