  • Page 1: Copyright Notice And Proprietary Rights

    Hydran* 201i System Installation Guide Energy, Lissue Industrial Estate East, Lissue Road, Lisburn, BT28 2RE, United Kingdom Tel: +44 (0) 28 9262 2915, Fax: +44 (0) 28 9262 2202 Email: [email protected], Web: www.gedigitalenergy.com/md.htm 17996 Rev 5, August 2013...
  • Page 2: Table Of Contents

    1.1.6 [SV] (in Swedish) VARNING: ....................5 1.2 Safety Symbols Description ......................... 6 1.3 Preface ................................ 7 1.4 Revisions ..............................7 1.5 Standard GE Energy Warranty ......................8 GENERAL ................................ 10 2.1 Typical Installation ..........................10 2.2 Preferred Locations ..........................11 2.3 Vibration-Absorbing Rubber Pads ....................
  • Page 3: Introduction

    Hydran 201i, and could lead to property damage, personal injury and/or death. • Installation and maintenance of the Hydran 201i must be carried out by qualified personnel only. Please advise station operator prior to maintenance. Working inside the Hydran 201i may trigger unwanted alarms due to parameter changes, power shutdown, system rebooting or electrostatic discharge.
  • Page 4: In German) Warnung

    Hydran* 201i Installation Guide • La instalación y mantenimiento del equipo Hydran 201i se reserva únicamente al personal perfectamente cualificado. Aconseje por favor a operador de la estación antes del mantenimiento. El trabajo dentro del Hydran 201i puede accionar alarmas indeseadas debido a los cambios del parámetro, parada de la energía, sistema que reanuda o descarga electrostática.
  • Page 5: Safety Symbols Description

    • Installation och underhåll av Hydran 201i måste utföras av behörig personal. Råd var god posterar operatören före underhåll. Funktionsduglig insida Hydran 201i kan starta oönskade parameterändringar för larm tack vare, driver avstängning, systemomstart eller elektrostatisk urladdning.
  • Page 6: Preface

    Hydran* 201i Installation Guide 1.3 Preface This manual provides an overview of the installation for the Hydran 201i. For complete explanations on the installation process, see Chapter 7 in the Hydran 201i Instruction Manual. The information in this manual may be used by: −...
  • Page 7: Standard Ge Energy Warranty

    Warranty Period. GE Energy shall not be responsible for removal or replacement of systems, structures or other parts of the Buyer’s facility. If a defect in Products or part thereof cannot be corrected by GE Energy’s reasonable efforts, the parties shall negotiate an equitable adjustment in price with respect to such Products or part thereof.
  • Page 8 GE Energy upon its request in connection with a warranty claim by the Buyer. GE Energy does not warrant any products or services of others designated by the Buyer where such products or services are not normally supplied by GE Energy.
  • Page 9: General

    Hydran* 201i Installation Guide 2 GENERAL 2.1 Typical Installation A typical installation of the Hydran 201i System is presented in Figure 1 below. Figure 1: Typical Installation of the Hydran 201i System Page 10 17996 Rev5, August 2013...
  • Page 10: Preferred Locations

    Hydran* 201i Installation Guide A description of each component: 1. Hydran 201Ci Controller (Hydran 201Ci-C Communications Controller or Hydran 201Ci-1 One -Channel Controller) installed on vibration-absorbing rubber pads (see Figure 3) 2. Full-bore gate or ball valve 3. Hydran 201Ti Intelligent Transmitter 4.
  • Page 11 Hydran* 201i Installation Guide readings; however, the lower operating temperatures and ease of access make this location a valid alternative choice. Figure 2: Mounting Locations of the H201Ti on a Transformer Also, note the following points: 1. The H201Ti must always be easily accessible. The distance between the valve and the ground must exceed 30cm (12in) to install and wire the H201Ti.
  • Page 12 Hydran* 201i Installation Guide The oil temperature at this location must always be below 30°C (86°F). Do not use a 90° elbow to convert a vertical installation to a horizontal installation. It is recommended to set the temperature set point (Temp SetPoint parameter in the Temperature submenu) of the H201 sensor to 45°C (113°F).
  • Page 13: Vibration-Absorbing Rubber Pads

