Bosch Rexroth IndraDrive FC Series Operating Instructions Manual page 51

Drive controllers frequency converters
Table of Contents
DOK-INDRV*-FCS01******-IT01-EN-P
Rexroth IndraDrive Fc Drive Controllers Frequency Converters FCS01
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Recommendation for complex systems: Install drive components in one cabi‐
net and the control units in a second, separate cabinet.
Badly grounded control cabinet doors act as antennas. Therefore, connect
the control cabinet doors to the cabinet on top, in the middle and on the bot‐
tom via short equipment grounding conductors with a cross section of at least
6 mm
2
or, even better, via grounding straps with the same cross section.
Make sure connection points have good contact.
Bosch Rexroth AG
EMC Measures for Design and Installation
49/69
Table of Contents
loading

This manual is also suitable for:

Rexroth indradrive fcs01 series

Table of Contents