PACSystems RX3i Genius
PACSystems RX3i Genius Communications Gateway
User Manual GFK-2892F
Communications
Gateway
User Manual
GFK-2892F
March 2019
For Public Disclosure
Table of Contents
loading

Summary of Contents for GE GFK-2892F

  • Page 1 Automation & Controls Programmable Control Products PACSystems RX3i Genius PACSystems RX3i Genius Communications Gateway User Manual GFK-2892F Communications Gateway User Manual GFK-2892F March 2019 For Public Disclosure...
  • Page 2 Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced herein.
  • Page 3 Online technical support and GlobalCare www.geautomation.com/support Additional information www.geautomation.com Solution Provider [email protected] Technical Support If you have technical problems that cannot be resolved with the information in this manual, please contact us by telephone or email, or on the web at www.geautomation.com/support...
  • Page 5: Table Of Contents

    Table of Contents PACSystems RX3i Genius Communications Gateway User Manual GFK-2892F Table of Contents ................................i Table of Figures ................................iv Introduction ............................... 1 Chapter 1 Revisions in this Manual .......................... 2 Acronyms and Abbreviations ........................ 3 PACSystems Documentation......................... 4 Description ..............................
  • Page 6 Clearing the RX3i Fault Tables ........................47 COMMREQ/Data_Init_Comm Programming ..................49 Chapter 6 COMMREQs and Passwords ......................... 50 Programming for a COMMREQ Communication Request ............. 50 COMMREQ Command Block Format ....................51 COMMREQ Command Block Contents ....................52 PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 7 COMMREQ #20: Write Point Command ....................75 COMMREQ #21: Read Block I/O Command ................... 76 COMMREQ #22: Read Map Command ..................... 80 COMMREQ #23: Write Map Command ....................81 COMMREQ #24: Read Data Command ....................82 COMMREQ #25: Write Data Command ....................83 GFK-2892F March 2019...
  • Page 8: Table Of Figures

    Figure 28: Genius Discrete Block Failed Switch Fault Display (Example) ................47 Figure 29: Genius Analog Block Over Range Fault Display (Example) ..................47 Figure 30: Ladder Logic to Clear Circuit Fault ............................ 59 Figure 31: Data_Init_Comm to Clear Circuit Fault ..........................60 PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 9: Chapter 1 Introduction

    PROFINET and Genius I/O. Introductory material may be found in this chapter. Chapter 2 provides installation and set-up information. Chapter 3 provides configuration instructions. Chapter 4 describes system operation. Chapter 5 provides diagnostic information. Chapter 6 covers the use and format of ladder logic COMMREQ instructions. GFK-2892F March 2019...
  • Page 10: Revisions In This Manual

    Correction to Figure 22: Genius Hot Standby Redundancy to indicate CPU type is CRU 2015 and RMX modules are required. • Clear All Faults can now be dispatched to all blocks on the bus in a single command. See Section 6.4.6. Initial release 2014 PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 11: Acronyms And Abbreviations

    Ethernet Media Redundancy Protocol Non-Real-Time PROFINET Communication PCIM Personal Computer Interface Module Proficy® Machine Edition PROFINET Controller PLC Protocol Variables Real-Time PROFINET Communication Genius Serial Bus Address Secure Digital Card Slot Shielded Twisted Pair Unshielded Twisted Pair GFK-2892F March 2019...
  • Page 12: Pacsystems Documentation

    VersaMax System Genius Network Interface Unit User’s Manual GFK-1535 In addition to these manuals, datasheets and product update documents describe individual modules and product revisions. The most recent PACSystems documentation is available on the GE Automation & Controls support website www.geautomation.com/support. PACSystems RX3i Genius Communications Gateway...
  • Page 13: Description

