Honeywell 2MLL-PMEC User Manual

Honeywell 2MLL-PMEC User Manual

Profibus-dp(pnet) module, honeywell process solutions

Quick Links

Honeywell Process Solutions
Profibus-DP(Pnet) Module
2MLL- PMEB/PSRA/PSEA
User's Guide
R2 4 0
J anuary 2018
Release 2 4 0
Honeywell
loading

Summary of Contents for Honeywell 2MLL-PMEC

  • Page 1 Honeywell Process Solutions Profibus-DP(Pnet) Module 2MLL- PMEB/PSRA/PSEA User's Guide R2 4 0 J anuary 2018 Release 2 4 0 Honeywell...
  • Page 2 In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
  • Page 3 First Edition ’07.10 V1.1 2MLI-CPUU added ’10.08 V 2.0 2MLR CPU added Ch. 11 Compliance with EMC Specification added 2MLL-PMEC added PROFICON configuration tool added Automatic Network Scan modified Ch.9.1.1 2MLL-PSRA added Ch.1.3.3 ’11.05 V 2.1 How to enable link through flag added Ch.5.2.3...
  • Page 4: Softmaster ---------------------------------------------------------------------------------------------------

    About User’s Manual Thanks for purchasing ML PLC of Honeywell Before use, make sure to carefully read and understand the User’s Manual about the functions, performances, installation and programming of the product you purchased in order for correct use and importantly, let the end user and maintenance administrator to be provided with the User’s Manual.
  • Page 5 3.2 From Setting to Operation ------------------------------------------------------------------------------------- 3-2 3.3 Installation of the product -------------------------------------------------------------------------------------- 3-3 3.3.1 Installation of 2MLL-PMEA --------------------------------------------------------------------------- 3-3 3.4 Test Operation ---------------------------------------------------------------------------------------------------- 3-6 3.4.1 Precautions for system configuration ------------------------------------------------------------- 3-6 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 6 6.4.2 Online to the CIF -------------------------------------------------------------------------------------- 6-18 6.4.3 Automatic network scan ----------------------------------------------------------------------------- 6-18 6.4.4 Start/Stop communication --------------------------------------------------------------------------- 6-20 6.4.5 Debug mode -------------------------------------------------------------------------------------------- 6-20 6.4.6 Diagnostic functions ---------------------------------------------------------------------------------- 6-20 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 7 8.3 Operation Sequence of High-speed Link ------------------------------------------------------------------- 8-3 8.4 High Speed Link Parameter Setting--------------------------------------------------------------------------- 8-4 8.5 High-speed Link Information --------------------------------------------------------------------------------- 8-10 8.5.1 Monitor of High-speed link information ---------------------------------------------------------- 8-12 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 8 12.1.3 Cable ----------------------------------------------------------------------------------------------------- 12-3 12.2 Requirements Complying with Low Voltage Direction ------------------------------------------------ 12-4 12.2.1 Specifications applicable to ML200 series ------------------------------------------------------ 12-4 12.2.2 Selection of ML200 series PLC -------------------------------------------------------------------- 12-4 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 9 Appendix A.1 Terminology ------------------------------------------------------------------------------------------------------- A-1 A.2 List of Flags ------------------------------------------------------------------------------------------------------- A-3 A.2.1 High-speed link flags ------------------------------------------------------------------------------------ A-3 A.2.2 Link devices (N) ------------------------------------------------------------------------------------------ A-6 A.3 Dimensions -------------------------------------------------------------------------------------------------------- A-8 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 10: Characteristics ----------------------------------------------------------------------------------------------------

