Hide thumbs Also See for dynalite:
Hardware
Installation Guide

Installing the Data Network

Do NOT connect DALI or mains power to DyNet data terminals.
A
1.
The data cable is connected to all devices as per the project
schematic following correct color code and DyNet terminations.
Devices may be wired in any order.
2.
The recommended connection method is to 'daisy chain' devices in sequence, starting at the first device,
then looping in and out of each device, with a single cable terminating at the last device. There should
not be any branching, and only the first and last device should terminate a single cable, all other devices
should terminate two cables.
3.
The cable tail can be returned to the original distribution board. Ground and Power can be connected in a
loop but D+ and D– must NOT be connected in a loop.
4.
A data cable that is connected to an energized device is live. Do not cut or terminate live data cables.
5.
Maximum data cable current = 2 Amps.
6.
The data cable should be segregated from mains cables by a minimum of 50 mm (2 in) for shielded cable
and 300 mm (12 in) for unshielded cable. If the data cable crosses over any mains cables, it should cross
at 90°.
7.
On Button Panels and Sensors, the Shield wires must be terminated into the shield terminal. Shield wires
are automatically earthed on each controller. For controllers that do not have a shield terminal, the shield
should be twisted together and taped to the cable sheath to maintain continuity.
8.
The maximum recommended length for DyNet cables between two network bridges is 800 m (2620 ft).
For cable runs over 300 m (1000 ft), (or baud rates over 9600 bps) a 120
installed across the D+ and D- terminals of the DyNet connector strip on the first and last device.
14
th
November 2019
Ω
end-of-line resistor must be
www.philips.com/dynalite
Table of Contents
loading

Summary of Contents for Philips dynalite

  • Page 1 For cable runs over 300 m (1000 ft), (or baud rates over 9600 bps) a 120 Ω end-of-line resistor must be installed across the D+ and D- terminals of the DyNet connector strip on the first and last device. November 2019 www.philips.com/dynalite...
  • Page 2 Dynalite Hardware ........Installation Guide ........Page 2 ........Data Cable Termination Strip off outer jackets of cables being daisy chained. Shielded cables only: Cut foil or braid flush to outer jacket. DO NOT cut drain (shield) wire. Strip insulation from each of the conductors.
  • Page 3 Dynalite Hardware ........Installation Guide ........Page 3 ........Recommended cable types For serial port connections, the recommended cable is screened RS-485/Cat5e data cable with at least three twisted pairs, such as DyNet-STP-CABLE-LSZH. Supplier Cable Dynalite DyNet-STP-CABLE-LSZH Dynalite DyNet -SFLAT6-CABLE. limited to 9600 bps. Maximum length 100 m (330 ft).
  • Page 4 Dynalite Hardware ........Installation Guide ........Page 4 ........DyNet-STP-CABLE-LSZH Signal Color Shield Cover with insulated sleeve Green/Green-White Paralleled for Ground Blue Data + Blue-White Data – Orange/Orange-White Paralleled for +12/24 Volts Spare pair can be used as a Brown/Brown-White...
  • Page 5 Dynalite Hardware ........Installation Guide ........Page 5 ........Other control cable types There are two types of data cable commonly used to connect to electronic drivers with LEDs or fluorescent lamps. 1-10V cabling 1-10V mains rated polarized cabling. Single pair figure-eight cable. Positive wire with dashed line.
  • Page 6 Dynalite Hardware ........Installation Guide ........Page 6 ........DALI Topology DALI Broadcast Each independent lighting group requires individual wiring. DALI Addressable DALI bus wiring to DALI enumerated lamp drivers. A DALI universe has up to 64 unique driver addresses.
  • Page 7 Dynalite Hardware ........Installation Guide ........Page 7 ........Installing load controllers The control equipment is connected to potentially lethal power supplies. To ensure safety during system maintenance, Installers must always follow safety installation rules and isolation procedure. When deciding on the mounting position, controllers must be mounted in a dry, well-ventilated location.
  • Page 8 Dynalite Hardware ........Installation Guide ........Page 8 ........Example Installations DIN rail mounted controllers Wall mounted controllers November 2019 www.philips.com/dynalite...
  • Page 9 Dynalite Hardware ........Installation Guide ........Page 9 ........Installing Gateways In multi-story buildings, each floor typically contains an independent network segment called a spur. Spurs can be joined via network gateways to a trunk network (RS-485 or Ethernet) installed in a riser linking all floors together.
  • Page 10 Dynalite Hardware ........Installation Guide ........Page 10 ........Installing user interfaces All devices come with three barcode labels, one on the device, and two extras, one for the plan and one for site documentation. Follow device Installation Instructions to select appropriate physical placement of user interfaces.
  • Page 11 Installing sensors Motion detection positioning A single Dynalite sensor can perform motion detection, light regulation and IR receive simultaneously. Typical detection range is measured at ≤ 25°C (77°F). Range is reduced at higher temperatures. Sensors must receive specified supply voltage (12-18 V or 20-26 V) from the DyNet network. If necessary, add a network power supply to ensure adequate network voltages during day to day fluctuations.
  • Page 12 Dynalite Hardware ........Installation Guide ........Page 12 ........Light regulation positioning When positioning sensors, there are two methods of light regulation to consider: • If the sensor is used for Closed loop sensing, then position the sensor so it sees a mixture of indoor and outdoor light.
  • Page 13 DLLI8I80 has an RS-485 interface and can be connected to eight open/close contacts and eight indicator LEDs. DPMI940-DALI has a DALI interface and can be connected to four open/close contacts (must be used with a Dynalite DALI Multimaster controller). Refer to installation instructions for cable length, safety insulation, requirements, and limitations. DLLI8I8O...
  • Page 14 Installing wireless devices PDZG-E Wireless Gateway The PDZG-E connects up to 25 ZigBee nodes (SNS401CMPs) to the Dynalite system over an Ethernet trunk to a PDEG. This allows communication and control between ZigBee and DyNet devices anywhere on the network.
  • Page 15 For touchscreens, Use the Preset buttons or Sliders on the page to dim channels and confirm that the touchscreen is communicating with the network. All devices are pre-programmed for out-of-the-box operation. Dynalite load controllers (dimmers) are set to provide full output by default, irrespective of having the network connected.
  • Page 16 Dynalite Hardware ........Installation Guide ........Page 16 ........Controller Service Switch functions The relevant Service Switch functions are: • 3 pushes = All Channels 100%. You should do this to normalize the connected driver settings. (DALI Broadcast Channels will setup the connected drivers with Min/Max/PowerOn/SystemFail levels, and 2 second Fade Time).
  • Page 17 Dynalite Hardware ........Installation Guide ........Page 17 ........Fault finding After completing the power up tests, all controllers should react to a single button push message. If not, check for any discrepancies between the installation and the installation instructions and check troubleshooting symptoms.
  • Page 18 Dynalite Hardware ........Installation Guide ........Page 18 ........Troubleshooting Load Controller Issues Probable cause Solution Symptom • Faulty mains supply Check power supply connections to the Controller does not operate at connection. device. Check Fuse if fitted. all. No Service LED activity.
  • Page 19 (incompatibility) DTK622-232). • Third party system (such as Install a suitable conversion such as AMX, DMX or gateway/interface (for example, a Dynalite controls operate Crestron) is streaming DTK622-232). intermittently messages and overriding DyNet. Disable DMX. To ensure safety and prevent damage to the system, appropriate isolation shall be provided. Only SELV/Class 2 (UL) systems shall be connected to non-isolated DyNet interfaces.
  • Page 20 Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.

Table of Contents