LG ATNH09GRLE2 Svc Manual
Hide thumbs Also See for ATNH09GRLE2:
Internal Use Only
http://biz.lgservice.com
Air Conditioner
SVC MANUAL(General)
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Table of Contents
loading

Summary of Contents for LG ATNH09GRLE2

  • Page 1 Internal Use Only http://biz.lgservice.com Air Conditioner SVC MANUAL(General) CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
  • Page 2: Table Of Contents

    3. Evacuation (All amount of refrigerant leaked) ............59 4. Gas Charging (After Evacuation)................60 5. Cycle Part........................61 6. Electronic Parts......................62 - 2 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 3: Part 1 General Information

    Part 1 General Information 1. Safety Precautions ......................4 2. Model Line Up ........................7 3. Nomenclature........................11 - 3 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 4: Safety Precautions

    Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug. There is risk of fire or electrical shock. - 4 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 5 Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred. - 5 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 6 Check the drainage of the indoor unit after the repair. If drainage is faulty the water to enter the room and wet floor. - 6 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 7: Model Line Up

    [CQ09 NA0] [CQ12 NA0] [CQ18 NA0] APNH48GTLA0 Floor standing [UP48 NT2] AJNW30GVLA0 AJNW36GVLA0 Wall mounted [UJ30 NV2] [UJ36 NV2] - 7 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 8 ABNH18GL2A2 [CB18L N22] ABNH24GL3A2 [CB24L N32] • Floor Standing • Wall mounted APNH48GTLA0 [UP48 NT2] AJNW30GVLA0 [UJ30 NV2] AJNW36GVLA0 [UJ36 NV2] - 8 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 9 1 ~ 4 Total capacity index of 12.5 14.0 15.0 connectable indoor units(kW) Power supply 1Ø, 220 - 240V, 50Hz Chassis - 9 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 10 1 ~ 4 Total capacity index of 12.5 14.0 15.0 connectable indoor units(kW) Power supply 3Ø, 380 - 415V, 50Hz Chassis - 10 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 11: Nomenclature

    C : Cooling Only H : Heat Pump U: Single A Decoration Panel of Ceiling Cassette Type Indoor Unit - 11 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 12 H : H/P Q : DC Inverter C/O W : DC Inverter H/P Indicates that this is a R410A outdoor unit - 12 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 13 C : Cooling Only H : Heat Pump U: Single A Decoration Panel of Ceiling Cassette Type Indoor Unit - 13 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 14 Model type W : Inverter Cooling capacity (kBtu/h) Type U : Outdoor units Model type U : Universal model - 14 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 15: Part 2 Functions & Controls

    6.11 Two Thermistor Control .....................49 7. Special Function & KIT ....................50 7.1 Low Ambient control....................50 7.2 Space Control ......................50 7.3 Auto Elevation Grille....................50 - 15 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 16: List Of Functions & Accessory

    PI 485(for Indoor Unit) Zone controller Special CTI(Communication transfer interface) function kit Electronic thermostat Remote temperature sensor PQRSTA0 Others Telecom shelter controller - 16 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 17 PI 485(for Indoor Unit) Zone controller Special CTI(Communication transfer interface) function kit Electronic thermostat Remote temperature sensor PQRSTA0 Others Telecom shelter controller - 17 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 18 Zone controller ABZCA Special CTI(Communication transfer interface) function kit Electronic thermostat Remote temperature sensor PQRSTA0 Others Telecom shelter controller - 18 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 19 Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. - 19 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 20 Zone controller Special CTI(Communication transfer interface) function kit Electronic thermostat Remote temperature sensor PQRSTA0 PQRSTA0 Others Telecom shelter controller - 20 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 21 Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate pack- age. - 21 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 22 Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. - 22 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 23 Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. - 23 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 24 Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. - 24 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 25 Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. - 25 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 26 Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. - 26 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 27: Air Flow

    Mode7 Mode6 Mode5 Mode4 Mode3 7~8° Mode2 OPEN NOTE: Some Models are different by swing width and swing pattern. - 27 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 28: Air Flow Step

    After one minute, it is opposite. Vane 1 Vane 3 Vane 4 • Comparison of Air Flow Types 4-Open (conventional) Swirl Swing (New) - 28 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 29: Air Purifying

    Dust electrode discharge Dust particles Photo-Catalyst Coated Mesh Ionizer +4.8KV discharge Polluted Air Purified fresh Air Generating plasma Odour Odour molecule - 29 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 30: Installation Functions

