Honeywell LLE Series Installation Instructions

Honeywell LLE Series Installation Instructions

Liquid level sensor

Quick Links

Installation instructions for LLE Series
Liquid level sensors
WARNING
PERSONAL INJURY
DO NOT USE these products as safety or emer-
gency stop devices, or in any other application
where failure of the product could result in personal
injury.
Failure to comply with these instructions could
result in death or serious injury.
CAUTION
Do not exceed maximum supply voltage.
Although the sensor is protected against supply
reversal, it is not recommended.
Do not overtighten screw-in type.
Do not use chlorinated solvents.
Do not mount with dome pointing downwards.
Failure to comply with these instructions may result
in product damage.

General description

The LLE Series liquid level sensor provides a single point
detection via a TTL compatible output. When liquid is
present on the surface of the sensor the output sinks up
to a maximum of 10 mA.
LED and phototransistor chips are sealed into the base of
the plastic dome, in such a position that light is totally
internally reflected from the dome boundary to the
phototransistor. Thus the output is normally high. When
liquid covers the dome, the change in refractive index at
the boundary means light escapes into the liquid, so less
light reaches the phototransistor which thus causes the
output to switch low.
Cleaning
Proper fluids should be selected based on type of
contaminant to be removed. Honeywell recommends
freon and alcohol based solvents. Do not use chlorinated
solvents such as trichlorethane as these are likely to
attack the sensor material.
Sensing and Control
Liquid media compatibility
Before use check that the fluid in which you wish to use
these devices is compatible with polysulphone.

Electrical specifications

Supply voltage (Vcc)
-25 °C to 80 °C (-13 °F to 176 °F) 5 V ± 5 %
LED (Vf) @ 25 °C (77 °F)
Supply current @ 25 °C (77 °F)
Output sink current (Io)
@ 25 °C (77 °F)
@ 80 °C (176 °F)
Operating temperature
Storage temperature

Electrical diagram

y y y y y y y y y y y y y y y y y y y y y y y y y y y y y
Vcc
RED
VOLTAGE
REGULATOR
IRED
0 V
BLUE
PK XP-4059
Issue 1
1.2 V @ 10 mA typ.
15 mA nominal
10 mA max.
3 mA max.
-25 °C to 80 °C
-13 °F to 176 °F
-30 °C to 85 °C
-22 °F to 185 °F
OUTPUT
GREEN
SCHMITT
TRIGGER
PHOTO
TRANSISTOR
loading

Summary of Contents for Honeywell LLE Series

  • Page 1: Electrical Specifications

    The LLE Series liquid level sensor provides a single point detection via a TTL compatible output. When liquid is present on the surface of the sensor the output sinks up to a maximum of 10 mA.
  • Page 2 While we provide application assistance personally, without charge those items it finds defective. The forego- through our literature and the Honeywell web site, it is up ing is Buyer’s sole remedy and is in lieu of all other to the customer to determine the suitability of the product warranties, expressed or implied, including those of in the application.