    Thus, when correctly configured, the entire Genius Bus, including the GCG001 itself, becomes visible to the controlling PLC. Note that the GCG001 operates only with GE PLC PROFINET IO Controllers. PROFINET operates on an Ethernet network. If the Ethernet network or Genius serial bus communications are lost, the GCG001 manages I/O states according to the individual module configurations.
  • Page 14: Product Overview

    SHLD GENIUS Figure 2: GCG001 Module Note: Although the hardware supports the 10/100BASE TX Ethernet standard, PROFINET I/O over wired infrastructure must be 100Mbps full-duplex or faster. 10Mbps should not be used for PROFINET. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 15: Specifications

    If configured to support Genius Hot Standby, the loss of a single GCG001 will be tolerated; otherwise not. For system standards, general operating specifications, and installation requirements, refer to the PACSystems RX3i System Manual, GFK-2314. GFK-2892F March 2019...
  • Page 16: Controls And Indicators

    Ethernet Port Indicator LEDs: LINK, PROFINET ETHERNET Ports Genius Bus Indicator LEDs: Genius Bus SER 1 Connector SER 2 SHLD SHLD GENIUS 24 V dc Power Connector Figure 3: Genius Gateway GCG001 Front Panel View PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 17: Mounting

    Align the two mounting screws of the module with the mounting holes in the panel. Using a Philips screwdriver, tighten the two screws to a maximum torque of 0.5 Nm (4.4 in-lbs). Figure 4: GCG001 Panel Mount Diagram GFK-2892F March 2019...
  • Page 18: Profinet Operation Overview

    PROFINET Communications Communications on an RX3i PROFINET network use the standard PROFINET communications described in this section. Note, however, that the Genius Gateway GCG001 is constrained to work only with GE PROFINET PLC products. Application Relationships Before a PROFINET IO-Controller can exchange data with a PROFINET IO-Device such as the GCG001, an Application Relationship (connection) must be established between the devices.
  • Page 19: Figure 6: Real-Time & Non-Real-Time Data Types

    Translates PROFINET packages that are sent by the PROFINET Controller into Genius Datagrams. This includes Datagrams that originated at the PLC through use of COMMREQ or Data_Init_Comm instructions. For example, a COMMREQ is used to generate a Clear Fault Report datagram. GFK-2892F March 2019...
  • Page 20: Figure 7: Plc - Gcg - Genius Scan Cycles

    PROFINET Controller module. This input data is then available for use by the application logic. After the logic solution, the CPU output scan writes the outputs to the PROFINET Controller. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 21 Fast ring-break detection is not fully functional until all MRP clients have received their MRP configuration. For a discussion of ring-break detection and bumpless operation with MRP, refer to sections 6.1.1 and 6.1.2 in the PACSystems RX3i & RSTi-EP PROFINET I/O Controller Manual, GFK-2571K or later. GFK-2892F March 2019...
  • Page 22: System Limits

    Refer to the Genius I/O System and Communications User's Manual, GEK-90486-1 for information on how much I/O, and which type of I/O, need to be allocated to Genius devices. PME (v8.0 or later) takes into account both system limits and I/O allocation. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 23: Operational Differences Vs. Genius Bus Controller

    12. Beginning with V2.2.4.1 Fault Status Bits are available to monitor each device on the bus. Refer to Section 5.1.3 for additional information. For Dual Bus Redundancy, GCG001 firmware version 2.2.0 or later is required; for all other redundancy modes, version 1.1.0 (minimum) is required. GFK-2892F March 2019...
  • Page 24: Supported Genius Devices

    Prior to GCG version 2.2.4.2, in PME Hardware Configuration, configure the BBD100 as a BBD101. Refer to Series 90-70 Remote I/O Scanner User’s Manual, GFK–0579, Chapter 1 for a list of S90-70 modules supported by BEM733. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 25: Chapter 2 Installation

    As the consignee, it is your responsibility to register a claim with the carrier for damage incurred during shipment. GE Automation & Controls will cooperate fully with you, however, should such action be necessary. After unpacking the RX3i equipment, record all serial numbers. Serial numbers are required if you should need to contact Customer Care during the warranty period.
  • Page 26: Installation In Hazardous Areas