    Function Pressure selection Zone state ESP standard value Variable High Fixed High Variable Fixed - 30 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 31 It does not work to setup ESP value for very low/power step for some products. • ESP value is available for specific range belongs to the product. - 31 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 32 - Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32) setting is being used. - For the static pressure value for each step, refer to the next page Table. 1 - 32 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 33 Setting Value 4(49) 6(59) 8(78) 10(98) 20.8 23.2 19.5 26.0 21.5 23.5 19.1 26.3 21.6 24.0 19.9 27.0 22.7 25.9 - 33 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 34 6(59) 8(78) 10(98) 12(118) 14(137) 41.3 45.4 39.7 49.5 44.1 38.6 48.5 44.2 38.9 49.8 44.7 42.2 50.5 48.1 - 34 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 35 * If it is zero static pressure, please set value below Maximum value. Model Maximum value ABNW18GM1A0 ABNW24GM1A0 ABNW30GM1A0 ABNW36GM2A0 ABNW42GM2A0 - 35 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 36 High ABNH48GRLA2 10(98) 35.0 5(49) 12(118) (factory set) 30.0 50.0 High 45.0 ABNH60GRLA2 10(98) 6(59) 14(137) (factory set) 40.0 - 36 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 37 16.19 22.75 20.86 18.44 Note : 1. The above table shows the correlation between the air rates and E.S.P. - 37 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 38 24.5 22.6 20.9 19.9 Note : 1. The above table shows the correlation between the air rates and E.S.P. - 38 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 39 36.8 43.1 41.2 45.6 Note : 1. The above table shows the correlation between the air rates and E.S.P. - 39 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 40: High Ceiling Operation

    • Ceiling height of ʻVery highʼ function may not exist depending on the indoor unit. • Refer to the product manual for more details. - 40 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 41: Reliability

    -0.5°C 18°C ≤ intake air temp. < 22°C intake air temp. intake air temp. < 18°C 18°C - 41 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 42: Convenience Functions & Controls

    Thermo ON : Setting temp. Thermo OFF : +4 °C above setting temp. Thermo OFF : +3 °C above setting temp. - 42 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 43: Auto Cleaning Operation

    Memorized condition are on / off condition, operating mode (cooling/ heating), set temperature and fan speed. The unit will memorize the above conditions and start with same memorized condition. - 43 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 44: Child Lock Function

    - The operation will be started if the ON/OFF button is pressed. - If you want to stop operation, re-press the button. - 44 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 45: Group Control

    • When controlling in groups, set the master/slaver of the remote controller. Refer to Installer setting section on how to set mas- ter/slave for more detail. - 45 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 46: Sleep Timer Operation

    • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. • If the appliance is on pause at the time set by the timer, the pause continues. - 46 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 47: Weekly Program

    Please move to 'minute' setup part of turning on by using button. If 'minute' indication blinks, please setup 'minute' by using button - 47 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 48 (Temperature selection range : 18℃~30℃) - When desired temperature is not set, it is turned on automatically with desired temperature of previous operation. - 48 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 49: Two Thermistor Control

    Operation of lower temperature by comparing indoor unit's and wired remote Heating controller's temperature. h The function of 2TH has different operation characteristics according to the product. - 49 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 50: Special Function & Kit

    3.1 m. So it enables to install the Indoor unit at high ceiling space. And Auto Elevation Grille makes you cleaning the filter easily. - 50 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 51 • In case when obstacle such as curtain hides the signal reception part of receiver in between the space interval, Remote Controller operation is infeasible. - 51 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 52 Automatic stop distance 1.5±0.5m 2.5±0.5m 3.5±0.5m S If you want to change automatic distance setting, consult with your sale agency. - 52 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 53: Part 3 Basic Control

    Part 3 Basic Control 3. Basic Control 1. Normal operation......................54 2 Compressor control ......................54 3. EEV( Electronic Expansion Valve) control ..............54 - 53 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 54: Normal Operation

    *Heating mode the target temperature of discharge pipe = T condenser + α T condenser : condenser temperature (℃) - 54 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 55: Part 4 Trouble Shooting Guide

    6.4 When indoor Fan does not operate................65 6.5 When the louver does not operate................66 6.6 Troubleshooting Indoor Error ..................67 6.7 Troubleshooting Outdoor Error ..................73 - 55 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 56: Self-Diagnosis Function

    EEPROM of Indoor unit is 0 or FFFFFF Disconnecting the fan motor connector/ Abnormal fan motor operation Failure of indoor fan motor lock - 56 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 57: Error Indicator (Outdoor)

