  • Page 1 DMS8000 MP4.xx Connectivity Guide Add-on NICE/RIVER Digital Video Recorders Building Technologies Fire Safety & Security Product...
  • Page 2 Data and design subject to change without notice. / Supply subject to availability. © 2009 Copyright by Siemens Building Technologies AG We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
  • Page 3: Table Of Contents

    Table of contents About this document....................2 Introduction .....................4 Installation ....................4 Software installation ..................4 2.1.1 Requirements ................4 2.1.2 Software License ................4 2.1.3 NICE add-on installation.............5 2.1.4 NICE add-on uninstall..............5 Configuration...................6 Video integration ..................6 Video Network Manager ................6 Video Drivers.....................7 Video components ..................7 NICE DVR configuration ................8 3.5.1 Configuration checklist ...............8...
  • Page 4: About This Document

    − Training program information including the Siemens intranet link − A complete list of all available DMS8000 documents − Instructions for how to obtain a document via the Siemens intranet using the STEP Documentation Repository System − A map of relevant documents for each target audience group −...
  • Page 5 Liability disclaimer for damage or injuries Before products are delivered, they are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions, or the disregard of danger adviso- ries.
  • Page 6: Introduction

    Introduction This is a guide to the software configuration procedures for the NICE and RIVER Digital Video Recorders (DVR) in the MM8000 Management Station. For a complete guide to the configuration process, this manual should be used with the DMS8000 Network, Fire and Intrusion Guide, and with the Installation, Configu- ration and Commissioning manual (ICC) of the specific product.
  • Page 7: Nice Add-On Installation

    2.1.3 NICE/RIVER add-on installation The following are the installation procedures for the NICE/RIVER add-on module. 1. Start Add-on Manager; from the Windows Start menu, select the following: Start DMS8000 Tools Add-on Manager The Add-on Manager window appears (Fig. 1). 2. In the list of add-ons Names, select Nice or River depending on which product family you have to use.
  • Page 8: Configuration

    Configuration Video integration The DMS8000 systems MM8000 and MK8000 can support the connection to the following NICE video systems (and to the corresponding RIVER products when applicable): Manufacturer Model Device type NICE NiceVision Alto Digital Video Recorder (DVR) NICE NiceVision Pro Digital Video Recorder (DVR) NICE NiceVision NVSat...
  • Page 9: Video Drivers

    Video Drivers The VNM can support the driver required to handle the network communication with NICE/RIVER units. To add the driver to your project, proceed as follows: 1. Select the VNM node. 2. In the toolbar, click the icon corresponding to the NR driver (Fig. 3): Fig.
  • Page 10: Nice Dvr Configuration

    NICE/RIVER DVR configuration 3.5.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceed- ing to the configuration procedure that follows. ITEMS NEEDED FOR CONFIGURATION The NR Video driver installed and configured under the Video Network Manager in Composer The DVR IP address The camera connections...
  • Page 11 Connecting the cameras 1. Select and expand the DVR node. 2. Select and expand the DVR Video-in folder. 3. Add the required video inputs: note that input number can be customised. 4. Select and expand the Video Cameras folder. 5. Select the video-out node of the camera. 6.
  • Page 12: Limitations

    Limitations Currently, the support of NICE/RIVER DVR units is subject to the following limita- tions (please check latest news with customer support): • Maximum number of connectable DVR units per Server or FEP is 150 (100 rec- ommended for best performance). •...
  • Page 13: Operations

    Operations MM8000 PTZ control panel MM8000 operations are described in the MM8000 Operation Manual (document no. A6V10062409). When operating with NICE/RIVER video systems in event treatment and plant browsing, a specific control panel is provided for the cameras equipped with PTZ control features.