Rexroth IndraDrive Rexroth IndraMotion MLD Application Examples
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
3. Taking control to the drive PLC
As long as "bEnable" has been set, the program in step 2 (Step 10) waits
for a rising edge of "bStart" (P‑0‑1390, bit 1, %IX0.1). After the edge has
been detected, MLD gets control. As soon as IndraMotion MLD has con‐
trol, the program jumps to the step with the corresponding reaction,
depending on the configured type of reaction (P‑0‑1370, bit 0). When
"bEnable" was reset, the error reaction is completed in Step 100 (see be‐
low).
Fig.6-11:
Step 10: Setting Drive Enable
4. Positioning
As long as "bEnable" has been set, the return motion is started or pro‐
cessed in step 3 (Step 20). When the return position has been reached,
i.e. when "bInPos" (P‑0‑1410, bit 1, %QX0.1) has been set or "bEnable"
was reset, the error reaction is completed in Step 100 (see below).
Fig.6-12:
Step 20: Positioning
5. Analog velocity input
Bosch Rexroth AG
45/97
Intelligent Error Reaction