    Within 1h Flashing 4 Flashing 4 1 time Outdoor Inlet Sensor Error Stop CH44 times times Within 1h - 57 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 58: Pump Down

    Pump Down Complete Gas Valve Closed (Red LED Off, Green LED On) Power off (Red LED Off, Green LED On) - 58 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 59: Evacuation (All Amount Of Refrigerant Leaked)

    Oxygen and do not use Flammable gases. pump). Otherwise, it may cause fire or explosion. - Otherwise, it may cause personal injury. - 59 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 60: Gas Charging (After Evacuation)

    - Any presence of foreign substance such as air repeat the procedure (pumping down-pin). can cause an abnormal pressure rise and may result in explosion or injury. - 60 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 61: Cycle Part

    2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty. - 61 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 62: Electronic Parts

    4) Replace PCB Assembly 5) IC01A(KIA7036) 5) The voltage of micom pin 19 5) Replace PCB Assembly : DC4.5V↑ - 62 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 63: The Product Doesn't Operate With The Remote Controller

    * Check display PCB Assembly - Voltage between CN-DISP1 should be DC +5V, - If problem still persists, Replace display PCB - 63 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 64: The Compressor/Outdoor Fan Are Don't Operate

    Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor. - 64 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 65: When Indoor Fan Does Not Operate

    The voltage of Pin No 1(orange) and 3(black) of CN-FAN. About AC 160V over About AC 50V over SSR is not damaged Check SSR - 65 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 66: When The Louver Does Not Operate

    If there are no problems after above checks. • Confirm the assembly condition that are catching and interfering parts in the link of the vertical louver - 66 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 67: Troubleshooting Indoor Error

    CN-PIPE IN : Pipe inlet temp sensor CN-PIPE OUT : Pipe outlet temp sensor Measure the resistance of outlet pipe temp sensor. - 67 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 68 CN-REMO : Remote controller connection The PCB can differ from model to model. Check from the right source. Checking communication cable connection status - 68 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 69 * If the float goes up higher than a half of float switch then the circuit is open & the unit is stopped automatically. (High position Open) float Condensate water - 69 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 70 (Check input of 220V) (Marked as CN-DPUMP) Float switch Housing (CN-FLOAT) [***] Standard of drain pipe head height / slope MAX 450 - 70 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 71 4. Trouble Shooting 6.6 Troubleshooting Indoor Error CH 09 (Indoor unit EEPROM error) - 71 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 72 (Notice: The connection of motor connector to PCB should be done under no power supplying to PCB) - 72 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 73: Troubleshooting Outdoor Error

