Operation with Residual-Current-Operated Circuit-Breaker

Operation in IT Mains

LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
The frequency converters FCS01 have been sized for operation with a 30 mA
residual-current-operated circuit-breaker sensitive to universal current.
If several FCS01 frequency converters are operated at a residual-current-op‐
erated circuit-breaker, the leakage currents must be reduced against PE.
General Information
Via jumpers at the top and bottom of the device, the FCS01 frequency con‐
verters can be set for operation at IT mains and for reduction of leakage cur‐
rents.
At the Top of the Device (Mains Input)
Fig.5-6:
Mains Input Jumper in Position "2"
Setting
Position
0
1
2
Fig.5-7:
Jumper Position at the Top
Bosch Rexroth AG
Instructions for Use
Effect
Operation at the IT mains
No effect
Standard position (condition as supplied)