Fujitsu AB G30LRTE Series Design & Technical Manual

Fujitsu AB G30LRTE Series Design & Technical Manual

Ceiling type
Hide thumbs Also See for AB G30LRTE Series:

Quick Links

AIR CONDITIONER
Ceiling type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AB G30LRTE
AB G36LRTE
AO G30LETL
AO G36LETL
Table of Contents
loading

Summary of Contents for Fujitsu AB G30LRTE Series

  • Page 1 AIR CONDITIONER Ceiling type DESIGN & TECHNICAL MANUAL INDOOR AB G30LRTE AB G36LRTE OUTDOOR AO G30LETL AO G36LETL...
  • Page 2: Indoor Unit

    1. INDOOR UNIT CEILING TYPE : G30LRTE G36LRTE DTR_AB037E_01 2013.02.28...
  • Page 3: Table Of Contents

    CONTENTS 1. INDOOR UNIT ......................01 - 01 1. FEATURES 2. WIRELESS REMOTE CONTROLLER ..........01 - 03 3. SPECIFICATIONS ....................01 - 05 4. DIMENSIONS ......................01 - 07 5. WIRING DIAGRAMS ..................01 - 09 6. CAPACITY TABLE ....................
  • Page 4: Features

    FEATURES MODEL AB G30LRTE / AO G30LETL AB G36LRTE / AO G36LETL FEATURES Energy efficiency class MODEL AB G30LRTE AB G36LRTE Cooling Heating Quiet operation Air flow mode can be set in 4 steps and more detailed air flow setting is possible. 30 type: 32 dB / 36 type: 32 dB at operation in the Quiet mode.
  • Page 5 Fresh-air intake Fresh-air INDOOR OUTDOOR FUNCTION SETTINGS Ceiling switching function (standard/high ceiling) Also delivers air to high ceilings by selecting the mode and raising the air flow according to the height of the ceiling. Standard ...Operates at normal air flow. Mode 1 ...Air flow becomes greater than normal.
  • Page 6: Wireless Remote Controller

    WIRELESS REMOTE CONTROLLER FEATURES 4 mode timer setup available (ON / OFF / PROGRAM / SLEEP). Four kinds of timers. Easy operation. Easy to change signal code (max. 4 units) by button operation. Simple function setting Setting of the air conditioner selection function is performed by remote controller. Built-in timers Select from four different timer programs (On/Off/Program/Sleep).
  • Page 7 FUNCTIONS MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. signal code change. (Max 4 types) 10°C HEAT button SET TEMP. button ( ▲ / ▼ ) Sets the indoor temp./ Sets R.C. signal code. ECONOMY button SLEEP button Pressed to select sleep timer.
  • Page 8: Specifications

    SPECIFICATIONS CEILING MODEL Type INVERTER HEATPUMP Model name AB G30LRTE AB G36LRTE Power source 230V~ 50Hz Available voltage range 198-264V~ 50Hz 8.50 9.40 Rated Btu/h 29000 32100 Cooling 2.80 -10.00 2.80 -11.20 Min.-Max. Btu/h 9500 -34100 9500 -38200 Capacity 10.00 11.20 Rated Btu/h...
  • Page 9 Model name AB G30LRTE AB G36LRTE Cooling Energy efficiency class Heating (Average) Cooling Pdesign Heating (Average) SEER Cooling 6.10 6.00 kWh/kWh SCOP Heating (Average) 4.20 4.10 Annual energy consumption kWh/a QHE (Average) 2662 2965 Cooling Sound power level High dB (A) Heating - (01 - 06) -...
  • Page 10: Dimensions

    DIMENSIONS MODEL : AB G30LRTE, AB G36LRTE (Unit : mm) Top view Side view Rear view Suspension bolt pitch 1,600 Dimensions (Space Required for Installation) INDOOR UNIT (Top view) Suspension bolt should extend INDOOR UNIT outward 30 to 75. 1 Refrigerant piping flare connection (Gas) 2 Refrigerant piping flare connection (Liquid) 3 Drain piping connection 4 Knock out hole for fresh air...
  • Page 11 INSTALLATION PLACE (Unit : mm) Ceiling INDOOR UNIT 80 or more 150 or more Ceiling 10 or more Obstruction Floor Ceiling pane INDOOR UNIT Ceiling panel 80 or more 150 or more 10 or more Obstruction Floor - (01 - 08) -...
  • Page 12: Wiring Diagrams

    WIRING DIAGRAMS MODEL : AB G30LRTE, AB G36LRTE - (01 - 09) -...
  • Page 13: Capacity Table