    DC link detection circuit fault. Improper power input, IPM connection fault, and insufficient distance Others between heat sink and control panel. - 73 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 74 Checking Checking Checking Compressor Checking Checking DC single connection current PCBA link voltage unit of IPM state detection circuit - 74 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 75 When the front/back has a wall (1 side) When the front/back/left/right have walls (3 sides) When the front/back/left/right have walls (2 sides) - 75 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 76 Replacing a part of or Check pipes the entire pipes SVC Valve SVC Valve Full Open Check EEV Check Replacing EEV - 76 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 77 0.628 ±7% 0.438 ±7% 0.859 ±7% ( at 25 W-U 1.040 ±7% 1.125±7% 0.628 ±7% 0.438 ±7% 0.864 ±7% - 77 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 78 4. Trouble Shooting How to check the compressor wiring error V (Blue) (Yellow) (Red) - 78 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 79 Normal Sequence of Normal Measurement Measurement Measurement Standards Measurement Standards 0.4V~0.6V U-Nu 0.4V~0.6V 0.4V~0.6V V-Nv 0.4V~0.6V 0.4V~0.6V W-Nw 0.4V~0.6V - 79 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 80 Check the voltage for being in the range of 0.4~0.6V. Judge IPM Pins for short. IPM Check Point IPM Check Point P U V W 2/2.5kW - 80 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 81 4. Trouble Shooting IPM Check Point P W V U - 81 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 82 4. Trouble Shooting IPM Check Point - 82 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 83 Apply the electricity. Turn indoor devices off. Measure voltage. Within 2.3 ~2.7V Current detection Replace PCBA. part is normal. - 83 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 84 4. Trouble Shooting Current Detection Circuit Check Point Compressor Phase Current Detection Comp Current 2/2.5kW Comp U - 84 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 85 4. Trouble Shooting Compressor Phase Current Detection - 85 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 86 4. Trouble Shooting Compressor Phase Current Detection - 86 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 87 CH 21 (DC Peak / Comp IPM Fault) Checking the output voltage of CN-4way (refer to next page) Check the 4-way.valve coil resistance. - 87 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 88 4. Trouble Shooting 4-Way Check Point 4Way Check CN-4Way 2/2.5kW CN-4Way - 88 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 89 4. Trouble Shooting Compressor Phase Current Detection CN-4Way CN-4Way - 89 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 90 4. Trouble Shooting Compressor Phase Current Detection CN-4Way - 90 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 91 4. Trouble Shooting LGMV Display - 91 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 92 45 ±5 45 ±5 [Pin No.] Measurement Pin Normal Standard 45 ±5 45 ±5 45 ±5 45 ±5 [Pin No.] - 92 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 93 CH 21 (DC Peak / Comp IPM Fault) Apply the electricity. Turn indoor devices off. Measure voltage. Within 2.3~2.7V Current detection Replace PCBA. part is normal. - 93 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 94 4. Trouble Shooting DC Link Detection Circuit Check Point DC Link Detection Circuit Check Point DC_ Link 2/2.5kW DC_ Link - 94 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 95 4. Trouble Shooting DC Link Detection Circuit Check Point DC_LINK DC_LINK - 95 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 96 4. Trouble Shooting DC Link Detection Circuit Check Point DC LINK-Voltage _ INV - 96 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 97 4. Trouble Shooting Controller Voltage 2~6kW 140V 380V - 97 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 98 Short between compressor coil and sash, abrasion of compressor, and Expected Compressor short/opening of compressor coil. Causes Input current detection circuit fault. Assembly Others Input of low-voltage. - 98 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 99 Checking Checking compressor compressor compressor compressor phase resis- insulation wiring tance resistance Checking input Checking current PCBA detection circuit - 99 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 100 CH 22 (Input of Over Current) Apply the electricity. Turn indoor devices off. Measure voltage. Within 2.3~2.7V Current detection Replace PCBA. part is normal. - 100 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 101 4. Trouble Shooting Input Current Detection Point Input_I 2/2.5kW I_CT - 101 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 102 4. Trouble Shooting Input Current Detection Point CT_INV INPUT(CT) - 102 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 103 4. Trouble Shooting Input Current Detection Point Input_Current_T_PFC Input_Current_R_PFC DC LINK-Voltage _ INV - 103 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 104 4. Trouble Shooting LGMV Display Controller Current Level 2.5kW - 104 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 105 Installation fault and input of low-voltage power Expected Causes Damage of DC link voltage detection circuit and reactor terminal Assembly connection error - 105 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 106 Model only) Checking the wire Installation coating of power source Checking Checking Checking compressor compressor PCBA phase resis- wiring tance - 106 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 107 4. Trouble Shooting 6.7 Troubleshooting Outdoor Error CH 23 (DC Link Voltage Low) Reactor Connector Point 2/2.5kW - 107 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 108 How to check PFCM IGBT (Diode Mode) Sequence of Normal Sequence of Normal Measurement Measurement Measurement Standards Measurement Standards 0.4V~0.6V U-Nu 0.4V~0.6V 0.4V~0.6V V-Nv 0.4V~0.6V - 108 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 109 Normal Sequence of Normal Measurement Measurement Measurement Standards Measurement Standards 0.4V~0.6V U-Nu 0.4V~0.6V 0.4V~0.6V V-Nv 0.4V~0.6V 0.4V~0.6V W-Nw 0.4V~0.6V - 109 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 110 4. Trouble Shooting PFCM Point PFCM Point - 110 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 111 4. Trouble Shooting PFCM Point IPM Check Point - 111 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 112 IPM parts fault, compressor current detection circuit