Emerson Rosemount 5300 Series Quick Start Manual
Emerson Rosemount 5300 Series Quick Start Manual

Emerson Rosemount 5300 Series Quick Start Manual

Level transmitter, guided wave radar
Hide thumbs Also See for Rosemount 5300 Series:
Quick Start Guide
00825-0100-4530, Rev HA
February 2019
Rosemount
5300 Level Transmitter
Guided Wave Radar
Table of Contents
loading

Summary of Contents for Emerson Rosemount 5300 Series

  • Page 1 Quick Start Guide 00825-0100-4530, Rev HA February 2019 ™ Rosemount 5300 Level Transmitter Guided Wave Radar...
  • Page 2: Table Of Contents

    Quick Start Guide February 2019 Contents About this guide..........3 Configure.............22 ® Confirm system readiness (HART only)..5 Safety Instrumented Systems (4-20 mA only).. Mount transmitter on tank......6 Adjust probe length........26 Prepare the electrical connections....11 Product certifications........29 Connect wiring and power up...... 19 Rosemount 5300 Level Transmitter...
  • Page 3: About This Guide

    Level Transmitter. Refer to the Rosemount 5300 Reference Manual for more instructions. The manual and this guide are also available electronically on Emerson.com/Rosemount. WARNING Failure to follow safe installation and servicing guidelines could result in death or serious injury. •...
  • Page 4 Quick Start Guide February 2019 WARNING Probes with non-conducting surfaces • Probes covered with plastic and/or with plastic discs may generate an ignition-capable level of electrostatic charge under certain extreme conditions. Therefore, when the probe is used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
  • Page 5: Confirm System Readiness (Hart ® Only)

    Verify that the latest Device Driver (DD/DTM ) is loaded on your systems to ensure proper communication. See Table 2-1. • Download the latest Device Driver from Emerson.com/DeviceInstallKits. Table 2-1: Rosemount 5300 Device Revisions and Files Firmware version Find Device Driver ® HART...
  • Page 6: Mount Transmitter On Tank

    Quick Start Guide February 2019 Mount transmitter on tank For flexible single lead probes ordered with weight unmounted (option code WU), refer to Adjust probe length before mounting the transmitter. ® Threaded/Flange/Tri-Clamp tank connection Procedure 1. Seal and protect the threads. Only for NPT threaded tank connection.
  • Page 7 February 2019 Quick Start Guide A. Tri-Clamp B. BSP/G C. Gasket 3. (Optional) Adjust display orientation. 4. Tighten the nut. Torque 30 ft-lb (40 Nm) Quick Start Guide...
  • Page 8 Quick Start Guide February 2019 Install remote housing Procedure 1. Carefully remove the transmitter. 2. Mount the probe on tank. A. Gasket 3. Mount the remote connection on the probe. Torque 30 ft-lb (40 Nm) Rosemount 5300 Level Transmitter...
  • Page 9 February 2019 Quick Start Guide 4. Mount the bracket to the pipe. A. Horizontal pipe B. Vertical pipe 5. Fasten the housing support. 6. Mount the transmitter head. Torque 30 ft-lb (40 Nm) Quick Start Guide...
  • Page 10: Bracket Mounting

    Quick Start Guide February 2019 Bracket mounting Procedure 1. Mount the bracket to the pipe/wall. On pipe: A. Horizontal pipe B. Vertical pipe On wall: 2. Mount the transmitter with probe to the bracket. Rosemount 5300 Level Transmitter...
  • Page 11: Prepare The Electrical Connections

    February 2019 Quick Start Guide Prepare the electrical connections Cable gland/conduit For explosion-proof/flameproof installations, only use cable glands or conduit entry devices certified explosion-proof or flameproof. Power supply (Vdc) ® ™ Approval type HART RS-485 with OUNDATION ® Fieldbus Modbus None 16-42.4 9-32...
  • Page 12 Quick Start Guide February 2019 ® 4-20 mA/HART communication 4.3.1 Wiring diagram ® Figure 4-1: Wiring Diagram for 4-20 mA/HART A. Handheld communicator B. Approved IS barrier (for Intrinsically Safe installations only) C. HART modem D. Current meter E. Load resistance (≥250 Ω) F.
  • Page 13 February 2019 Quick Start Guide Figure 4-2: Intrinsically Safe Installations A. Loop Resistance (Ohms) B. External Power Supply Voltage (Vdc) C. Operating region Figure 4-3: Non-Hazardous and Non-Sparking/Energy Limited Installations A. Loop Resistance (Ohms) B. External Power Supply Voltage (Vdc) C.
  • Page 14 Quick Start Guide February 2019 Figure 4-4: Explosion-Proof /Flameproof (Ex d) Installations A. Loop Resistance (Ohms) B. External Power Supply Voltage (Vdc) C. Operating region Note For the Ex d case, the diagram is only valid if the load resistance is at the + side and if the - side is grounded, otherwise the maximum load resistance is limited to 435 Ω.
  • Page 15: Power Consumption

