Requirements; Firmware And Hardware Requirements; Enabling Of Functional Packages - Bosch REXROTH IndraDrive Applications Manual

Hide thumbs Also See for REXROTH IndraDrive:
Table of Contents
DOK-INDRV*-MLD-APPLI**-AW02-EN-P
Rexroth IndraDrive Rexroth IndraMotion MLD Application Examples
4

Requirements

4.1

Firmware and Hardware Requirements

4.2

Enabling of Functional Packages

LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Using the drive-integrated PLC (Rexroth IndraMotion MLD-S/M) requires the
following hardware/firmware combinations:
Control section for IndraDrive C/M:
CSH01.*C (as of FWA-INDRV-MPH02VRS)
CSB01.1** (as of FWA-INDRV-MPB03VRS)
IndraDrive Cs:
HCS01 (as of FWA-INDRV-MPB17VRS)
With BASIC control sections (CSB01.1), using MLD-S has only
been enabled for self-contained Bosch Rexroth system solutions
("technology functions")! MLD is not available for double-axis devi‐
ces (HMD01.1 with CDB01.1C).
As of firmware MPH04V06, IndraMotion MLD is available as a multi-
axis PLC (MLD-M). Access to remote axes (CCD slaves) requires
the control section hardware CSH01.2C (firmware versions
MPH04/05VRS) or CSH01.3C (firmware version >= MPC06VRS)
and the enabling of the functional firmware package "ML".
Using the PLC functionality does not require any special optional
card or control section configuration, because it is a PLC that is
running in parallel in the drive processor in the real-time kernel.
In addition to the functional package "Closed Loop", the functional package
"IndraMotion MLD" (drive PLC) must have been enabled in the drive so that
IndraMotion MLD can be used.