    CAPACITY TABLE 6-1. COOLING CAPACITY This table is created using the maximum capacity. MODEL : AB G30LRTE 27.7 Indoor temperature °CDB °CWB °CDB 8.60 6.53 1.32 9.59 6.57 1.35 9.91 7.14 1.35 10.57 7.17 1.37 10.89 7.74 1.37 11.55 7.71 1.39 12.20 8.21...
  • Page 14: Heating Capacity

    6-2. HEATING CAPACITY This table is created using the maximum capacity. MODEL : AB G30LRTE 27.7 Indoor temperature °CDB °CDB °CWB 8.22 3.38 8.02 3.45 7.83 3.52 7.63 3.59 7.44 3.67 8.79 3.39 8.58 3.46 8.37 3.53 8.16 3.60 7.95 3.67 9.54 3.40...
  • Page 15: Fan Performance

    FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION MODEL : AB G30LRTE Note: Condition Fan speed : High Unit : m/s Operation mode : FAN 0.25 Unit : m/s 10 11 12 13 14 15 16 17 TOP VIEW VERTICAL : UPWARD HORIZONTAL : CENTER 0.25 Unit : m/s...
  • Page 16 MODEL : AB G36LRTE Note: Condition Fan speed : High Unit : m/s Operation mode : FAN 0.25 Unit : m/s 10 11 12 13 14 15 16 17 TOP VIEW VERTICAL : UPWARD HORIZONTAL : CENTER 0.25 Unit : m/s 10 11 12 13 14 SIDE VIEW FLAP : CENTER...
  • Page 17: Airflow

    7-2. AIRFLOW MODEL : AB G30LRTE COOLING Number of Fan speed rotations Airflow (r.p.m.) 1660 HIGH 1000 1500 1200 1000 QUIET HEATING Number of Fan speed rotations Airflow (r.p.m.) 1660 HIGH 1000 1500 1200 1000 QUIET - (01 - 14) -...
  • Page 18 MODEL : AB G36LRTE COOLING Number of Fan speed rotations Airflow (r.p.m.) 1900 HIGH 1100 1118 1500 1200 1000 QUIET HEATING Number of Fan speed rotations Airflow (r.p.m.) 1900 HIGH 1100 1118 1500 1200 1000 QUIET - (01 - 15) -...
  • Page 19: Fresh Air Characteristic

    7-3. FRESH AIR CHARACTERISTIC MODEL : AB G30LRTE, AB G36LRTE (mmAq) (Pa) 98 Fresh air flow (m /min) - (01 - 16) -...
  • Page 20: Operation Noise

    OPERATION NOISE 8-1. NOISE LEVEL CURVE MODEL : AB G30LRTE Cooling Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 21: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT Microphone Microphone - (01 - 18) -...
  • Page 22: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model name AB G30LRTE AB G36LRTE Voltage 230 ~ Power supply Frequency Max. operating current (Indoor unit) Connection cable 1.5 - 2.5 *1) Wiring spec. Limited wiring length *1) Wiring spec. Selected Sample (Selected based on Japan Electrotechnical Standards and Committee E0005) - (01 - 19) -...
  • Page 23: Safety Devices

    SAFETY DEVICES Model Protection form AB G30LRTE AB G36LRTE Circuit protection Current fuse (PCB) 250V 3.15A Thermal protection 135±15°C OFF Fan motor protection program 115±15°C ON - (01 - 20) -...
  • Page 24: External Input & Output

    EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CN102 Control input — See external CN103 — Operation status output input/output settings for details. — Fresh air control output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
  • Page 25: External Output

    11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor Connected unit control PC board Connector Ex.)Relay unit Ex.)Display 24V DC Relay power supply *10 m Signal Field supply * Make the distance from the PC board to the connected unit within 10m. Relay spec.
  • Page 26 FRESH AIR CONTROL OUTPUT A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example Indoor Connected unit control PC board Ex.) Fan Ex.) Relay unit 12 V Connector Relay...
  • Page 27: Function Settings

    FUNCTION SETTINGS 12-1. INDOOR UNIT INDOOR UNIT DIP SW Remote controller address setting Jumper Wire Setting forbidden SWITCH POSITION MAIN PCB Indoor unit Printed circuit board DIP-SW SETTING Remote controller address setting A number of indoor units can be operated at the same time using a wired remote controller. Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board.
  • Page 28: Indoor Unit (Setting By Remote Controller)