    Group IIC and rated IP54. The enclosure shall only be able to be opened with the use of a tool. ATEX Marking II 3 G Ex nA IIC T4 X Ta: 0 - 60C PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 27: Module Installation

    Connector pin-outs are identified on the module, as indicated at right. The +24 VDC module draws 0.2 A maximum current. (Use for cable tie-downs) 24 Vdc Power Connector Figure 9: GCG001 Power Connector GFK-2892F March 2019...
  • Page 28: Figure 10: Daisy Chain Genius Bus Wiring

    Serial 2, with SHLD IN unterminated, (as shown above right). The value of the termination resistor must match the impedance of the Genius Bus cable. Note: Whenever the GCG001 Genius terminal blocks are removed from the faceplate, the continuity of the Genius Bus is disrupted. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 29: Gcg001 Module Removal

    GCG001. This permits the PROFINET configuration of the removed module to be transferred to the successor module. • Once the successor module has been mounted, the original Power, PROFINET and Genius connections may be restored to it. GFK-2892F March 2019...
  • Page 30: Light-Emitting Diode (Led) Indications

    A fault or other PROFINET diagnostic data exists on the Gateway CONNECT — indicates status of the connection to a PROFINET controller. One or more connections with GE PROFINET Controllers have been established to this device. Device trying to connect to a controller.
  • Page 31: Fault Notifications

    Note that when a GCG001 is replaced by a successor GCG001, it is important to ensure that the successor is configured for PROFINET in the same manner as its predecessor. The quickest way to ensure this is to remove the SD Card from the original and insert it into the successor GCG001. GFK-2892F March 2019...
  • Page 32: Configuring The Genius Gateway To Operate With The Rx3I Cpu

    GFK-2571, for adding devices to the PROFINET IO Network. The GCG001 will be one of those devices. 4) Note that each IO Device connected to the GCG001 will be mapped per the RX3i PROFINET Controller configuration. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 33: Ethernet Port Connections

    Cables may be up to 100 meters in length. Cables for 100BaseTX must be data grade Category 5 or better unshielded twisted pair (UTP) or shielded twisted pair (STP). 10BaseT may be used for the general Ethernet traffic, but not for PROFINET communications. GFK-2892F March 2019...
  • Page 34: Firmware Updates

    PC and copy the new firmware to the SD Card. The ZIP file containing the GCG001 firmware upgrade may be found on the GE Automation & Controls Product Support web-site http://www.geautomation.com. Unzip the file as shown in the following figure.
  • Page 35: Chapter 3 Configuration

    • Serial or Ethernet cable for connecting the computer hosting PME to the RX3i CPU. • General Station Description Markup Language (GSDML) file for the GCG001, available from GE’s Automation and Controls support website, http://www.geautomation.com. 3.2 Configuration Overview GCG001 in Simplex Genius Bus Configuration The steps involved in configuring a GCG001 Genius Gateway are as follows: If you haven’t already done so, use PME to add a PROFINET IO-Controller (IC695PNC001) to the...
  • Page 36: Figure 14: Hardware Configuration Expanded Tree

    When Output at Startup is set to Disabled, no output data is sent to the Genius devices when the PLC transitions from STOP to RUN. In this case, the Enable/Disable Outputs COMMREQ must be used to enable outputs on the Genius bus. Figure 16: Genius Gateway Parameters PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 37: Figure 17: Change Module List For Genius Gateway Gcg001

    Figure 17: Change Module List for Genius Gateway GCG001 12. Select individual Genius I/O devices from the right-hand panel of Figure 17 and then drag/drop them into the appropriate location row on the left-hand side, resulting in Figure 18. GFK-2892F March 2019...
  • Page 38: Figure 18: Populating The Genius Io Devices To Be Controlled By The Genius Gateway

