Ratings And Dimensions; Technical Data; General Data Fcs01 - Bosch Rexroth IndraDrive FC Series Operating Instructions Manual

Drive controllers frequency converters
Table of Contents
DOK-INDRV*-FCS01******-IT01-EN-P
Rexroth IndraDrive Fc Drive Controllers Frequency Converters FCS01
3

Ratings and Dimensions

3.1

Technical Data

3.1.1

General Data FCS01

Function
Output frequency
Pulse frequency fs
Typ. overload capability
Protection against
Closed-loop and open-loop control
Analog command value input / PID input
Analog command value resolution
Analog output
Command value constancy
Motor temperature monitoring
Digital input
Galvanic isolation
Ramp times
Control outputs
Interfaces
Frequency converter efficiency
Ambient temperature
Storage and transport temperature
Long-time storage
Degree of protection
Max. installation altitude / power reduction
Overvoltage category
Delay time between two mains activation cycles 60 s for all devices, in normal operation cycle
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Specification
0.0... 400.0 Hz
3.0... 16.0 kHz; standard setting: 6 kHz
Derating with 230V devices from fs > 8 kHz
Derating with 400V devices from fs > 6 kHz
150% for 60 s, 200% for 3.5 s
Overtemperature of the frequency converter, short circuit, ground fault,
overvoltage and undervoltage, overload, no-load operation
Sensorless current vector control (ISD), linear U/f characteristic
2x 0... 10 V, 0/4... 20 mA, scalable
10-bit related to measuring range
0... 10V scalable
Analog < 1%
Digital < 0.02%
I
t motor (UL/cUL approved), PTC / bimetal switch (not UL/cUL)
2
5 * 7.5... 30V (2.5V); Ri = 6.1 kohm (2.2 kohm); cycle time = 1... 2 ms
Control terminals of the digital and analog inputs
0... 320.0 s
2x relay 28V DC / 230V AC, 2A
Standard: RS 485 (USS), RS 232 (single slave)
Optional: Profibus DP; CANopen, DeviceNet
Approx. 95%
0°C... +40°C (S1-100% ED), 0°C... +50°C (S3-75% ED 10 min)
-25°C... +70°C
Connect the frequency converter to mains voltage for a period of 60 mi‐
nutes after expiry of one year at the latest. This cycle must be main‐
tained over the whole storage period.
IP20 (for installation in control cabinet)
Up to 1000°m above sea level: None
1000... 4,000 m above sea level: 1%/100 m
Up to 2000 m: Overvoltage category 3
2000... 4000 m: Overvoltage category 2, external overvoltage protection
required at the mains input
Bosch Rexroth AG
23/69
Ratings and Dimensions
Table of Contents
loading

This manual is also suitable for:

Rexroth indradrive fcs01 series

Table of Contents