    ▶ Max. output data: 244 Bytes/Slave ▶ Max. data size : 244 Bytes/Slave, 10 kbyte/Master ▶ Communication speed : 9.6k, 19.2k, 31.25k, 45.45k, 93.7k, 187.5k, 500k, 1.5M, 3M, 6M, 12M Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 11 This describes on the product configuration of the ML200 Pnet I/F module. Model Contents Remark 2MLL-PMEA Profibus-DP Master Supports DP-V0 2MLL-PMEC Profibus-DP Master 2MLK/2MLI/2MLR 2MLL-PMEB Profibus-DP Master Supports DP-V1 Note (1) ML200 Pnet supports only Profibus-DP. FMS, PA are not supported and protocol conversion is...
  • Page 12 (1) Master module Connection Item Model Product code contents Remark cable 2MLL-PMEA 47200001 Profibus DPv0 Sycon Master Twisted pair 2MLL-PMEC 47200103 Profibus DPv0 module (Electricity) ProfiCon 2MLL-PMEB 47200180 Profibus DPv1 (2) Slave module Item Connection cable Model Product code contents...
  • Page 13 This describes on the software tool for the Pnet I/F module. For programming and application, refer to the followings 1.4.1 Check list for the software (1) Software list Communication Item Programming tool configuration tool 2MLL-PMEA 2MLL-PMEC Profibus-DP master module SOFTMASTER 2MLL-PMEB (2) Selecting the CPU (Version) to use the Pnet I/F module Available version Item Model Remark...
  • Page 14 After connection, execute [Online]-[Communication module setting]-[System Diagnosis] d) In the “System Diagnosis” screen, select “Module Information” by double-clicking the communication module and pop-up window e) Software information appears at the right-bottom. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 15 The module information is attached at the external case every communication modules In case online connection is not available, take a module apart and check the label in the module case. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 16 An index indicating pollution degree of the operating environment which decides insulation performance of the devices. For instance, Pollution degree 2 indicates the state generally that only non-conductive pollution occurs. However, this state contains temporary conduction due to dew produced. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 17 Communication Parameters SoftMaster , SyCon (2MLL-PMEA Dedicated Configuration Tool) to set N Configurator (2MLL-PMEB/C Dedicated Configuration Tool) Internal-consumed current 550(2MLL-PMEA), 450(2MLL-PMEC), 500(2MLL-PMEB) (mA) Weight (g) 114(2MLL-PMEA), 112(2MLL-PMEC), 88(2MLL-PMEB) [Table 2.2] Performance Specifications Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide...
  • Page 18 Normal status of High-speed link communication STAT Abnormal status of Master module Error Error It needs to check the slave module Normal Normal status [Table 2.3.1] LED display of 2MLL-PMEA Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 19 There is no Configuration Setting in the Pnet I/F module Blink Normal Downloading or uploading the Configuration Setting Normal A Pnet I/F module is configured normally [Table 2.3.2] LED Display of 2MLL-PMEC Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 20 No network configuration for Profibus-DP Master module Blink Standby Downloading or uploading configuration parameter to Master module Normal Network configuration is installed successfully [Table 2.3.3] LED display of 2MLL-PMEB Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 21 1) The profibus standard defines two types of bus cables, but it is usually recommended to use a type. Please contact the cable manufacturer for details. 2) Awg is a numbering scheme that indicates the size of the wire. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 22 If the lock is not applied, it may cause an error on the interface with CPU. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 23  Execute [Online] – [Communication module setting] – [System Diagnosis]  Open the [Status by service] window in [System Diagnosis]  Check the normal operation with P2P and High-speed Link service  Start Run Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 24 (9) After the cable connected, measure the line resistance value on the master by means of digital multi-meter. (If terminal resistance at the both ends of the cable is On, it will be generally 110Ω + line resistance value + connector resistance value) Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 25 (3) Connect shield to clamp of shield (4) In case of installing the connector at terminal, install the cable at A1, B1 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 26 (2) Termination is available to turn on/off by the switch of special connector. (3) If possible, install the master at the end of one side. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 27 7) If LED operation is abnormal, refer to Chapter 10 Troubleshooting to check for causes and take actions against. Contact service center if the error is as before. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 28 Set the Pnet I/F module as master in system and the others have to set as slave module. To connect LS inverter, Pnet I/F option module have to install applicable product then it will be communicate. [Figure 4.1] ML200 Pnet + Smart I/O diagram Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 29 GSD folder of Pnet configuration software tool(SYCON, N Configurator) and then if you use Pnet configuration software tool(SYCON, N Configurator), you can configure the slave modules in the network automatically. Sensor [Figure 4.1.2] ML200 Pnet + Composite system Diagram Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 30 (1) How to set SoftMaster is same though CPU type is different. 1) CPU type: 2MLI, 2MLK, 2MLR system common (2) P2P communication is available with 2MLL-PMEB only that supports PROFIBUS DPv1. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 31 [File]  [New File]. On the new project menu, input the project name, project type and PLC type as shown below [Fig. 5.2.1] is initial screen of the SoftMaster [Figure 5.2.1] initial screen of the SoftMaster Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 32: Software -------------------------------------------------------------------------------------------------------------