    Add the BEM733 to the Genius Bus configuration as described above. Drill down into the BEM733. A display of rack I/O will be presented (Figure 19). Figure 19: Populating Slots in S90-70 Rack Controlled by Remote I/O Scanner (BEM733) PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 39 18. In PME, store the Hardware Configuration to the RX3i CPU. This act also stores the GCG001 configuration data to the PNC001. GCG001 firmware version 2.0.0 is required to support GNIU; GCG001 firmware version 2.2.0 is required for FBIU. GFK-2892F March 2019...
  • Page 40: Figure 20: Pme Display Of Complete Genius Gateway Configuration

    Chapter 3. Configuration The following screenshot shows a completed configuration. Figure 20: PME Display of Complete Genius Gateway Configuration PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 41: Genius Hot-Standby Redundancy Configuration

    The block prefers outputs sent by the GCG with SBA#31. If those outputs are not available, the block uses outputs from the GCG with SBA#30. If no outputs from either GCG are available, outputs either Hold Last State or default (as configured). GFK-2892F March 2019...
  • Page 42: Genius Duplex Configuration

    Devices configured as a BSM Controller will automatically switch away from a defective bus, expecting that the alternate bus is intact and can function properly. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 43: Genius Hot Standby Dual Bus Configuration

    Such devices would not employ a BSM. • The two CPUs are synchronized to accomplish Hot Standby. In Figure 21, a dual RMX link is diagrammed. For a CPE400, the synchronization would be performed over LAN3. GFK-2892F March 2019...
  • Page 44: Figure 21: Gcg001 Units Deployed In Genius Hot Standby Dual Bus Redundancy

    Chapter 3. Configuration Figure 21: GCG001 Units Deployed in Genius Hot Standby Dual Bus Redundancy PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 45: Chapter 4 System Operation

    HHM can command the target device to change to a new baud rate, which will take effect upon power cycling the device. Remember to then change the baud rate of the HHM to the new baud rate. GFK-2892F March 2019...
  • Page 46: Redundancy

    Discrete outputs in the I/O controlled by the GR7 and GNIU also behave in this way. The GCG001 can be used to achieve Genius Dual Bus Redundancy when used in conjunction with application code provided by GE Automation & Controls. Please contact Customer Support for assistance. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 47: I/O Scans

    All of the I/O scans described above are asynchronous and may vary depending on the path through the RX3i logic, traffic on the PROFINET and traffic on the Genius Bus. Should I/O update rates be a concern for the application, it would be prudent to perform a worst-case analysis of the interacting scan cycles. GFK-2892F March 2019...
  • Page 48: Alarms

    Genius Device will continue to indicate Fault conditions; however, no datagram will be issued for each fault occurrence. An intermediate solution is to periodically query each such device with a Read Diagnostics datagram (Section 6.4.4) and parse the response in order to detect faulted circuits. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 49: Chapter 5 Diagnostics

    Genius Status Bits for GCG Fault Status Bits for GCG Gateway Status Bits for GCG • Module LED Indicators • Power-up Module Restart Problems During Power-up and Reset Transitioning from Firmware Update Mode to Normal Operating Mode GFK-2892F March 2019...
  • Page 50: Status Data

    Indicates that the GCG001 is an MRP Client (if MRP is enabled), or that MRP is not enabled. MRP Role Indicates role is that of an MRP Manager – this is not a possible role for the GCG001. Always off 12-31 Reserved PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 51: Genius Status Data

    SBA is configured but is offline, or the device at this SBA is configured and online but has one or more diagnostic faults present. 5.2 Module LED Indicators Refer to Section 2.4.4 above for a description of LED indications. GFK-2892F March 2019...
  • Page 52: Power-Up

    GCG001 firmware load mode. Whenever the GCG001 is powered up without this button being depressed, normal operating mode will commence following power-up testing and initialization. Cycling power will transition the module from one mode to the other, depending on the condition of the pushbutton. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 53: Module Faults In The Rx3I I/O Fault Tables