    Hydran* 201i Installation Guide 2.3 Vibration-Absorbing Rubber Pads If vibrations are present, rubber pads (which can be purchased from General Electric) are used on the back of the Hydran 201Ci Controllers; an example is shown in Figure 3 below. Figure 3: Vibration-Absorbing Rubber Pads Page 14 17996 Rev5, August 2013...
  • Page 14: General Warnings

    Hydran* 201i Installation Guide 3 GENERAL WARNINGS 1. Do not separate the Hydran 201Ti Intelligent Transmitters from their respective Hydran 201 sensor. The H201Ti is set at the factory for a specific H201 sensor. To verify whether the two components are paired correctly, consult the serial numbers indicated on the shipping box and/or the Test Certificate and Data Sheet.
  • Page 15 Hydran* 201i Installation Guide Figure 5: H201Ti's Serial Number and Protective Cap 2. Do not remove the protective plastic caps from the sensor and/or the brass adaptor’s threaded extremity until ready to install on the transformer valve. These caps protect the adaptor threads (see Figure 5 above) and the sensor membrane from debris and sharp objects.
  • Page 16 Hydran* 201i Installation Guide Figure 6: Do Not Touch the Membrane 4. Do not block or puncture the sensor’s breathing membrane. Located above the sensor’s connector (see Figure 4), this opening provides oxygen to the gas detector inside the sensor. Blocking or puncturing this membrane damages the sensor permanently, thus voiding the warranty.
  • Page 17 Hydran* 201i Installation Guide Figure 7: Do not Paint the Sensor or Clean it with any Solvent 7. Do not use a pipe wrench or chain wrench to install the sensor. Doing so may cause serious damage to the sensor, thus voiding the warranty. It is recommended to use General Electric’s Hydran 201TW tube wrench (see Figure 8 below) to correctly install the Hydran 201 sensor.
  • Page 18 Hydran* 201i Installation Guide Figure 8: Use the Hydran 201TW instead of a Pipe Wrench Page 19 17996 Rev5, August 2013...
  • Page 19 Hydran* 201i Installation Guide 8. Do not install the H201Ti on the inlet side of the radiator pump (see Figure 9 below). Figure 9: Do Not Install the H201Ti on the Inlet Side of the Radiator Pump 9. Do not use galvanized fittings to install the brass adaptor and the sensor. Galvanized fittings (pipes, reducing bushings, rings, etc.) may react with the oil and produce elevated gas level readings.
  • Page 20 Hydran* 201i Installation Guide 10. Install the H201Ti horizontally; not at an angle, vertically or horizontally using an elbow (see Figure 10 below). Elbows may cause turbulence that can reduce the accuracy of gas level readings. Figure 10: Do Not Install the H201Ti on an Elbow 11.
  • Page 21: Before Installation

    Hydran* 201i Installation Guide If additional openings are made, the protection level given by the CAUTION NEMA / IP rating of the product may be compromised. 13. Do not remove the watertight cap from unused openings of the H201Ci’s enclosure. 4 BEFORE INSTALLATION 1.
  • Page 22 Hydran* 201i Installation Guide 3. It is recommended to mount the Hydran 201Ti horizontally. Ensure the bleed screw is on top (at the “12 o’clock” position); see Figure 13 below. Figure 13: Bleed Screw must be on top, at the 12 O’clock position 4.
  • Page 23 Hydran* 201i Installation Guide 6. The total distance between the H201Ti and the mounting point of the valve must not exceed six times the nominal diameter of the valve (230mm [9 in] for a 38mm [1.5in] valve). See Figure 14 below. Figure 14: Maximum Distance between the Hydran 201Ti and the Valve 7.
  • Page 24: Installation