    12-2. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
  • Page 29 CONTENTS OF FUNCTION SETTING • Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control. •...
  • Page 30 5) Auto restart Enable or disable automatic system restart after a power outage. ( . . .Factory setting) Setting Description Function Number Setting Value * Auto restart is an emergency function such as for power failure etc. Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
  • Page 31 REMOTE CONTROLLER SIGNAL CODE SETTING Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) 1.
  • Page 32: Optional Parts

    OPTIONAL PARTS 13-1. CONTROLLER Exterior Parts name Model No. Summary Large and full-dot liquid Wired remote crystal screen, wide and UTY-RVN M controller large keys easy to press, user-intuitive arrow key. Wired remote Unit control is performed by UTY-RNN M controller wired remote controller Simple...
  • Page 33: Others

    13-2. OTHERS Exterior Parts name Model No. Summary Drain Pump Optional drain lift-up mechanism UTR-DPB24T unit allows more flexible installation. Round flange is used when the fresh air duct is installed. Round flange UTD-RF204 Round flange Use to connect with various External UTY-XWZX peripheral devices and air...
  • Page 34 2. OUTDOOR UNIT SINGLE TYPE : AO G30LETL AO G36LETL DTR_AO135E_01 2013.02.28...
  • Page 35 CONTENTS 2. OUTDOOR UNIT ....................02 - 01 1. SPECIFICATIONS 2. DIMENSIONS ......................02 - 02 3. REFRIGERANT CIRCUIT ................02 - 03 4. WIRING DIAGRAMS ..................02 - 04 5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE ..................
  • Page 36: Specifications

    SPECIFICATIONS Type INVERTER HEATPUMP Model name AO G30LETL AO G36LETL Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current 12.2 13.7 Cooling 3600 3800 Airflow rate Heating 3600 3800 Type × Q'ty Propeller × 1 Motor output Cooling Sound pressure level dB(A)
  • Page 37: Dimensions

    DIMENSIONS MODELS : AO G30LETL, AO G36LETL (Unit : mm) Top view Front view Side view Air flow Bottom view INSTALLATION PLACE When there are obstacles at the back When there are obstacles at the back, When there are obstacles at the back, or front sides.
  • Page 38: Refrigerant Circuit

    REFRIGERANT CIRCUIT MODELS :AO G30LETL, AO G36LETL Refrigerant direction Cooling Heating Refrigerant pipe diameter Liquid : 9.52 mm (3/8") Gas : 15.88 mm (5/8") - (02 - 03) -...
  • Page 39: Wiring Diagrams

    WIRING DIAGRAMS MODEL : AO G30LETL - (02 - 04) -...
  • Page 40 MODEL : AO G36LETL - (02 - 05) -...
  • Page 41: Capacity Compensation Rate For Pipe Length And Height Difference

    CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE MODELS :AO G30LETL, AO G36LETL Pipe length (m) COOLING 0.908 0.894 0.876 0.935 0.923 0.909 0.891 Indoor unit is higher 0.968 0.951 0.938 0.924 0.906 than outdoor unit 0.982 0.972 0.954 0.942 0.928 0.909...
  • Page 42: Additional Charge Calculation

    ADDITIONAL CHARGE CALCULATION MODELS : AO G30LETL, AO G36LETL Refrigerant type R410A Refrigerant amount 2100 Refrigerant Charge Total pipe length 20 or less 50 (MAX) 40g/m Additional charge 1200 - (02 - 07) -...
  • Page 43: Airflow

    AIRFLOW MODEL : AO G30LETL COOLING Number of rotations Airflow (r.p.m) 3600 1000 2119 HEATING Number of rotations Airflow (r.p.m) 3600 1000 2119 MODEL : AO G36LETL COOLING Number of rotations Airflow (r.p.m) 3800 1056 2236 HEATING Number of rotations Airflow (r.p.m) 3800...
  • Page 44: Operation Noise (Sound Pressure)

    OPERATION NOISE (SOUND PRESSURE) 8-1. NOISE LEVEL CURVE MODEL : AO G30LETL COOLING HEATING NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 45: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT - (02 - 10) -...
  • Page 46: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model name AO G30LETL AO G36LETL Voltage 230 ~ Power supply Frequency *1) Max. operating current 17.0 20.0 Starting current 12.2 13.7 Main fuse (Circuit breaker) current *2) Wiring spec. Power cable *1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring spec.
  • Page 47: Safety Devices

    SAFETY DEVICES Model Protection form AO G30LETL AO G36LETL Current fuse (Near the terminal) 250V 25A Circuit protection Current fuse (Filter printed circuit board) 250V 10A Current fuse (Main printed circuit board) 250V 3.15A OFF : 140±20°C Fan motor protection Thermal protection program ON : 110±20°C OFF : 4.2±0.1MPa...