    GCG001 itself and b) for the Genius bus devices it controls and c) for Fault status related to devices on the bus. These are not to be confused with the entries in the I/O Fault Table. GFK-2892F March 2019...
  • Page 54: Fault Types Reported To The Rx3I Controller I/O Fault Table

    Configuration mismatch in Field Control I/O Station 1032 Mismatch between configured Genius device and actual device present. 1033 Genius device is present on the bus, but is not in the configuration. Figure 27 - I/O Fault Table Message Identifiers PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 55: Clearing The Rx3I Fault Tables

    This action merely clears the I/O Fault Table temporarily. Use the Genius HHM or COMREQs in the PLC program to exercise I/O points that had previously exhibited faults, and where the underlying field fault condition has already been corrected. GFK-2892F March 2019...
  • Page 57: Chapter 6 Commreq/Data_Init_Comm Programming

    It performs the same functions as are described in this Chapter. An example is shown at Figure 31. For additional information about Genius datagrams, refer to the Genius I/O System and Communications Manual, GEK-90486–1, which describes Genius Datagrams in detail. GFK-2892F March 2019...
  • Page 58: Commreqs And Passwords

    COMMREQ to the targeted PROFINET Controller is complete before sending it another one. Failure to do this may result in improper operation of the PROFINET Controller. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 59: Commreq Command Block Format

    COMMREQ that transfers a 128–byte datagram. Most Command Blocks are much shorter. The table in Section 6.3.3 gives an overview of the contents of each type of COMMREQ that may be sent to a PROFINET Controller for transfer to a Genius Gateway. GFK-2892F March 2019...
  • Page 60: Commreq Command Block Contents

    Targeted Genius Device Number (0-31). The serial bus address + 8 address (SBA) of the Genius device connected to the targeted Genius Gateway. Parameters of the specific Command Number (see thru address + 78 following sections in this chapter). PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 61: Commreq Commands Supported By The Genius Gateway (Gcg001)

    6.4.14 Read Map 6.4.15 Write Map 6.4.16 Read Data 6.4.17 Write Data 6.4.18 Note that while the GCG001 does support the indicated COMMREQs, the devices which respond to such COMMREQs are not currently supported by the GCG001 GFK-2892F March 2019...
  • Page 62: Commreq Command Block Quick Reference

    6.3.1 1-255 0-31 Read Block see 6.3.1 1-255 0-31 Read Map see 6.3.1 1-255 0-31 Write Map see 6.3.1 1-255 0-31 Read Data see 6.3.1 1-255 0-31 Write Data see 6.3.1 1-255 0-31 PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 63: Mechanics Of The Commreq Instruction

    If there are errors in the portion of the Command Block used specifically by the PROFINET Controller or Genius Gateway (for example, the Device Number entered is incorrect), these errors are reflected in the value returned in the Status Block location, not in the FT output. GFK-2892F March 2019...
  • Page 64 Command not supported. 4096 00010000 00000000 Command failed. 32769 00100000 00000001 Unknown Task ID rejected by the PNC COMMREQ Manager. 32770 00100000 00000010 PNC COMMREQ Manager got an internal error while dispatching the request. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 65 An internal error has been detected in the PNC COMMREQ firmware. 0x22 The COMMREQ request is not supported by the specified Genius device. The data type code specified for a Read Data or Write Data COMMREQ does not have a value 0x23 recognized by the High-Speed Counter. GFK-2892F March 2019...
  • Page 66 The ladder logic displayed in Figure 30 shows how to clear a fault on circuit #2 of the Genius Device at SBA#13 when connected via a Genius Gateway to the PROFINET Controller located at Rack 0 Slot 7. Figure 31 uses a Data_Init_Comm to set up the same COMMREQ. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 67: Figure 30: Ladder Logic To Clear Circuit Fault