    Hydran* 201i Installation Guide 5 INSTALLATION 5.1 Tools and Materials Required • Flat-blade screwdriver • General Electric’s Hydran 201TW tube wrench to tighten the Hydran 201 sensor • Pipe wrench to tighten the brass adaptor onto the valve • Allen keys supplied with the Hydran 201Ti •...
  • Page 25 Hydran* 201i Installation Guide Figure 15: Hydran 201Ti Assembly 7. Separate the adaptor and the heating plate. 8. Protect the adaptor’s threads with the supplied plastic cap, see Figure 7. Do not remove the protective plastic caps from the sensor and/or brass adaptor’s threaded extremity until ready to install CAUTION on the transformer valve.
  • Page 26: Installing The Brass Adaptor Onto The Valve

    Hydran* 201i Installation Guide 11. Protect the sensor’s membrane by placing the supplied plastic cap over the sensor’s threads (see Figure 4) 5.4 Installing the Brass Adaptor onto the Valve 1. Wipe the inside of the transformer valve. 2. Cover the adaptor’s threads with PTFE tape; see Figure 12. Use only PTFE tape to seal the threads of both the adapter and the Hydran 201 sensor.
  • Page 27: Opening The Valve

    Hydran* 201i Installation Guide 5.6 Opening the Valve This step should be performed according to company regulations. Proceed carefully to avoid introducing air into the CAUTION transformer. Use a bucket to collect the oil. 1. Using the supplied 5/32-in Allen key, fully close the sensor’s bleed screw and then open it 1/8 of turn.
  • Page 28 Hydran* 201i Installation Guide 5. Wipe all traces of oil from the sensor. Do not use any solvent. CAUTION 6. Inspect the adaptor and sensor for oil leaks. 7. Dispose of the collected oil according to company standards. Page 29 17996 Rev5, August 2013...
  • Page 29: Fastening The Hydran 201Ti To The Brass Adaptor

    Hydran* 201i Installation Guide 5.7 Fastening the Hydran 201Ti to the Brass Adaptor 1. Using the supplied 3/16-in Allen key, fasten the H201Ti’s heating plate to the brass adaptor with the six 1/4-28 cap screws. See Figure 17 below. Figure 17: Fastening the Heating Plate to the Brass Adapter Be careful not to squeeze the nearby electrical wires between the lock washers and the heating plate or not to damage the CAUTION...
  • Page 30: Installing The Cables

    Hydran* 201i Installation Guide 5.8 Installing the Cables 1. Remove the cover from the connection box located under the brass adaptor. 2. As required, install one or two watertight conduit fittings (not supplied) onto the connection box. • One conduit is used to run the supervisory link cable (which connects the H201Ti to the Hydran 201Ci Controller) and, if used, the cable of the H201Ti’s analog output.
  • Page 31 Megger* instrument) on cables connected to an H201Ti or a Hydran 201Ci Controller. Never apply high voltages to the CAUTION components of a Hydran 201i System, as they are equipped with surge protection devices that could be damaged by Megger* tests.
  • Page 32: Installing The Cpu Module

    Hydran* 201i Installation Guide 5.9 Installing the CPU Module 1. Align and carefully insert the CPU module on the central post of the Hydran 201Ti until the connector (at the back of the module) is completely inserted in the mating connector. 2.
  • Page 33: Verifying The Hydran 201Ti Operation

    Hydran* 201i Installation Guide Verifying the Hydran 201Ti Operation 5.10 1. Power up the H201Ti. 2. Verify the operation of the H201Ti by observing the six small LED diagnostic indicators on the right side of the I/O module (from left to right in Figure 19 below): •...
  • Page 34 • The System OK indicator (yellow, DS11) is lit. Note: The H201Ci-1’s display must also be functional. 7. The H201Ti requires set-up (alarms, temperature, data logging) and commissioning for normal use. Please refer to the Hydran 201i System Instruction Manual. Page 35...
  • Page 35: Appendix A: Electrical Connections

    Hydran* 201i Installation Guide 6 APPENDIX A: ELECTRICAL CONNECTIONS Figure 20: Electrical Connections for the Hydran 201Ti Page 36 17996 Rev4, June 2013...
  • Page 36 Hydran* 201i Installation Guide Figure 21: Electrical Connections for the Hydran 201Ci-C Page 37 17996 Rev4, June 2013...
  • Page 37 Hydran* 201i Installation Guide Figure 22: Electrical Connections for the Hydran 201Ci-1 Page 38 17996 Rev4, June 2013...