GE MRV-S Series Installation Instructions

Plenum, slim duct models
Available languages

Available languages

Quick Links

1. Dimensions
Supply air outlet
A
F
Return air inlet
H
C
Model
A
B
Supply
AD07SL2VH*
35
7-1/2
PAD0890SA
AD09SL2VH*
(890)
(190)
AD12SL2VH*
MVAD007MV2AA
Return
MVAD009MV2AA
PAD0890RA
MVAD012MV2AA
Supply
AD18SL2VH*
47-5/8
7-1/2
PAD1210SA
MVAD018MV2AA
(1210)
(190)
MVAD024MV2AA
Return
PAD1210RA
2. Rough Opening Dimensions:
A
E
F
I
J
Model
A
B
C
Supply
AD07SL2VH*
30-1/2
5-7/8
7-5/8
PAD0890SA
AD09SL2VH*
(776)
(150)
(194)
AD12SL2VH*
MVAD007MV2AA
Return
MVAD009MV2AA
PAD0890RA
MVAD012MV2AA
Supply
AD18SL2VH*
43-1/8
5-7/8
7-5/8
PAD1210SA
MVAD018MV2AA
(1096)
(150)
(194)
MVAD024MV2AA
Return
PAD1210RA
Ceiling opening
Plenum opening
Ceiling opening
Plenum opening
C
D
E
F
G
H
35
11-1/2
3-1/2
25-1/4
6
29-7/8
(890)
(291)
(90)
(640)
(152)
(760)
47-5/8
11-1/2
3-1/2
37-3/4
6
42-1/2
(1210)
(291)
(90)
(960)
(152)
(1080)
D
C
G
D
E
F
G
H
I
J
3/4
7/8
1-5/8
32-1/4
10-1/4
2-3/8
1-1/4
(20)
(21)
(40)
(820)
(260)
(60)
(31)
3/4
7/8
1-5/8
44-7/8
10-1/4
2-3/8
1-1/4
(20)
(21)
(40)
(1140)
(260)
(60)
(31)
Installation Instructions
Plenum, Slim Duct Models
3. Typical Configurations
Supply and return down
Supply down, return rear
Supply side, return down
Supply side, return rear
NOTES:
Maintain 36" (915 mm) between supply outlet and re-
turn inlet for floor and ceiling locations.
If the supply outlet and the return inlet are on a com-
mon wall, one must be 36" (915 mm) higher than the
other.
All duct longitude and latitude joints must be sealed.
Duct insulation values should meet local code require-
ments.
The cabinet of the Slim Duct unit must be insulated if
installed in a non-conditioned space.
4. Set the Blocking in the Ceiling to Pro-
tect the Indoor Unit
The inside of two sides of the celing must
be sealed.
31-5000441 Rev. 0 09-19 GEA
loading

Summary of Contents for GE MRV-S Series

  • Page 1 Installation Instructions Plenum, Slim Duct Models 1. Dimensions 3. Typical Configurations Supply air outlet Ceiling opening Plenum opening Supply and return down Supply down, return rear Return air inlet Ceiling opening Plenum opening Supply side, return down Supply side, return rear Model Supply AD07SL2VH*...
  • Page 2 Installation Instructions 5. Minimum Clearances 7. Swing Motor Wiring, FlexFit Models 39-3/8 INDOOR UNIT PCB SWING MOTOR-UP/DOWN CN16 CN15 electrical box SWING MOTOR-UP/DOWN CN14 SWING MOTOR-LEFT/RIGHT accessing opening >100 Connect up/down swing motors to CN15 and CN16. If the unit location is not readily accessible, provide a 24” The left/right swing motor goes to CN14.
  • Page 3 Instructions d’installation Modèles à plénum, conduits étroits 1. Dimensions 3. Configurations typiques Sortie d’air fourni Ouverture du plafond Ouverture du plénum Air fourni et repris dans le bas Entrée d’air repris Ouverture du plafond Ouverture du plénum Air fourni dans le bas, air repris en arrière Air fourni sur le côté, air repris dans le bas...
  • Page 4 Instructions d’installation 5. Dégagements minimaux 7. Câblage du moteur oscillant, modèles FlexFit 39-3/8 CARTE DE CIRCUIT MOTEUR OSCILLANT - HAUT/BAS Boîte électrique UNITÉ INTÉRIEURE CN16 CN15 MOTEUR OSCILLANT - HAUT/BAS CN14 MOTEUR OSCILLANT - GAUCHE/DROITE Orifice d’accès >100 Si l’emplacement de l’unité n’est pas aisément accessible, Connecter les moteurs haut/bas à...

This manual is also suitable for:

Flexfit seriesAd07sl2vh seriesAd09sl2vh seriesAd12sl2vh seriesAd18sl2vh seriesMvad007mv2aa ... Show all