    There are 4 types of PLC (2MLK, ML50, 2MLI, and 2MLR). For detail on the CPU, refer to CPU manual. Here we select 2MLK for example. After setting, menu of [Figure 5.2.3] appears Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 33 Registration example of base 0, slot 2 is as follow. a) Right click [Unspecified Network] in project tree and select [Add Item] -> [Communication module] Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 34 Click [Add module] in [Select Communication Module] window. [Figure 5.2.5] Add module c) Select the type, base and slot in [Communication Module Settings] window. [Figure 5.2.6] Communication module setting Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 35 Base no. of mounted module module setting Slot Slot no. of mounted module [Table 5.2.1] Communication module setting contents Registration PMEB module on base 0, slot 2 [Figure 5.2.7] Registration screen Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 36 [Figure 5.2.6] Read IO Information In case Pnet is installed at the base 0, slot 10, it searches and registers as follows. [Figure 5.2.7] Basic setting and Communication module Settings screen Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 37 (2) Uploading a configuration tool (SyCon or N-Configurator) With the mouse cursor positioned on “High-speed link1”, select [Online]-[Communication module setting]-[Config. Upload (Dnet, Pnet)] [Figure 5.2.10] Config data Upload from SyCon or N-Congurator Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 38 - In case of I/O module of 8 bits or less, please set 1 byte. (Byte) *1 : Area is not able to set [Table 5.2.2] High-speed link Block Settings Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 39 Chapter 5 Communication Program (5) High-speed link parameters download [Figure 5.2.12] High-speed link parameters download (6) Enabling the Link [Figure 5.2.13] Link Enable of High-speed link parameters Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 40 Read area Sending data area Setting Save area Save area of receiving data Data size Sending/Receiving data size *1 isn’t setting area. [Table 5.2.15] P2P block setting Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 41 Chapter 5 Communication Program (5) Download P2P parameter [Figure 5.2.16] P2P parameter download (6) Enable link [Figure 5.2.17] Enable link P2P parameter Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 42 _HS2_REQ_NUM F10311 HS link 2 enable/disable setting _HS3_REQ_NUM F10312 HS link 3 enable/disable setting _HS4_REQ_NUM F10313 HS link 4 enable/disable setting _HS5_REQ_NUM F10314 HS link 5 enable/disable setting Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 43 -HS link/P2P enable/disable setting flag OFF  HS link/P2P enable/disable request flag ON ▶ You can monitor the Enable/Disable state of the each link through “enable/disable current states” flag. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 44 5.2.16] and then, check the applicable parameters and click [OK]. [Figure 5.2.14] Read screen (c) Reads previously specified values for the parameters checked. (8) View Tree by Transmission/Reception Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 45 Chapter 5 Communication Program Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 46 ▪ RAM with 16MB or more ▪ Graphic Resolution: min. 800 x 600 pixel ▪ Windows 95: Service Pack 1 or higher ▪ Windows NT: Service Pack 3 or higher Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 47 2) Do you want to install the SyCon integrated OPC Server?  No 3) Do you want to the Stand-Alone OPC Server/Busserver?  Yes 4) Do you have a License code? 5) Select Language Select here  Next Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 48 Chapter 6 SyCon Setting 3. License Agreement  Select I agree 4. Program Registration Input License code: F90BF4B3E874  Select ‘OK’  Select ‘Yes’. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 49 Chapter 6 SyCon Setting 5. Configuration Setup  Select ‘Next’. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 50 1) Components Select Network to install Select the destination folder to install Display minimum Disk Space required of PC  Select ‘Next’ 2) Program Folder  Select ‘Next’ Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 51 Chapter 6 SyCon Setting 3) Setup complete 6. Installed contents 1) Installed file Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 52 Chapter 6 SyCon Setting 2) Contents of Folder - Destination: C:\Program Files\Honeywell\SyCon 3) GSD files for Profibus - GSD files are generated as shown below. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 53 Chapter 6 SyCon Setting 6.3 Communication Settings in SyCon 6.3.1 Initial screen Menu Icon Status Network Menu Icon Status Edit Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 54 Activate the basic menu Toolbars Fieldbus Activate the Insert Icon on menu Status Bar Display the Status Bar on SyCon basic window Master Insert Master module Insert Device Insert Slave module Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 55: Bus Parameter -----------------------------------------------------------------------------------------

