ABB ACS355 Quick Installation And Start-Up Manual
ABB ACS355 Quick Installation And Start-Up Manual

ABB ACS355 Quick Installation And Start-Up Manual

Hide thumbs Also See for ACS355:

Quick Links

ABB MACHINERY DRIVES
ACS355 drives
Quick installation and start-up guide
Safety instructions
WARNING! Obey these instructions. If you ignore them, injury or death,
or damage to the equipment can occur. If you are not a qualified
electrical professional, do not do electrical installation or maintenance
work.
Keep the drive in its package until you install it. After unpacking, protect the
drive from dust, debris and moisture.
Use the required personal protective equipment: safety shoes with metal toe
cap, safety glasses, protective gloves and long sleeves, etc.
When the drive or connected equipment is energized, do not do work on the
drive, motor cable, motor, control cables or control circuits.
Do not do work on the drive when a rotating permanent magnet motor is
connected to it. A rotating permanent magnet motor energizes the drive,
including its input and output power terminals.
Electrical safety precautions
1. Clearly identify the work location and equipment.
2. Disconnect all possible voltage sources. Make sure that re-connection is not
possible. Lock out and tag out.
Open the main disconnecting device of the drive.
If you have a permanent magnet motor connected to the drive,
disconnect the motor from the drive.
Disconnect any dangerous external voltages from the control circuits.
After you disconnect power from the drive, always wait 5 minutes to let
the intermediate circuit capacitors discharge before you continue.
3. Protect any other energized parts in the work location against contact.
4. Take special precautions when close to bare conductors.
5. Measure that the installation is de-energized.
Use a multimeter with a minimum impedance of 1 Mohm.
Make sure that the voltage between the drive input power terminals (U1,
V1, W1) and the ground (PE) is close to 0 V.
Make sure that the voltage between the drive output terminals (U2, V2,
W2) and the ground (PE) is close to 0 V.
Make sure that the voltage between the drive DC terminals (BRK+ and
BRK-) and the ground (PE) is close to 0 V.
6. Install temporary grounding as required by the local regulations.
7. Ask the person in control of the electrical installation work for a permit to
work.
See the drive user's manual for the complete safety instructions.
1. Examine the installation area
The drive is intended for cabinet installation and has a degree of protection of
IP20 / UL open type as standard.
Make sure that in the installation area:
There is sufficient space above and below the drive for cooling, and hot air
does not recirculate. Refer to
Free space requirements
The ambient conditions are suitable. Refer to
The mounting surface is non-flammable and can hold the weight of the drive.
Refer to
Dimensions and weights
.
Materials near the drive are non-flammable.
There are no sources of strong magnetic fields, such as high-current single-
core conductors or contactor coils near the drive. A strong magnetic field
can cause interference in the operation of the drive.
2. Install the drive
You can install the drive with screws or to a DIN rail [Top Hat, W x H = 35 ×
7.5 mm (1.4 × 0.3 in)].
Make sure that there is a minimum of 75 mm (3 in) of free space above and
below the drive for cooling air.
When placing drives on top of each other in a panel or cabinet, make sure
that the hot air from the drives below do not directly enter the drive above.
WARNING! Do not install the drive upside down. Make sure that the
cooling air exhaust (at the top) is above the cooling air inlet (at the
bottom).
To install the drive with screws
1. Cut out the mounting
template from the
package and use it to
mark the locations for
the mounting holes.
2. Make the holes for the
mounting screws and
install suitable plugs or
anchors.
3. Start to tighten the
screws into the
mounting holes.
4. Place the drive onto
the mounting screws.
5. Tighten the mounting
screws securely.
To install the
drive to a DIN
rail
1.
Place the top of the
drive onto the DIN
installation rail in an
angle as shown in
figure.
2. Set the drive against
the wall.