    Chapter 6. COMMREQ/Data_Init_Comm Programming Figure 30: Ladder Logic to Clear Circuit Fault GFK-2892F March 2019...
  • Page 68: Comparison: Commreq Vs Data_Init_Comm

    Also note that the pop-up window presented in Data_Init_Comm (as shown in Figure 31), allows the user to scroll through the parameters of the command. This is especially useful where the command has multiple parameters. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 69: Commreq Differences: Genius Bus Controllers And Genius Gateway

     Read Identification    Write Point    Read Block I/O    Read Map    Write Map    Read Data    Write Data    GFK-2892F March 2019...
  • Page 70: Commreq Descriptions And Formats

    Max. communications time Address +6 Command number Address +7 PROFINET Device number 1-255: The device number of the targeted GCG Genius Gateway. Address +8 Genius Device Number 1-29: the SBA of the targeted Genius Device. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 71: Commreq #2: Read Configuration Command

    Genius Device. Use the same codes as in Address+2. Memory offset bytes 1, 2 Starting address within the Deposit Memory type. Address +11 Address +12 bytes 3 ,4 (Byte 4 is MSB, Byte 1 is LSB) GFK-2892F March 2019...
  • Page 72: Commreq #3: Write Configuration Command

    Configuration Command for data lengths associated with other Genius devices. Address +10 Configuration data for transfer to the target Genius device. Configuration Data Formats are given in the Genius I/O System and Communications User’s Address +n Manual, GEK-90486-1. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 73: Commreq #4: Read Diagnostics Command

    Genius Device. Use the same codes as in Address+2. Memory offset bytes 1, 2 Starting address within the Deposit Memory type. Address +11 Address +12 bytes 3, 4 (Byte 4 is MSB, Byte 1 is LSB) GFK-2892F March 2019...
  • Page 74: Commreq #5: Clear Circuit Fault Command

    For example, to clear faults on discrete I/O block circuit #5, enter 5 here. For a 4-Input/2-Output analog block, circuit numbers 1 to 4 are for input channels, 5 and 6 are for output channels. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 75: Commreq #6: Clear All Circuit Faults Command

    This enhancement (use of 255 as Genius Device Number) requires that the supervising PNC001 firmware be version 2.11 or later; otherwise the COMMREQ command will fail. If CPE330 is used, firmware version 8.80 is required. If CPE400 is used, all firmware versions support this functionality. GFK-2892F March 2019...
  • Page 76: Commreq #7: Assign Monitor Command

    SBA in this field each time. Genius Device Number of the bus interface device that will Address +9 0-31: the SBA of the receiving Genius Device (i.e. the Assigned Monitor). RECEIVE the extra fault reports. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 77: Commreq #8: Enable/Disable Outputs Command

    Enter 1-29 to enable or disable outputs to one block. Or Address +8 Genius Device Number enter 255 to enable or disable outputs to ALL devices on the bus. Address +9 Enable/Disable Command To disable outputs, enter 0. To enable outputs, enter 1. GFK-2892F March 2019...
  • Page 78: Commreq #10: Switch Bsm Command

    1-29: the SBA of the Genius block to which the Bus Switching Module is Address +8 Genius Device Number attached. Address +9 Desired bus position Enter 0 for Bus A or 1 for Bus B. All other values are invalid. PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 79: Commreq #11: Read Device Command

    Address+10 contains the zero-based offset into the memory being read. For legacy devices, use an absolute address, where Address+9 is the least-significant word of the address and Address+10 is the most-significant word of the address field. GFK-2892F March 2019...
  • Page 80: Commreq #12: Write Device Command

    The maximum length is equal to 128 bytes. Address +20 Data to be transmitted, then written into the specified memory of the Data target device. Address +n PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 81: Commreq #19: Read Identification

