CB1N1428en
2017-11-21
Wireless multizone receiver RDE-MZ6
for floor heating / zone heating systems
∂ Mains-powered RDE-MZ6 multizone wireless receiver (AC 230 V)
∂ DIN rail mounting
∂ 2-position control with On/Off output for each zone / room
∂ Room temperature control of each zone/room
∂ Control output for up to 6 zones with actuators/valves or 5 zones plus
pump/boiler release
∂ Switching voltage AC 24...230V
∂ Each zone can be connected to a maximum of 3 actuators/valves
∂ Easy and quick installation due to new design and easily identifiable
terminal markings
∂ Simple pairing of operation helps reduce installation time
∂ Indication of operating state via LEDs
∂ Only for use in connection with RDD100.1RF and RDE100.1RF room
thermostats (to be ordered separately)
∂ Optional: External antenna for multizone installation inside a metal
enclosure or weak wireless connectivity (provided free)
1
Building Technologies
428
loading

Summary of Contents for Siemens RDE-MZ6

  • Page 1 Wireless multizone receiver RDE-MZ6 for floor heating / zone heating systems ∂ Mains-powered RDE-MZ6 multizone wireless receiver (AC 230 V) ∂ DIN rail mounting ∂ 2-position control with On/Off output for each zone / room ∂ Room temperature control of each zone/room ∂...
  • Page 2 The RDE-MZ6 is used in connection with room thermostats for zone/room temperature control in heating systems. Typical applications: ∂ Apartments ∂ Commercial spaces For the control of the following pieces of equipment: ∂ Thermal valves or zone valves ∂ Floor heating systems ∂...
  • Page 3 Mechanical design The RDE-MZ6 multizone receiver consists of a plastic housing which accommodates the electronics and features a built-in snap for direct mounting on DIN 35 rails (as per EN 50022). 1) Channel state LEDs for zones Operation and settings 1 to 6.
  • Page 4 The green LED is lit when the relay is energized. It extinguished when any other relay is deenergized. Fails to receive wireless data If the respective zone of the RDE-MZ6 fails to receive wireless data, the red LED will start to flash after 125 minutes.
  • Page 5 (RoHS compliance, compatibility materials composition, packaging, environmental benefit, disposal). Weight 0.482 kg General Color of housing front RAL9003 *) The documents can be downloaded from http://siemens.com/bt/download. 5 / 8 Siemens RDE-MZ6 Wireless multizone receiver CB1N1428en Building Technologies 2017-11-21...
  • Page 6 Connection diagrams 10 A Live, AC 230 V Neutral conductor N1 Wireless multizone receiver RDE-MZ6 Note: Use only valve actuators rated for AC24… 230V. 6 / 8 Siemens RDE-MZ6 Wireless multizone receiver CB1N1428en Building Technologies 2017-11-21...
  • Page 7 10 A Recirculation or pump application (DIP switch: ON/OFF) Live, AC 230 V Neutral conductor N1 Wireless multizone receiver RDE-MZ6 Note: Use only valve actuators rated for AC24… 230V. Dimensions Dimensions in mm 7 / 8 Siemens RDE-MZ6 Wireless multizone receiver...
  • Page 8 Issued by © Siemens Switzerland Ltd, 2013 - 2017 Siemens Switzerland Ltd. Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6300 Zug Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies 8 / 8 Siemens...