Table of Contents
Available languages

Available languages

Series 61 and Series 62
Modutrol IV™ Motors
APPLICATION
The Series 61 and Series 62 Modutrol IV™ Motors are
three-wire spring return and non-spring return floating control
motors. Use these motors with controllers that provide a
switched spdt or floating output to operate dampers or valves.
The Series 62 motors have an internal electrically isolated
feedback potentiometer that provides indication of the motor
shaft position and can be used for slaving Series 90 Motors or
rebalancing an external control circuit.
FEATURES
• Replaces M644, M944B,E,G,H,J,K,R,S and
M945B,C,G,K,L,AD Motors.
• Integral junction box provides NEMA 3 weather
protection.
• Integral spring return returns motor to normal position
upon power failure.
• Motor and circuitry operate from 24 Vac. Models
available with factory installed transformer, or a field
added internal transformer.
• Quick-connect terminals are standard—screw terminal
adapter is available.
• Adapter bracket for matching shaft height of older
motors is available.
• Motors have field adjustable stroke (90° to 160°).
• Die-cast aluminum housing.
• Integral auxiliary switches are available factory
mounted, or can be field added.
• Nominal timing standard of 30 seconds (90° stroke),
and 60 seconds (160° stroke). Other timings available.
• Spring return motors can operate valve linkages from
power end or auxiliary end shafts for normally closed
or normally open valve applications.
• All models have dual shafts (slotted and tapped on
both ends).
• All models have auxiliary switch cams.
• Fixed torque throughout the entire voltage range.
• Motors are designed for either normally open or
normally closed valves and dampers.
• Series 62 models include electrically isolated
potentiometer that provides shaft position indication.
• Series 62 TRADELINE models have linear feedback,
configurable for slaving Series 90 Motors.
SPECIFICATIONS
Models: TRADELINE models are selected and packaged to
provide ease of stocking, ease of handling and maximum
replacement value. TRADELINE model specifications are the
same as those of standard models unless specified otherwise.
PRODUCT DATA
Put Bar Code Here
63-2629EF-01
Table of Contents
loading

Summary of Contents for Honeywell Modutrol IV M6284A1089-S

  • Page 1 Series 61 and Series 62 Modutrol IV™ Motors PRODUCT DATA FEATURES • Replaces M644, M944B,E,G,H,J,K,R,S and M945B,C,G,K,L,AD Motors. • Integral junction box provides NEMA 3 weather protection. • Integral spring return returns motor to normal position upon power failure. • Motor and circuitry operate from 24 Vac. Models available with factory installed transformer, or a field added internal transformer.
  • Page 2 SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS Modutrol IV Order Number Guide: See Table 1. Feedback See Table 2. Dimensions: See Fig. 2. Electrical Ratings: See Table 4. Table 1. Modutrol IV Series 2 Version Order Number Guide. Motor Floating Control Floating Control with feedback 60 lb-in.
  • Page 3 SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS ASYMMETRICAL MOTORS SYMMETRICAL MOTORS VERTICAL VERTICAL VERTICAL REFERENCE VERTICAL REFERENCE REFERENCE REFERENCE FULLY CLOSED FULLY CLOSED FULLY CLOSED FULLY CLOSED FULLY OPEN FULLY OPEN FULLY OPEN FULLY OPEN 90 DEGREE STROKE 160 DEGREE STROKE 90 DEGREE STROKE 160 DEGREE STROKE SPRING RETURN MOTORS AND NON-SPRING RETURN MOTORS...
  • Page 4 SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS TOP VIEW TOP VIEW OF BRACKET 4-7/8 4-1/4 (124) (107) 4-5/8 5-13/16 (116) (148) 5-1/2 2-5/16 (140) (58) 11/16 (17) 13/16 POWER END (20) 1/4 (7) 13/16 (20) 4-7/8 (124) 4-1/16 (103) 1-1/2 (37) 5-9/16 (141) 4-1/16 (103)
  • Page 5: Installation