    February 2019 Quick Start Guide ™ Fieldbus OUNDATION 4.4.1 Wiring diagram Figure 4-5: Wiring Diagram for F Fieldbus OUNDATION A. Handheld communicator B. Approved IS barrier (for Intrinsically Safe installations only) C. F Fieldbus modem OUNDATION D. Power supply Note Rosemount 5300 Level Transmitters with flameproof/explosion-proof output have a built-in barrier;...
  • Page 16 Quick Start Guide February 2019 4.5.2 Wiring diagram ® Figure 4-6: Wiring Diagram for RS-485 with Modbus A. “A” line B. “B” line C. 120 Ω D. RS-485 Bus E. Power supply F. HART - G. HART + H. If it is the last transmitter on the bus, connect the 120 Ω termination resistor.
  • Page 17 February 2019 Quick Start Guide Note Grounding the transmitter via threaded conduit connection may not provide sufficient ground. Note In the explosion-proof/flameproof version, the electronics is grounded via the transmitter housing. After installation and commissioning make sure that no ground currents exist due to high ground potential differences in the installation.
  • Page 18 Quick Start Guide February 2019 Figure 4-8: Cable Shield A. Insulate shield B. Minimize distance C. Trim shield and insulate D. Connect shield back to the power supply ground Rosemount 5300 Level Transmitter...
  • Page 19: Connect Wiring And Power Up

    February 2019 Quick Start Guide Connect wiring and power up Procedure Make sure the power supply is switched off. 2. Remove the terminal block cover. 3. Remove the plastic plugs. 4. Pull the cable through the cable gland/conduit. Adapters are required if M20 glands are used. Quick Start Guide...
  • Page 20 Quick Start Guide February 2019 5. Connect the cable wires (see Figure 4-1, Figure 4-5, and Figure 4-6). 6. Ensure proper grounding (see Grounding). 7. Use the enclosed metal plug to seal any unused port. Note Apply PTFE tape or other sealant to the threads. 8.
  • Page 21 February 2019 Quick Start Guide Mount the cover making sure the cover is secure to meet explosion- proof requirements. 10. Turn the jam screw counterclockwise until it contacts the cover. Required for Flameproof installations only. 11. Connect the power supply. Quick Start Guide...
  • Page 22: Configure

    Quick Start Guide February 2019 Configure Basic configuration can easily be done either with Rosemount Radar Master, a ™ handheld communicator, AMS Device Manager, DeltaV , or any other DD ™ (Device Description) or DTM compatible host system. For advanced configuration features, Rosemount Radar Master is recommended.
  • Page 23 February 2019 Quick Start Guide 3. In the Device Connection View, double-click the modem icon. 4. Double-click the device icon. 6.2.2 Connect to device using a handheld communicator Procedure Turn on the handheld communicator and connect to the device. 6.2.3 Configure device ®...
  • Page 24 Quick Start Guide February 2019 ™ Fieldbus parameters OUNDATION Table 6-1: F Fieldbus Parameters OUNDATION Function Parameter Probe type TRANSDUCER_1100 > PROBE_TYPE Probe length TRANSDUCER_1100 > PROBE_LENGTH Hold off distance/Upper null zone TRANSDUCER_1100 > GEOM_HOLD_OFF_DIST Tank height TRANSDUCER_1100 > GEOM_TANK_HEIGHT Mounting type TRANSDUCER_1100 >...
  • Page 25: Safety Instrumented Systems (4-20 Ma Only)

    February 2019 Quick Start Guide Safety Instrumented Systems (4-20 mA only) For Safety Certified installations, refer to the Rosemount 5300 Reference Manual. Quick Start Guide...
  • Page 26: Adjust Probe Length

    Quick Start Guide February 2019 Adjust probe length This section describes how to adjust the length of flexible single lead probes with weight unmounted (option code WU). For other probe types, refer to Section 3 in the Rosemount 5300 Reference Manual.
  • Page 27 February 2019 Quick Start Guide 3. Mark where to cut the probe. 4. Slide the weight up. 5. Cut the probe at the mark. Quick Start Guide...
  • Page 28 Quick Start Guide February 2019 6. Fasten the weight. Weight material Torque (Nm) Stainless steel Alloy C-276 Alloy 400 Duplex 2205 7. Update transmitter configuration to the new probe length. Probe length (L): Rosemount 5300 Level Transmitter...
  • Page 29: Product Certifications

