Honeywell Ex-Or MLS Series Connecting Manual

Connect digital remote detectors for cdw12u5, cdh4u5 & cdh8u5 lcms

Quick Links

Connect - Lighting control modules and plug-in connection centres
MLS Connect Digital Remote Detectors
for CDW12U5, CDH4U5 & CDH8U5 LCMs
CDW12U5 Programmable Connection Centres and
CDH4U5/CDH8U5 Hard-Wired Intelligent Lighting Control
Modules support a range of dedicated high-performance
presence detectors. Detectors contain a photocell to
monitor total light levels, allowing the light output of
dimmable luminaires to be adjusted to suit the natural light
level available.
The range of detectors for remote mounting encompasses
both PIR and Microwave technology:
o
MLS2001CDR - 360 PIR presence detection
o
MLS2401CDR - 360 microwave presence detection
MLS2500CDR - directional microwave presence detection
All contain an infrared port that can be used both for local
control from a hand-held device when in service and for
initial commissioning of the CDW12U5/CDH4U5/CDH8U5
Intelligent LCM system.
Detectors connect to the LCM via RJ45 patch leads and all
are SELV devices when properly installed and connected.
Ready-made patch leads are available in lengths of 3m,
5m and 10m.
T: +44 (0)1942 719229 F: +44 (0)1942 272767 E: [email protected] & [email protected] www.ex-or.com
MLS2001CDR
MLS2401CDR
Commissioning
With the CDW12U5 and CDH4U5/CDH8U5 LCM systems,
all configuration information is held within the Connection
Centre itself, not the individual detectors. Most of the
parameters are set up with the aid of a dedicated
progamme running on a portable PC which communicates
with the LCM either by an infrared link, via one of the
attached detectors, or by a specialised serial link into the
LCM itself.
When setting the actual light levels around which dimming
or switching decisions are made, the system utilises the
same simple and convenient method as used for Ex-Or's
traditional stand-alone detectors. An infrared programming
tool (HP2000 or HC5) is used to set the controlling or
switching set-point for the photocell. The setting is then
transmitted from the detector to the LCM where it is
uniquely associated with that particular detector. The
setting will be preserved in the event of power failure. All
settings can be re-programmed any number of times.
(See 'Setting the Regulating Photocell' and 'Setting the
Switching Photocell' sections of installation instructions for
details of setting procedure.)
Please check www.ex-or.com to ensure this is the most
recent issue - Ref: D4123B
Ex-Or, Haydock Lane, Haydock, Merseyside WA11 9UJ
MLS2500CDR
Surface-mount versions
also available (suffix SM)
loading

Summary of Contents for Honeywell Ex-Or MLS Series

  • Page 1 Switching Photocell’ sections of installation instructions for details of setting procedure.) Please check www.ex-or.com to ensure this is the most recent issue - Ref: D4123B Ex-Or, Haydock Lane, Haydock, Merseyside WA11 9UJ T: +44 (0)1942 719229 F: +44 (0)1942 272767 E: [email protected] & [email protected] www.ex-or.com...
  • Page 2 Positioning, Fixing & Connections Positioning Notes View on back of MLS2001CDR Do not mount within 0.25m of a luminaire. MLS2401CDR The MLS2401CDR should not be positioned on a pitch narrower than 5m. Detectors Microwave detectors (MLS2401CDR & MLS2500CDR) are extremely sensitive to movement and must be installed on a rigid surface that will not itself be subject to movement.