13. CONTROL
13-2. Indoor unit address setting
(Be sure to operate with the main power turned OFF.)
SWU2
SWU1
13-2-1. Switch operation (BC controller)
There are two types of rotary switch setting available: setting addresses 1 to 9 and over 10, and setting branch numbers.
a) How to set addresses
Example: If Address is "3", SWU2 (for over 10) remains at "0", and match SWU1 (for 1 to 9) to "3".
b) How to set branch numbers SWU3 (only for R2/WR2-Series)
Branch number matches the BC controller branch number. If two branches are used, SWU3 should be set to a smaller
branch number. For other than R2/WR2-Series, remain SWU3 as "0".
- example -
BC controller
OC
13-2-2. Switch operation (WCB)
a) How to set addresses
Example: If Address is "3", SWU2 (for over 10) remains at "0", and match SWU1 (for 1 to 9) to "3".
b) How to set branch numbers SWU3 (only for R2-Series)
There are two branches for WCB. Indoor unit/PWFY connecting branch should be set as "0" and PWFY connecting
branch as "1".
- example -
WCB
OC
MEES19K013
SWU3
BC
4
3
2
1
IC1
IC2
WCB
Indoor/PWFY
PWFY connecting
connecting branch
branch
address
(01)
SWU2 SWU1 SWU3
(02)
IC1
IC2
(03)
address
SWU2 SWU1 SWU3
(01)
(02)
IC1
IC1
IC2
IC2
(03)
IC3
IC3
(04)
AIR TO WATER
0
1
1
0
2
3
0
3
4
0
1
1
0
2
0
0
3
0
0
4
0
44