Fujitsu UTY-RVN*M Series Technical Manual

Fujitsu UTY-RVN*M Series Technical Manual

Wired remote controller

Quick Links

WIRED REMOTE
CONTROLLER

(Optional parts)

MODEL NAME :

UTY-RVNM
UTY-RVNYN
For Zone Controller functions using this remote controller,
refer to "ZONE CONTROL SYSTEM (DTR_OP006E)".
DTR_OP005E_02
2012.12.12
loading

Summary of Contents for Fujitsu UTY-RVN*M Series

  • Page 1: Optional Parts

    WIRED REMOTE CONTROLLER (Optional parts) MODEL NAME : UTY-RVNM UTY-RVNYN For Zone Controller functions using this remote controller, refer to "ZONE CONTROL SYSTEM (DTR_OP006E)". DTR_OP005E_02 2012.12.12...
  • Page 2 FEATURES MODEL „ „ UTY-RVNM, UTY-RVNYN ● Large and full-dot liquid crystal screen ● Screen with backlight can be seen even in the dark ● Wide and large keys easy to press, user-intuitive arrow key Monitor Mo 10:00AM Mode Set temp. °...
  • Page 3 MAIN FUNCTIONS „ „ Auto off timer „ Ex) At interval time hour (17:00 to 24:00) to prevent ● The indoor unit automatically turns forgetting to turn off off after a set time has passed. ● The time interval for which auto off Set interval time hour (17:00 to 24:00) works can be set.
  • Page 4: Child Lock

    22°C 10:00 12:00 14:00 17:00 20:00 23:59 Time Setting menu in Weekly timer function „ remote controller ● Not only time setting On/Off, but also setting of the operation mode and set temperature can be set by Weekly timer function. Two types of setting: Weekly 1 and Weekly 2 for summer and winter are possible.
  • Page 5: Function List

    FUNCTION LIST „ „ It's shown below function of UTY-RVNM / UTY-RVNYN, UTY-RNNM / UTY-RNNYN and mixture use. When used in mixture, set the UTY-RVNM to Primary unit, and set the UTY-RNNM to Secondary unit. UTY-RVNM UTY-RNNM Mixture use of UTY-RVNYN UTY-RNNYN UTY-RVNM...
  • Page 6 FUNCTIONS 1 Display panel (with backlight) 6 Screen switch button (Right) 2 Screen switch button (Left) 7 Power indicator 3 Menu button 8 On / Off button 4 Cancel button 9 Enter button 5 Cursor button - (OP005 - 05) -...
  • Page 7 SPECIFICATIONS SPECIFICATIONS „ „ Dimensions [H x W x D]: mm (in.) 120 (4-23/32) x 120 (4-23/32) x 21.3 (27/32) Weight: g (oz.) 220 (7.8) WIRING SPECIFICATIONS „ „ Cable size Wire type Remarks UTY-RVNM Use sheathed PVC cable. Remote controller 0.33 mm ( 22AWG ) Polar 3 core cable...
  • Page 8 DIMENSIONS Unit : mm (in.) 33.5 (1-3/16) (1-5/16) 21.3 (27/32) 120 (4-23/32) (29/32) 9 (11/32) 4.5 (3/16) Front View Side View Rear View - (OP005 - 07) -...
  • Page 9 WIRING DESIGN SYSTEM DIAGRAM „ „ 1 remote controller z 2 remote controllers „ Indoor unit Indoor unit A , B , C : Remote controller cable. Secon- Primary dary Remote controller Remote controllers ELECTRICAL WIRING „ „ 1 remote controller z 2 remote controllers „...
  • Page 10 INSTALLATION 1) Installation space. Unit : mm (in.) * Please secure enough space 30 (1-3/16) where a flat screwdriver to take off or more a case can be inserted. 30 (1-3/16) 30 (1-3/16) or more or more 220 (8-21/32) or more* 2) Processing of the remote controller cable.
  • Page 11 4) Installing the remote controller A1 When attaching to switch box: (1) Seal the wiring hole of the remote controller cable. (2) Put a remote controller cable through the hole of the rear case. (3) Fix the rear case by securing it with attached screws (2 places). B1 When attaching to the wall directly: (1) Seal the wiring hole of the remote controller cable.
  • Page 12 5) Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2N • m (8 to 12 lbf • in) 1.
  • Page 13: Function Setting

    FUNCTION SETTING 7-11 SWITCH SETTING Memory backup setting Switch Dual remote controller setting Switch position „ DIP Switch setting „ Memory backup setting ● Set to ON to use batteries for the memory backup. If batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 14 7-21 INDOOR UNIT (setting by controller) Function setting for indoor unit can be done by using the remote controller. As for the "FUNCTION SETTING", refer to the DESIGN & TECHNICAL MANUAL for each product. 1) When [Menu button] is pressed twice while “Monitor” Submenu Mo 10:00 screen is displayed, it switches to the “Submenu”...
  • Page 15 7-31 REMOTE CONTROLLER Perform the following operations within 3 minutes after turning on the power. 1) Enter the “Service” screen. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. Press the [Screen switch button (Left)] and [Screen switch button (Right)] simultaneously for 5 seconds to switch to “Service”...
  • Page 16: Accessory Parts

    ACCESSORY PARTS Q'ty Summary Name and shape UTY-RVN UTY-RVNYN  Installation manual Instruction book for installation Operating manual Instruction book for operation Remote controller cable For connecting the remote controller Connecting cable For connecting the remote controller cable to the wall mounted type and the floor type indoor unit Screw...

This manual is also suitable for:

Uty-rvnyn