    The path of GSD setting file and project Language Language selection Cascade Window array to cascade Window Tile Window array to tile Help Topics Help view Help About Information of SyCon program Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 56 2) The composition of picture 3) Master selection Master type GSD File Name Master name ML200 2MLL-PMEA HIL_069E COM-C-DPM G3L-PUEA G4L-PUEA HIL_7065 COM-DPM/PKV20-DPM G6L-PUEA GM/MK G3L-PUEB G4L-PUEB HIL_1662 COM-PB/PKV-PB G6L-PUEB Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 57 Menu Insert Master Icon 2) Insert Master type GSD File Name Master name ML200 2MLL-PMEA HIL_069E COM-C-DPM G3L-PUEA G4L-PUEA HIL_7065 COM-DPM/PKV20-DPM G6L-PUEA GM/MK G3L-PUEB G4L-PUEB HIL_1662 COM-PB/PKV-PB G6L-PUEB Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 58 Chapter 6 SyCon Setting 3) Edit 4) Master Configuration - Select “Settings”  “Master Configuration” on menu. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 59 “Parameter to process data interface” (a) Set “Byte addresses” in “Addressing mode” (b) Set “Little Endian” in “Storage format(word module)” d) Set “Buffered, host controlled” in “Handshake of the process data” Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 60 Selected slaves Display of slave module designated Station address Display of Slave module station number (It must not duplicate) Description Explain of Slave module (It must not duplicate) Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 61 Slave Adapter for GM7 Pnet I/F Expand type Pnet I/F Expand type Pnet I/F Adapter MPL_BSSA MPL-BSSA Adapter module module Inverter(AC Drive) HNWL0552 SV-IS series Inverter Option module 3) Edit Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 62 Actual slave Slave2 Slave operation display 6.3.6 Bus parameter “Settings”  “Bus Parameter”, it can be set the communication speed. Baud rate is selected correspond to system operation. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 63 3) Baud rate setting: Settings  Bus parameter 4) Download the setting value in Master: Online  Download 5) Saving: File  Save 6) Network scan: Online  Automatic Network Scan Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 64 7) If select the “Yes’, Dialog box is opened as shown below. 8) At upper dialog box, If select the “Accept Configuration”, it is display the connected slave module. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 65 It is display the station number of Master connected the network and station number of Slave. Color of number Description Green Number Display of connected Master station number Blue Number Display of connected Slave station number Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 66 Statistic bus information Display of network error Parameterized Devices Display of Slave parameter Device specific status bits Activated Devices Display of Slave operation Devices with Diagnostic Display of Slave diagnosis Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 67  N Configurator configures with standardized GSD file.  N Configurator has diagnostic function.  N Configurator has a function to upload network settings which was previously downloaded. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 68 GSD directory to use, and copy bitmap image files used by the GSD to the bmp directory. Start again the N Configurator program to apply the copied GSD. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 69 - Slave property window: Set up property of slave device composed on the project window - Bus parameter window: Set up communication property of PROFIBUS Network composed on the project window Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 70 Add GSD Add gsd in List of devices Report(MS-Excel) Output as a MS Excel file type Recent File List Shows the project file opened recently. Exit Close the program Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 71 Cut the selected device from the topology Copy Copy the selected device from the topology Paste Paste the cut or copied device on the topology Delete Delete the selected device from the topology Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 72 Match the space between devices on the topology with based on the master Tool Bar Show or remove tool bar of program Status Bar Show or remove status bar of program Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 73 Download network configuration composed on the topology Download Image From File… Download the saved network configuration file Upload Image Upload network configuration information saved in the master module Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 74 Monitor I/O of slave Disconnection Report… Display the number of disconnection among slaves set up at master Device Information… Hardware and software information of master Firmware Reset Reboot the master Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 75 (9) Help menu [Figure 7.3.10] Help menu composition This is a manual and help menu. Sub-menu Description N Configurator Help Display N configurator manual About Configuration Tool… Introduction of program Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 76 Each device module property is also easily configured by using the configuration tab. Moreover, the project explorer help to find out slave modules you want to edit from so many slave modules. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 77 Chapter 7 N Configurator Setting 7.4 Network composition through N CONFIGURATOR 7.4.1 Master composition Master device is displayed on the top of the device list, then select 2MLL-PMEC as shown in the figure below. [Figure 7.4.1] 2MLL-PMEC selected from the list of device If you drag &...
  • Page 78 If you change properties like station address of the master or description, click “Master Properties” of the “Configuration” menu to activate the master property change tab as below [Figure 7.4.3] Master property tab Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 79 (See Figure 7.4.5, at this time, it is confirmed that the slave is subordinated to the relevant master through the project explorer.) [Figure 7.4.5] Compose slave to master Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 80 User’s parameter and module are configured by using separate window. [Figure 7.4.6] slave property tab First of all, the parameter is configured by using slave parameter settings window as shown below. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 81 MPL-BSSA, you can add the module to the expansion adapter by double clicking the module at the above module list. If you add wrong one, double click the item to delete it. [Figure 7.4.8] Slave module settings window Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 82 [Figure 7.4.9] bus parameter settings tab If you simply select PROFIBUS DP communication speed (Baud-rate) here, then the selected bus parameter values will be applied. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 83 If you select “Settings…” item from the “Communication” menu, the window will be popped up as seen below. Here you should select “Communication with ML200” and enter the information with current 2MLL-PMEC module, and click “OK” button. [Figure 7.5.1] Communication Settings window: Information of 2MLL-PMEC settings Then, ML200 CPU connection settings window will pop up as shown below.
  • Page 84 The status bar runs progress bar, and the output window shows the progress rate. [Figure 7.5.3] Download status If downloading is completed, the progress bar is full, and “Done” message will be displayed on the output window. [Figure 7.5.4] Downloading completed Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 85 If uploading is completed, “Done” message will be displayed on the output window. Project topology will show the Network Configuration composition uploaded from current master. [Figure 7.5.6] Uploading completed Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 86 The “Start Debug Mode” of “Diagnostics” menu continuously monitors the status of slave in debug mode. At this time, the topology is activated, and regularly checks out the status information of slaves from master. [Figure 7.6.1] Master debug mode Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 87 If any slave generates diagnostic information for cable cut-off, incorrect parameter or configuration, then “Diag” event is displayed at the slave on the topology as shown in the Figure 7.6.2 to inform the user. [Figure 7.6.3] Slave diagnostic Information Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 88 If “Live List…” is selected from “Diagnostics,” then the live list window appears as shown below. [Figure 7.6.4] Live list If “Update” button on the right side is clicked, then the contents of the live list will be updated. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 89 GSD file, then obtain formal GSD file provided by the manufacturer of the slave and compose the Network by yourself. If the scanned contents are correct, then click OK button to check out the collected Network composition as shown below. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 90 And then the values entered through current slave will be monitored through the input data area. (Here the number of data available for I/O is 32 bytes respectively.) [Figure 7.6.9] I/O monitor Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 91 For the information of current master, select “Device Information...” item from “Diagnostics,” then the contents below are displayed as shown in the figure below. [Figure 7.6.11] Master information 7.6.8 Master reset (Firmware Reset) Reset current master by software. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R240 Honeywell January 2019...
  • Page 92 Speed link “x”, _HSx_TRXy flag will be ON. 2) For example, In case of communicating with the slave module whose station number is “1” through High- Speed link “1”, _HS1_TRX001flag will be ON. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 93  Station number : 2 D00201 Input Area  Mode : Receive  Save area : D00201 D00202 ~ D00202 [Figure 8.2.1] Block diagram of High-speed link process Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 94: Softmaster --------------------------------------------------------------------------------------------