3. To remove the drive,
press the release lever
on top of the drive.
3. Attach the clamping plates
1. Fasten the clamping
plate to the plate at
the bottom of the drive
with the provided
screws.
2. Frame sizes R0...R2:
Fasten the I/O
clamping plate to the
clamping plate with
the provided screws.
4. Measure the insulation resistance
Measuring the insulation is typically not required in North America.
Drive: Do not do voltage tolerance or insulation resistance tests on the drive,
because this can cause damage to the drive.
Input power cable: Before you connect the input power cable, measure the
insulation of the input power cable. Obey the local regulations.
Motor and motor cable:
1. Make sure that the motor cable is connected to the motor and disconnected
from the drive output terminals U2, V2 and W2.
2. Use a voltage of 1000 V DC to measure the
insulation resistance between each phase
conductor and the protective earth conductor.
The insulation resistance of an ABB motor must
be more than 100 Mohm (at 25 °C/77 °F). For the
insulation resistance of other motors, refer to
the manufacturer's documentation. Moisture in
the motor decreases the insulation resistance.
If you think that there is moisture in the motor,
dry the motor and do the measurement again.
5. Select the cables
Input power cable: IEC/EN 61800-5-1 requires two protective earth (ground)
conductors. Prefer a symmetrical shielded cable (VFD cable).
Motor cable: Use a symmetrical shielded cable (VFD cable) for the best EMC
performance and to meet the European EMC requirements.
Control cable: Use a double-shielded twisted-pair cable for analog signals. Use a
double- or single-shielded cable for digital, relay and I/O signals. Do not mix 24 V
and 115/230 V signals in the same cable.
6. Connect the power cables
Connection diagram (shielded cables)
PE
U1/L V1/N W1
5)
4)
PE
1 360-degree grounding of the cable shield. Required for the motor cable and brake
resistor cable, recommended for the input power cable.
2 Use a separate grounding cable if the conductivity of the cable shield is not sufficient
(smaller than the conductivity of the phase conductor) for the protective grounding, or
there is no symmetrically constructed grounding conductor in the cable.
3 In one-phase installations, connect phase to U1/L, neutral to V1/N and leave W1
disconnected.
4 Use two grounding conductors if the cross-section of a single grounding conductor is
less than 10 mm2 Cu or 16 mm2 AI (IEC/EN 61800-5-1). For example, use the cable shield
in addition to the fourth conductor.
5 Use a separate grounding cable (line side) if the conductivity of the fourth conductor or
shield is not sufficient for the protective grounding.
.
Ambient conditions
.
Connection procedure (shielded cables)
WARNING! Make sure that the drive is compatible with the earthing
system. You can connect all drive types to a symmetrically grounded
TN-S system. For other systems, see the drive user's manual.
1. Strip the input
power cable. Ground
the cable shield (if
any) under the
grounding clamp.
Twist the cable
shield into a bundle,
mark it accordingly
and connect it to the
grounding terminal.
Connect other
grounding
conductors (PE) to the grounding terminal. Connect the phase conductors to
the U1, V1 and W1 terminals.
2. Strip the motor cable. Ground the cable shield
under the grounding clamp. Twist the motor
cable shield into a bundle, mark it accordingly
and connect it to the grounding terminal.
Connect the phase conductors to the U2, V2 and
W2 terminals.
3. If applicable, connect the brake resistor cable to
the BRK+ and BRK- terminals. Use a shielded
cable and ground the shield under the
grounding clamp.
4. Mechanically attach the cables on the outside of
the drive.
R0...R2
ohm
1000 V DC
Drive
BRK+ BRK-
U2 V2 W2
1)
1)
U1
Optional brake
3 ~
resistor or
common DC
Motor
3)
L1/L L2/N L3/-
Frame size
U1, V1, W1, U2, V2, W2,
R0...R2
R3
R4
7. Connect the control cables
Default I/O connections
The diagram shows the I/O connections when parameter
(ABB STANDARD).
X1A
1
2
3
4
1...10 kohm
5
6
7
8
max.500 ohm
4)
9
10
11
12
13
14
15
16
X1B
17
18
19
20
21
22
U1
M
X1C:STO
V1
3~
1
W1
PE
2
3
100 M h
4
1)
AI1 is used as a speed reference if vector
mode is selected.
2)
See parameter group