    Genius Device. Use the same codes as in Address+2. Memory offset bytes 1, 2 Starting address within the Deposit Memory type. Address +11 Address +12 bytes 3, 4 (Byte 4 is MSB, Byte 1 is LSB) GFK-2892F March 2019...
  • Page 82 0 0 0 1 x x x x 153.6 K baud, standard 0 0 1 0 x x x x 76.8 K baud 0 0 1 1 x x x x 38.4 K baud PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 83: Commreq #20: Write Point Command

    Address +11 AND mask is in the LSB; OR mask is in the MSB for byte 1 AND & OR Masks Address +12 AND mask is in the LSB; OR mask is in the MSB for byte 2 GFK-2892F March 2019...
  • Page 84: Commreq #21: Read Block I/O Command

    Starting address within the Deposit Memory type. Address +11 Address +12 bytes 3, 4 (Byte 4 is MSB, Byte 1 is LSB) Address +13 I/O Offset Byte offset from the beginning of the device’s I/O data (zero-based). PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 85 µA Feedback value for output channel 1 (MSB) 28-29 µA Feedback value for output channel 2 Engineering Units feedback value for output channel 1 (LSB) Engineering Units feedback value for output channel 1 (MSB) 32-33 Engineering Units feedback value for output channel 2 GFK-2892F March 2019...
  • Page 86 Engineering Units value for input channel 2 18-19 Engineering Units value for input channel 3 20-21 Engineering Units value for input channel 4 22-23 Engineering Units value for input channel 5 24-25 Engineering Units value for input channel 6 PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 87 Channel 1/2 internal CJS temperature (tenths of degrees C) (LSB) Channel 1/2 internal CJS temperature (tenths of degrees C) (MSB) 58-59 Channel 3/4 internal CJS temperature (tenths of degrees C) 60-61 Channel 5/6 internal CJS temperature (tenths of degrees C) 62-73 Reserved GFK-2892F March 2019...
  • Page 88: Commreq #22: Read Map Command

    Length of %I data (bytes) %AI Starting Reference Length of %AI data (bytes) %Q Starting Reference Length of %Q data (bytes) 10-11 %AQ Starting Reference Length of %AQ data (bytes) 8-bit additive checksum 14-15 16-bit LRC checksum PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 89: Commreq #23: Write Map Command

    1-29: the SBA of the targeted Genius Device to which data is to be Address +8 Genius Device Number transmitted. Address +9 Same format as Read Map Returned Data described above. Data to be written to the target device. The checksums will be ignored. Address +16 GFK-2892F March 2019...
  • Page 90: Commreq #24: Read Data Command

    Address +14 Counter Number 1 – 4 Read Data Reply Byte Command Code See Read/Write Data Command Code Table below. Byte +1 Counter Number 1 – 4 Value returned by Command Bytes 2 -5 Code PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 91: Commreq #25: Write Data Command

    Address +10 Counter Number Data to be written Four bytes of data to be written to the target Genius HSC Address +11 bytes 1, 2 Address +12 (Byte 4 is MSB, Byte 1 is LSB) bytes 3, 4 GFK-2892F March 2019...
  • Page 92 Load/Read ON Preset n.4 0015 Load/Read OFF Preset n.1 0016 Load/Read OFF Preset n.2 0017 Load/Read OFF Preset n.3 0018 Load/Read OFF Preset n.4 001F Load/Read PRELOAD n.1 0020 Load/Read PRELOAD n.2 0032 Load/Read Oscillator Divisor PACSystems RX3i Genius Communications Gateway GFK-2892F...
  • Page 93 GFK-2892F March 2019...
  • Page 94 GE Automation and Controls Additional Resources Information Centers For more information, please visit our web site: Headquarters: 1-800-433-2682 or 1-434-978-5100 www.geautomation.com Global regional phone numbers are available on our web site www.geautomation.com Copyright © 2014-2019 General Electric Company. All Rights Reserved *Trademark of General Electric Company.