    Online  Write: check applicable High-speed link and High-speed Link Parameters Write write Online  Communication module setting  Enable High-speed Link Enable Link: enable applicable High-speed link [Table 8.3.1] Operation sequence of High-speed link Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 95 2MLK- CPUH, CPUS ML50 ML50- MLIE, MLCH, MLM, MLIH, MLIS, MLIU CPU type 2MLI 2MLI-CPUH, CPUS, CPUS/P, CPUU 2MLR 2MLR-CPUH/F, CPUH/S, CPUH/T Project description Writing the comment about the project. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 96 4) Read I/O information Select “Online”  “Diagnosis”  “I/O Information” and click “I/O Sync” to read modules installed on the base. Surely execute “I/O Sync” for High-speed link setting. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 97 Communication module settings and Communication period settings is opened. In this screen, communication module, communication period and output data in case of emergency can be specified. [Figure 8.4.4] Communication module setting Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 98 After “Setting of communication module and communication period” is complete, while putting the mouse cursor on High-speed link window (right screen of SoftMaster), and select “Online”  “Communication module setting”  “Config. Upload (Dnet, Pnet)” to upload a configuration file. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 99 - In case of I/O module of 8 bits or less, please set 1 byte. (Byte) *1 : Area is not able to set [Table 8.4,3] Setting of High-speed link block Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 100 High-speed link and then click [Write]. If High-speed link is enabled, on the module’s LED display High-speed LED will be on, when High-speed link starts. [Figure 8.8] Screen of Link Enable Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 101 Bit-Array Bit-Array Monitor Available Available Available Available Available Available Program Available Available Available Available Available Available [Table 8.5.1] High-speed link information function [Figure 8.5.1] Monitor window of variables Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 102 In other words, if the applicable list’s Send/Receive status is normal with the operation mode of Run and with no error, it will be On, and if the conditions above are violated, it will be Off. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 103 Displays the information of communication module High Speed Link Displays the information of high speed link Auto scan Displays the information of the slave configuration [Table 8.5.2] System diagnosis Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 104 Displays the relevant station number Hardware Error Displays the hardware status. Hardware Version Displays the hardware version. O/S Version Displays the software version [Table 8.5.4] Communication module information Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 105 Displays the information of high speed link between High-speed link status master and slave Error Displays the error information between master and slave [Table 8.5.4] High Speed Link Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 106 Network speed (9,600 bps ~ 12Mbps) Module Status Displays the status of communication module Status information HS link status Displays the status of high speed link [Table 8.5.5] Autoscan Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 107 User can set the read area of sending data or save area of receiving data. Remark 1) P2P communication is required the DPv1 to both master and slave module. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 108  Read area: M0200 Slave station “1” Master  Station number: 1 aCyclic Area M0400  Mode: READ  Save area: M0400 [Figure 9.2.1] Block diagram of P2P process Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 109 Online  Write: check applicable P2P and write P2P Parameters Write Online  Communication module setting  Enable P2P Enable Link: enable applicable P2P [Table 9.3.1] Operation sequence of P2P Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 110 ML50- MLIE, MLCH, MLM, MLIH, MLIS, MLIU CPU type 2MLI 2MLI-CPUH, CPUS, CPUS/P, CPUU 2MLR 2MLR-CPUH/F, CPUH/S, CPUH/T Project description Writing the comment about the project. [Table 9.4.1] Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 111 4) Read I/O information Select “Online”  “Diagnosis”  “I/O Information” and click “I/O Sync” to read modules installed on the base. Surely execute “I/O Sync” for P2P setting. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 112 Setting of slot position installed module settings Slot No. Range of setting: 0~11 Setting of P2P index number P2P index Range of setting: 1~8 [Table 9.4.3] Communication module setting Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 113 2) READ function; reads the arbitrary address of slave and saves to set area of master when the condition flag has been turned on 3) DIAGNOSTIC function; reads the diagnostic information of P2P Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 114 P2P and then click [Write]. If P2P is enabled, on the module’s LED display P2P LED will be on, when P2P starts. [Figure 9.4.7] Screen of Link Enable Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 115 Single and continuous real-time monitoring are available through this menu. How to open this menu is as follow (a) Select ‘Connection’ -> ‘Online’-> ‘Communication module setting’-> ‘System diagnosis’ in SoftMaster. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 116 (b) Right clink on the Pnet I/F module and select [Status by service], then P2P service information will be open as [Figure 9.5.3] [Figure 9.5.3] P2P service monitor Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 117 Diagnostic communicates by REQUEST/RESPONSE structure with connected slaves. If there is not connected slave, local indicates the information that slave is not connected. Also it is not related with error count Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 118 %MW3000~3010 area to MPL-BSSA. 2MLI CPU saves 2 byte of 16-point input data in MPL-D22A onto %MW200 area and 20 byte of input data in MPL-BSSA onto %MW3011~3020 of 2MLK CPU. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 119 After communication types chose, Select Master type as COM-C-DPM, 2MLL-PMEA master board. Add COM-C-DPM and then set station address of master module. [Figure 10.1.3] master module type settings Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 120 1 as shown below, click ‘OK’. Slave module setting is as shown below. Double-click the applicable module, Slave configuration is displayed. In the slave configuration, it displays the status of slave module GSD file applied and status of Input/Output appended currently. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 121 Chapter 10 Program Example [Figure10.1.6] Slave module setting in SyCon [Figure 10.1.7] Slave Configuration MPL-D22A setting is a same process as shown above. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 122 Analog Output Analog Output 8 byte (MLF-DV04A) Analog Output Analog Output 8 byte (MLF-DC04A) Analog Input Analog Input 8 byte (MLF-RD04A) Digital Output Digital Output 2 byte (MLE-RY16A) Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 123 [Figure 10.1.11] Selection of communication speed of master module Communication speed is accorded to Master (Pnet I/F) module. After [Setting] – [Master setting] is as shown below. [Figure 10.1.12] DP Master Settings Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 124 If setting and download is completed, All setting of SyCon is finished. Before close the SyCon, It is very useful to save the network file in order to recover the damaged network. This part explains the automatic setting. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 125 GSD file of current slave module. In [Figure 10.1.16], select [Accept Configuration] and the setting is automatically completed as shown below. [Figure 10.1.17] The screen after Automatic Network Scan Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 126 This part describes how to assign the internal memory by SoftMaster. Click ‘Project’ ->’New Project’ and select project name and PLC series in the New Project window. [Figure 10.1.19] New project Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 127 Select High-speed link tab in lower end tab of left frame, Right click PLC  Add Item  High-speed Link Communication. It can available to set the module type, base (no.) number, slot (no.) number and communication cycle. [Figure 10.1.21] Screen of communication module setting Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 128 Double click the applicable index to set the address. Set %MW200 for station3, %MW0 for station 4 and %MW3000 for area to read, %MW3011 for area to save of station 6. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 129 After finish the setting, setting information is downloaded in PLC. Select [Online] – [Write] (standard settings, High-speed link, P2P). Here, Check High-speed link to download and click ‘OK’. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 130 [Communication module setting]-[Enable Link] (High-speed, P2P). And Link Enable window is displayed as shown below. Select the applicable High-speed link number and then select ‘Write’ to set. [Figure 10.1.26] Link Enable Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 131 Chapter 10 Program Example 10.2 Example of communication with 2MLL-PMEC This example shows a program that is installed on No. 0 slot of ML200 No. 0 base, sending and receiving data to Smart I/O module(Station Number 4 and 1) and Extended Smart I/O Pnet(Station [Figure 10.2.1] I/O Structure and Sending/Receiving Data...
  • Page 132 [Figure 10.2.2] Initial Execution Screen: New Project Window For network configuration, the master module (2MLL-PMEC) should be composed first. Select 2MLL-PMEC from the device list window on the left and drag and drop on the topology in the project window as seen in the figure below.
  • Page 133 Change the station number of the slave module in the Slave Properties window on the left bottom as seen in [Figure 10.2.6]. To activate this window, select a Slave from the topology. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 134 If station number and description properties are changed, the changed number and properties are immediately reflected on the project window as seen in the figure below. [Figure 10.2.7] Topology after properties are changed Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 135 Digital input 4byte(MLE-DC32A) Analog Input Analogue input 8byte(MLF-AD04A) Analog Output Analogue output 8byte(MLF-DV04A) Analog Output Analogue output 8byte(MLF-DC04A) Analog Input Analogue input 8byte(MLF-RD04A) Digital Output Digital output 2byte(MLE-RY16A) Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 136 [Figure 10.2.9] Slave Module Setting Setting a network is completed (See [Figure 10.2.10]). Now, a bus parameter needs to be set. [Figure 10.2.10] Screen of Network Setting Completion Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 137 “Communication” menu and set access. After assigning a number to the slot in which the current Pnet I/F module is installed, set access as in [Figure 10.2.13]. [Figure 10.2.12] Communication Settings Window for ML200: Set to install Pnet I/F module Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 138 As seen in [Figure 10.2.14], the Progress Bar shows download progress and setting Pnet I/F module network are completed once download ends. Before closing this tool, save the current network project for recover the project later. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 139 Then, the scanned results are shown as in [Figure 10.2.16]. [Figure 10.2.16] Results of Automatic Network Scan At this time, pressing the “OK’ button will prompt setting network topology automatically as seen in [Figure 10.2.17]. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 140 This part describes how to assign the internal memory by SoftMaster.. Click ‘Project’ ->’New Project’ and select project name and PLC series in the New Project window. [Figure109.2.18] New project Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 141 Select High-speed link tab in lower end tab of left frame, Double click High-speed link 1. It can available to set the module type, base (no.) number, slot (no.) number and communication cycle. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 142 After block is created, click the index of block information frame (right frame). Click [Online]- [Communication module setting]-[Config. Upload (Dnet, Pnet) and it brought the setting information in N Configurator [Figure 10.2.21] Config. Upload (Dnet, Pnet) menu Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 143 After Write is finished, the operation is by applicable high-speed link enabled. Select the [Online]- [Communication module setting]-[Enable Link] (High-speed, P2P). And Link Enable window is displayed as shown below. Select the applicable High-speed link number and then select ‘Write’ to set. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 144 Chapter 10 Program Example [Figure 10.2.24] Link Enable (High-speed link, P2P) Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 145 In addition, it is necessary to write high-speed link parameters after setting Network Configuration through N Configurator and download to PLC in order to send/receive data as in [Table 10.3.1]. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 146 2MLL-PMEB from the device list window on the left and drag and drop on the topology in the project window as seen in the figure below. [Figure 10.3.3] Insert Master module Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 147 Change the station number of the slave module in the Slave Properties window on the left bottom as seen in [Figure 10.3.5]. To activate this window, select a Slave from the topology. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 148 [Figure 10.3.5] Change Slave Properties If station number and description properties are changed, the changed number and properties are immediately reflected on the project window as seen in the figure below. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 149 [Figure 10.2.7] Topology after properties are changed Set remaining MPL-D24C through the process described above. Finished network configuration is as follow. (Figure 10.3.7) [Figure 10.3.7] Finished network setting Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 150 “Communication” menu and set access. After assigning a number to the slot in which the current Pnet I/F module is installed, set access as in [Figure 10.3.10]. [Figure 10.3.9] Communication Settings Window for ML200: Set to install Pnet I/F module Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 151 As seen in [Figure 10.3.11], the Progress Bar shows download progress and setting Pnet I/F module network are completed once download ends. Before closing this tool, save the current network project for recover the project later. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 152 Then, the scanned results are shown as in [Figure 10.3.13]. [Figure 10.3.13] Results of Automatic Network Scan At this time, pressing the “OK’ button will prompt setting network topology automatically as seen in [Figure 10.3.13]. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 153 This part describes how to assign the internal memory by SoftMaster.. Click ‘Project’ ->’New Project’ and select project name and PLC series in the New Project window. [Figure10.3.15] New project Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 154 Select High-speed link tab in lower end tab of left frame, Double click High-speed link 1. It can available to set the module type, base (no.) number, slot (no.) number and communication cycle. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 155 After block is created, click the index of block information frame (right frame). Click [Online]- [Communication module setting]-[Config. Upload (Dnet, Pnet) and it brought the setting information in N Configurator Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 156 After finish the setting, setting information is downloaded in PLC. Select [Online] – [Write] (standard settings, High-speed link, P2P). Here, Check High-speed link to download and click ‘OK’. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 157 [Communication module setting]-[Enable Link] (High-speed, P2P). And Link Enable window is displayed as shown below. Select the applicable High-speed link number and then select ‘Write’ to set. [Figure 10.3.21] Link Enable (High-speed link, P2P) Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 158 10.4.1 SoftMaster settings This part describes how to assign the internal memory by SoftMaster.. Click ‘Project’ ->’New Project’ and select project name and PLC series in the New Project window. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 159 [Figure10.4.1] New project Select the ‘Online’ to connect with CPU and [Online]-[Diagnosis]-[I/O information]-[Click I/O Sync] is brought I/O information of each slot installed. [Figure 10.4.2] SoftMaster connection screen Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 160 [Figure 10.4.5] P2P READ variable setting After P2P READ setting, set P2P WRITE setting. Read 10 bytes from %MB200 of PLC and save 0x04 slot, 0x15 index of slave. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 161 After finish the setting, setting information is downloaded in PLC. Select [Online] – [Write] (standard settings, High-speed link, P2P). Here, Check P2P to download and click ‘OK’. [Figure 10.4.8] Write Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 162 Link] (High-speed, P2P). And Link Enable window is displayed as shown below. Select the applicable P2P number and then select ‘Write’ to set. [Figure 10.4.9] Link Enable Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 163 High slave Speed Link operation Check the setting of slave Error in OS Request A/S Error Request A/S [Table11.1.2] Symptoms related communication module (When High-speed link is enabled) Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 164 If you click the “System Diagnosis” on the [online]-[Communication module setting] menu, the following screen shows. If you click the right button on the individual module, the diagnosis items are displayed. [Figure 11.2.1] System diagnosis Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 165 11.2.2 Information on communication module It displays the number of base, number of slot, information of version about Pnet I/P module installed currently) [Figure 11.2.2] Communication Module Information Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 166 Size of Receive data information Mode Present operation status Transmission/Reception Send/Receive status displayed status High-speed link status High-speed link status displayed Error Error status displayed [Table 11.2.2] High-speed link diagnosis Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 167 Status Displays the status of P2P block Diagnostics Service count Service count of P2P block Error count of P2P block in communication Error count [Table 11.2.4] P2P diagnosis Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 168 Chapter 11 Troubleshooting 11.2.4 Auto-scan Slave modules connected with Pnet I/F module are displayed. [Figure 11.2.5] Auto-scan Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 169 If a hardware error or a CPU interface error occurs on the module, LED of the communication module itself operates abnormally in general, whose status can be monitored simply through its dedicated program. [Figure 11.3.1] shows Error/Warning information through PLC History on the SoftMaster [Diagnosis] menu. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 170 Install the module on slot correctly. Is there a problem in Serial cable? Check the serial cable. Is the environment appropriate with Operate in environment prescribed standard specifications? st standard specifications. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 171 Check the cable that connected with CPU that connected with CPU? Is the environment appropriate with Operate in environment prescribed standard specifications? standard specifications. Ask to Customer Service Center Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 172 Chapter 11 Troubleshooting 11.4.3 SoftMaster abnormal connection Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 173 Is there a problem in serial cable? Check the serial cable connector Is the cable specified cable Check the cable type and and long length? length in product specifications Ask to customer service center Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 174 *2 : PLC is a type of open device(installed on another device) and to be installed in a panel. For any applicable tests, the system is tested with the system installed in a panel. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 175: Panel -----------------------------------------------------------------------------------------------------