12 CONSTANT
SPEEDS
:
DI3
DI4 Operation (par.)
0
0
Set speed through AI1
1
0
Speed 1 (
1202
1203
0
1
Speed 2 (
1204
1
1
Speed 3 (
Connection procedure
To prevent inductive coupling, keep the
signal wire pairs twisted all the way up
to the terminals.
1. Remove the terminal cover.
2. Strip the outer insulation of the
cable and ground the bare shield
360 degrees under the clamp.
3. Connect the conductors to the
correct control terminals. Torque
2)
the terminals to 0.4 N·m (3.5 lbf·in).
4. For double-shielded cables, twist
also the grounding conductors of
each pair in the cable together and
V1
W1
connect the bundle to the SCR
terminal (terminal 1).
5. Mechanically attach the control
cables on the outside of the drive.
6. If you are going to use an optional
Safe Torque Off function, connect
STO conductors to the correct
terminals. Use a tightening torque
of 0.4 N·m (3.5 lbf·in).
7. Unless you need to install the
optional fieldbus module, slide the
terminal cover back into place.
8. Install the fieldbus
module (optional)
See the drive user's manual.
9. Install the control panel (if any)
10. Start up the drive
WARNING! Before you start up the drive, make sure that the installation
is complete. Make sure that the cover of the drive is in place. Make sure
also that the motor does not cause danger when it starts. Disconnect
the motor from other machinery, if there is a risk of damage or injury.
There is an extensive installation checklist in the drive user's manual.
Start up without a control panel
1. Apply input power and wait for a moment.
2. Check that the red LED is not lit and the greed LED is lit but not blinking.
The drive is now ready for use.
Start up with a control panel (manual start-up)
You can use the basic control panel or the assistant control panel. The
instructions below are valid for both control panels, but the displays shown are
the basic control panel displays, unless the instruction applies to the assistant
control panel only.
Before you start, ensure that you have the motor nameplate data at hand.
POWER-UP
Apply input power.
The basic control panel powers up into the
Output mode.
The assistant control panel asks if you want to
run the Start-up assistant. If you press
Start-up assistant is not run, and you can
continue with manual start-up in a similar
manner as described below for the basic control
panel.
Tightening torques
PE
BRK+ and BRK-
0.8 N·m (7 lbf·in)
1.2 N·m (11 lbf·in)
1.7 N·m (15 lbf·in)
1.2 N·m (11 lbf·in)
2.5 N·m (22 lbf·in)
1.2 N·m (11 lbf·in)
00353783 L
9902
has value 1
SCR
Signal cable shield (screen)
1)
AI1
Output frequency reference: 0...10 V
GND
Analog input circuit common
+10V
Reference voltage: +10 V DC, max. 10 mA
AI2
Not in use by default. 0...10 V
GND
Analog input circuit common
AO
Output frequency value: 0...20 mA
GND
Analog output circuit common
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
GND
Auxiliary voltage output common
DCOM
Digital input common
DI1
Stop (0) / Start (1)
DI2
Forward (0) / Reverse (1)
2)
DI3
Constant speed selection
2)
DI4
Constant speed selection
3)
DI5
Acceleration and deceleration selection
ROCOM
Relay output 1
No fault [Fault (-1)]
RONC
RONO
DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
DOOUT
DOGND
OUT1
STO (Safe torque off) connection
OUT2
IN1
IN2
3)
0 = ramp times according to parameters
2202
2203
and
. 1 = ramp times according to
parameters
2205
and
2206
.
4)
360 degree grounding under a clamp.
Tightening torque: 0.4 N·m / 3.5 lbf·in.
)
)
)
00
.
REM
OUTPUT
REM
CHOICE
EXIT
, the
Do you want to
use the start-up
assistant?
Yes
No
EXIT
00:00
Hz
FWD
OK
loading

Summary of Contents for ABB ACS355

  • Page 1 DOGND conductor and the protective earth conductor. X1C:STO The insulation resistance of an ABB motor must WARNING! Obey these instructions. If you ignore them, injury or death, be more than 100 Mohm (at 25 °C/77 °F). For the OUT1 STO (Safe torque off) connection or damage to the equipment can occur.
  • Page 2 1000 m [3281 ft]) 3AXD50000622467 Rev A EN 2020-04-21 Surrounding air -10…+50 °C (14…122 °F). If the temperature is more than 40 °C © Copyright 2020 ABB. All rights reserved. temperature (104 °F), output derating is necessary. No frost permitted. Relative humidity...