fault, and DC link Assembly detection circuit fault Input of abnormal power, IPM connection fault, and power connection Others fault - 112 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 113 Checking Checking Checking Compressor Checking Checking DC single connection current PCBA link voltage unit of IPM state detection circuit - 113 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 114 Input of abnormal power, power connection fault, reactor terminal con- Others nection fault, and faulty distance between heatsink and sash - 114 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 115 Distance Checking input Checking between current detection PCBA heatsink and circuit panel - 115 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 116 Compressor current detection circuit fault, DC link detection circuit fault, Assembly and fault of single unit of IPM Others Input of abnormal power and power connection fault - 116 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 117 Checking Checking Checking Compressor Checking Checking DC single connection current PCBA link voltage unit of IPM state detection circuit - 117 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 118 Compressor current and DC link voltage detection circuit fault Assembly Sensor Discharge temperature sensor fault - 118 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 119 Checking Checking Checking Checking compressor compressor compressor compressor phase insulation wiring resistance resistance Checking Checking outset PCBA Temperature sensor - 119 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 120 Outdoor air temperature sensor Open/Short Outdoor piping temperature sensor Open/Short Outdoor suction temperature sensor Open/Short Constant rate outlet temperature sensor Open/Short - 120 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 121 6.7 Troubleshooting Outdoor Error Compressor discharge sensor Pipe sensor Compressor Pipe sensor inlet sensor Ω Ω Ω Outdoor temperature sensor Ω - 121 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 122 Voltage of 5V is output PCB checking and replacement from the PCB? No malfunction of the pressure Replace the pressure sensor sensor - 122 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 123 "Maximum Model Name total capacity" MU2M15 MU2M17 MU3M19 MU3M21 MU4M25 MU4M27 MU5M30 MU5M40 FM40AH FM48AH FM56AH FM41AH FM49AH FM57AH - 123 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 124 Damage of and Chassis Panel power source wire coating Replacement of LED Off inverter PCB Replacement of main PCB - 124 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 125 : Interference with wires or wire coating damage with chopping Inverter PCB LED : Replacement of inverter PCB during LED Off after resetting - 125 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 126 Check LGMV Wire tongue Installation connection Communication termination state rate Replacing Communication Communication indoor Grounding cable length cable length - 126 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 127 CH 05/53 (Indoor/Outdoor Device Communication Error) → Detection by indoor devices Fuse Point 2/2.5kW PCBA Fuse PCBA Fuse PCBA Fuse - 127 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 128 Neutral Wire-to-Wire Wire tongue-termination fault. Communication noise by oxidized wire arrangement : Soldering is required. Neutral - 128 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 129 4. Trouble Shooting ↔ ↔ ↔ ↔ ∞ ∞ Ω Ω - 129 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 130 Neutral and Pipe Pipe ∞ ∞ Ω Ω Check Resistance Check Resistance Communication Line and Pipe Pipe ∞ Ω - 130 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 131 4. Trouble Shooting 6.7 Troubleshooting Outdoor Error CH 05/53 (Indoor/Outdoor Device Communication Error) → Detection by indoor devices - 131 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 132 (Refer to PCB P/no of attached file) Applied S/No : ~ 301xxxxxx (~ Jan, 2013) 1. Symptom 2. Causes 3. Improvement - 132 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 133 4. Trouble Shooting PCBA P/NO EBR362668** EBR356522** EBR481682** EBR610154** EBR614818** EBR633722** EBR652505** EBR683491** EBR723989** EBR753611** EBR741383** - 133 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 134 Checking N-phase phase loss Checking for open and reverse phase Fuse damage AC load (R and S phases) Inverter PCB - 134 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 135 N-phase N-phase N-phase N-phase unavaila unavaila unavaila phase availab N-phase N-phase N-phase phase phase phase unavaila availa availa availa - 135 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 136 CH 54 (Open and Reverse Phase Error) Brown B Black Green Brown B Black Green Brown B Black Green Green - 136 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 137 Prompt generation just after power resetting EEPROM Checking connection state Replacing PCB How to check the EEPROM assembling state of outdoor devices - 137 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 138 4. Trouble Shooting EEPROM Position 2/2.5kW - 138 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 139 Checking EEV for Pipe Checking fan Cycle proper working blocking for working Properties Sensor of unit Replacing - 139 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 140 Installation Whether to shield Outdoor Fan Checking for proper working Restoration of Checking for proper working temperature Replacing PCB - 140 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 141 6.7 Troubleshooting Outdoor Error CH 62 (Heat sink High Error) Controller Current Level All PCBA 95℃ ↑ 85℃ ↑ - 141 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 142 Items for checking Sub-items for checking Working Temperature Outdoor Temperature Replacing PCB Environmental factor checking method Sensor checking method - 142 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 143 4. Trouble Shooting Heat sink Tempe Sensor Point #14,16 2/2.5kW #19,20 Ω #19,20 Ω #19,20 Ω - 143 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 144 Damage of fan motor driving circuit Trouble Checking Flow Sub-items for checking Items for checking Outdoor Fan Outdoor fan damage Connection state PCBA Cautions - 144 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 145 How to check the outdoor fan motor of BLDC Tester (±10%) Dozens k Dozens k ~hundreds k ~hundreds k Dozens k Dozens k ~hundreds k ~hundreds k - 145 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 146 December, 2013 P/NO : MFL67478301...