    (5) The inside plate of panel should have proper conductivity with a wide surface as possible by eliminating the plating of the bolt used to be mounted on the main frame in order to secure the electric contact with the frame. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 176: Cable -----------------------------------------------------------------------------------------------------

    The metallic plate of panel may shield noise from electromagnetic wave while it a cable as a noise source is close to the place, it can serve as an antenna. Every fast signal cable as well as the extension cable needs proper spacing from the panel. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 177 The modules use DC5V, 3.3V circuits, so they are not applicable to the low voltage directions. (4) Special module, Communication module The modules use the rated voltage less than DC 24V, so they are not applicable to the low voltage directions. Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 178: Log ------------------------------------------------------------------------------------------------------

    7) Broadcast communication Used to send the message whose operation station is not recognized to all the stations (Master, Slaves). A - 1 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 179 It is used to initialize the communication module when Error is occurred. In SoftMaster, Select [Online]-[Reset/Clear]-[Reset PLC] , Reset is operated. And PLC is restarted. A - 2 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 180 No.1, Block No.k OCK[k] Array setting displayed L00041F [Table 1] List of communication flags based on HS link number (HS link No. 1 ~ 12) A - 3 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 181 L00011, L00012, L00013, L00014, L00015, L00016, L00017 from block 0 to block 15 for mode information (_HS1MOD). Thus, the mode information of the block No. 55 will be displayed in L000137. A - 4 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 182 DWord service abnormal execution times displayed execution times [Table 2] List of communication flags based on P2P service setting (P2P parameter: 1~8, P2P block: 0~63) A - 5 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 183 No.00 saved saved area size 4 [Table 3] List of communication devices based on P2P number (P2P No. : 1~8, P2P block : 0~63) A - 6 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 184 2) Since the addresses of N area available are classified according to P2P parameter setting No. and block index No., the area not used for P2P service can be used as an internal device. A - 7 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...
  • Page 185 Appendix A.3 Dimensions 2MLL-PMEA/B/C have same dimensions. Unit : mm A - 8 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220 Honeywell January 2019...

This manual is also suitable for:

2mll-pmea2mll-psea2mll-pmeb2mll-psra