    You need to order a 7617DM coupling assembly from drilled for 1/4 inch (6.4 mm) machine screws or bolts. Honeywell to use with the cover. • Non-Spring Return Motors are shipped from the factory in the closed position (at the limit of counterclockwise INSTALLATION rotation, as viewed from the power end of the motor).
  • Page 6: Spring Return

    SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS — Crank arm rotation through the downward position. To mount the motor with the bracket: — Sufficient damper linkage to reach the motor shaft. 1. Mount the bracket to the equipment with existing or •...
  • Page 7: Damper Linkages

    SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS Wiring JUNCTION CAUTION Electrical Shock or Equipment Damage Hazard. POWER MOTOR Can shock individuals or short equipment circuitry. END OF MOTOR Disconnect all power supplies before installation. Motors with auxiliary switches can have more than one Q5001 disconnect.
  • Page 8 SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS SERIES 61 SERIES 60 R927C OR R9107A RELAY SERIES 90 MOTOR CONTROLLER CONTROLLER L1 (HOT) (HOT) L1 Q181A 160 STROKE SERIES 62 MOTOR POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. POWER SUPPLY.
  • Page 9 NOTE: Vibration does not affect Modutrol IV Motor performance (as it did in earlier Modutrol Motors). When replacing a motor that was con- nected to an R927C or R9107A Relay, Honeywell recommends performing a retrofit to remove the relay and the old motor. Replace both with one Series 90 Modutrol IV motor (that is, do not replace the relay).
  • Page 10: Settings And Adjustments

    SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS CAUTION YELLOW LEAD BLUE LEAD Equipment Damage Hazard. Can damage the motor beyond repair. Never turn the motor shaft by hand or with a wrench. Forcibly turning the motor shaft damages the gear train and stroke limit contacts.
  • Page 11: Auxiliary Switches

    SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS Auxiliary Switches a. For Non-Spring Return models without a transformer, connect 24 Vac to terminals 2 and 3 to drive motor Adjustable cams actuate the auxiliary switches. These cams open (clockwise as viewed from the power end), or to can be set to actuate the switches at any angle within the terminals 1 and 3 to drive motor closed motor stroke.
  • Page 12: Operation

    SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM. NOTE: CAMS ARE OFFSET VERTICALLY TO 1/8 INCH PROVIDE BETTER VIEW OF BACK CAM. STRAIGHT-BLADE SCREWDRIVER RIGHT/INNER SLOW RISE AUXILIARY PORTION SWITCH (APPROX. 10 DIFF.) INNER AUXILIARY (BLUE)
  • Page 13: Damper Application

    2. Remove the crank arm from the shaft of the old motor height. Valve applications with a Q5001 Linkage do not and remove the old motor. require the 220738A Adapter Bracket. To operate Honeywell 3. Determine mounting bracket necessity. If the linkage V5011 Two-way or V5013 Three-way Valves through full can reach the new motor shaft position and the crank stroke, use a 160°...
  • Page 14: Caractéristiques

    Servomoteurs Modutrol IV Séries 61 et 62 NOTICE TECHNIQUE CARACTÉRISTIQUES • Remplacent les servomoteurs M644, M944B, E, G, H, J, K, R, S et M945B, C, G, K, L, AD. • Boîte de jonction intégrée assurant une protection contre les intempéries selon la norme NEMA 3. •...
  • Page 15: Caractéristiques Techniques

    SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 CARACTÉRISTIQUES Guide des numéros de pièce des Modutrol IV : Voir le Tableau 1. TECHNIQUES Encombrement : Voir la Figure 2. Asservissement : Voir le Tableau 2. Modèles : Les modèles TRADELINE® ont été choisis et emballés pour faciliter le stockage et la manutention et offrir Caractéristiques électriques nominales : une valeur de remplacement maximale.
  • Page 16 SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 Tableau 12. Caractéristiques de rétroaction Série 62 Résistance de shunt asserv. Résistance de rétroaction (résistance Réglage de la Rétroaction servomoteur Numéro de pièce entre les bornes T, G et Y) sensibilité linéaire série 90 M6284F1062-S TG = 370-2800-1990 Courbe ohm (non Non disponible...
  • Page 17 SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 Course : Modèles à course réglable : réglable sur place de Minimum : -40°C (-40°F). 90° à 160° (Voir la marche à suivre pour le réglage de la Poids neutre sur l'arbre (maximum) : course).
  • Page 18 Il faut obtenir un ensemble d'accouplement 7617DM de bornes standards à connexion rapide en bornes à vis. Honeywell qui sera utilisé avec le couvercle. 221455A Bras de manivelle réglable à l'infini; il peut faire une rotation vers le bas et dégager la base du servomoteur INSTALLATION sans qu'il soit nécessaire d'installer un support.
  • Page 19: Montage

    SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 8. Vérifier les caractéristiques spécifiées dans les instruc- Dans les atmosphères très salines, la plaque de montage et tions et indiquées sur le produit, et s'assurer que celui-ci les vis devraient être plaquées au zinc ou au cadmium et non correspond à...
  • Page 20: Accouplement De Vannes

    SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 BOULONS STANDARDS (4) BOULONS FOURNIS (4) BOÎTE DE JONCTION MOTEUR SUPPORT D’ADAPTATION BASE DE L’APPAREIL VIS À MÉTAL OU BOULONS ZINGUÉS Nº 12 OU ¼ PO MF18999 SANS RESSORT DE RAPPEL AVEC RESSORT DE RAPPEL Fig.
  • Page 21 SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 Raccordement POTENTIOMÈTRE DE SENSIBILITÉ (SUR CERTAINS CAUTION MODÈLES DE LA SÉRIE 62, VOIR LE TABLEAU 5) Risque de choc électrique et de dommage matériel. Peut donner un choc électrique ou court-circuiter le circuit du matériel. Couper toute alimentation INTERR.
  • Page 22 SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 SCHÉMA DE CÂBLAGE RÉGULATEUR RÉGULATEUR – APPLICATION EN PARALLÈLE DU M62XX SÉRIE ET SÉRIE 2 DE SÉRIE 62 DE SÉRIE 60 TRANS 3 4 R 1 3 4 R 1 (SOUS TENSION) L1 M62 S2 M62 S1 ALIMENTATION.
  • Page 23 (comme c'était le cas pour les servomoteurs vent alors être remplacés par un servomoteur Modutrol antérieurs). Lors du remplacement Modutrol IV de série 90 (c'est-à-dire qu'il ne d'un servomoteur qui était raccordé à un relais faut pas remplacer le relais). R927C ou R9107A, Honeywell recommande 63-2629EF—01...
  • Page 24: Réglages Et Ajustements

    SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 maximale du sens horaire et l'extrémité maximale du sens antihoraire permet de régler la course à une position entre FIL JAUNE FIL BLEU 160° and 90°. CAUTION À manipuler avec précautions. FIL ROUGE L'usage excessif de la force lors de l'ajustement UTILISER DU FIL DE CLASSE 1 NEC À...
  • Page 25: Interrupteurs Auxiliaires

    SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 3. Amener le servomoteur à la position où l'équipement auxiliaire doit être commandé, comme suit : a. Pour les modèles sans ressort de rappel et sans transformateur, raccorder le courant 24 V c.a. aux bornes 2 et 3 pour amener le servomoteur à...
  • Page 26 SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62 DÉPLACER LE TOURNEVIS PAR LE DESSUS SEULEMENT POUR AJUSTER LA CAME. REMARQUE: LES CAMES SONT DÉSAXÉES À LA VERTICALE POUR OFFRIR UNE MEILLEURE VUE DE L’ARRIÈRE DES CAMES. TOURNEVIS À LAME DROITE DE 3 MM INTERR.
  • Page 27 5-95 % de la tension d'entrée de la deux voies V5011 ou une vanne à trois voies V5013 de position fermée à ouverte. Honeywell sur toute sa course, utiliser un servomoteur à 4. Pour les moteurs à ressort de rappel, s'assurer que la course de 160°.
  • Page 28 SERVOMOTEURS MODUTROL IV SÉRIES 61 ET 62...