    EU Declaration of Conformity. The most current revision is available at Emerson.com/Rosemount. Safety Instrumented Systems (SIS) SIL 3 Capable: IEC 61508 certified for use in safety instrumented systems up to SIL 3 (Minimum requirement of single use (1oo1) for SIL 2 and redundant use (1oo2) for SIL 3).
  • Page 30 Quick Start Guide February 2019 2. WARNING – The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. 9.5.2 I5 Intrinsic Safety (IS), Nonincendive (NI) Certificate FM16US0444X Standards FM Class 3600 –...
  • Page 31 February 2019 Quick Start Guide accordance with control drawing 9240030-936; -50 °C ≤ Ta ≤ 60 °C / 70 °C; Type 4X Special Conditions for Safe Use (X): 1. WARNING – Potential Electrostatic Charging Hazard – The enclosure contains non-metallic material. To prevent the risk for electrostatic sparking the plastic surface should only be cleaned with a damp cloth.
  • Page 32 Quick Start Guide February 2019 Entity parameters 30 V 130 mA 7.26 nF HART Entity parameters 30 V 300 mA 1.3 W Fieldbus 9.6.3 IF FISCO Certificate 1514653 Standards CSA C22.2 No.0-M91, CSA C22.2 No.25-1966, CSA C22.2 No.30-M1986, CSA C22.2 No.94-M91, CSA C22.2 No.142- M1987, CSA C22.2 157-92, CAN/CSA C22.2 No.
  • Page 33 February 2019 Quick Start Guide 2. Parts of the sensor probes, for type 5300 are non-conducting material covering metal surfaces. The area of the non-conducting part exceeds the maximum permissible areas for Group III according to EN 60079-0.2012 clause 7.4:3. Therefore, when the probe is used in a potentially explosive atmosphere group III, EPL Da, appropriate measures must be taken to prevent electrostatic discharge.
  • Page 34 Quick Start Guide February 2019 9.7.3 IA ATEX FISCO Certificate Nemko 04ATEX1073X Standards EN 60079-0:2012, EN 60079-1:2014, EN 60079-11:2012, EN 60079-26:2015, EN 60079-31:2014 Markings II 1G Ex ia IIC T4 Ga (-55 °C ≤ Ta ≤+60 °C) or II 1/2G Ex ia/ib IIC T4 Ga/Gb (-55 °C ≤ Ta ≤ +60 °C) II 1D Ex ia IIIC T69 °C Da, (-50 °C ≤...
  • Page 35 February 2019 Quick Start Guide Standards EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010, EN 60079-31:2014 Markings II 3G Ex nA ic IIC T4 Gc (-50 °C ≤ Ta ≤ +60 °C /+70 °C) II 3G Ex ic IIC T4 Gc (-50 °C ≤ Ta ≤ +60 °C /+70 °C) II 3D Ex tc IIIC T69 °C/T79 °C Dc (-50 °C ≤...
  • Page 36 Quick Start Guide February 2019 atmosphere group III, EPL Da, appropriate measures must be taken to prevent electrostatic discharge. 3. ½” NPT threads need to be sealed for dust and water ingress protection, IP 66, IP 67 or “Ex t”, EPL Da or Db is required. 9.8.2 I7 IECEx Intrinsic Safety Certificate IECEx NEM 06.0001X Standards IEC 60079-0:2011, IEC 60079-1:2014-06, IEC 60079-11:2011;...
  • Page 37 February 2019 Quick Start Guide Standards IEC 60079-0:2011, IEC 60079-1:2014-06, IEC 60079-11:2011; IEC 60079-26:2014, IEC 60079-31:2013 Markings Ex ia IIC T4 Ga (-55 °C ≤ Ta ≤ +60 °C) Ex ia/ib IIC T4 Ga/Gb (-55 °C ≤ Ta ≤ +60 °C) Ex ia IIIC T69 °C Da (-50 °C ≤...
  • Page 38 Quick Start Guide February 2019 Ex tc IIIC T69 °C/T79 °C Dc (-50 °C ≤ Ta ≤ +60 °C /+70 °C) Special Conditions for Safe Use (X): 1. The transmitter circuits does not withstand 500V AC dielectric strength test according to EN 60079-11 clause 6.3.13 due to earth connected transient suppressing devices.
  • Page 39 February 2019 Quick Start Guide Entity parameters 30 V 130 mA 1.0 W 7.26 nF Negligible HART Entity parameters 30 V 300 mA 1.5 W 4.95 nF Negligible Fieldbus 9.9.3 IB INMETRO FISCO Certificate UL-BR 17.0188X Standards ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013, ABNT NBR IEC 60079-26:2016, ABNT NBR IEC 60079-31:2014 Markings Ex ia IIC T4 Ga (- 55 °C ≤...
  • Page 40 Quick Start Guide February 2019 Markings Ex ia IIC T4 Ga (-50 °C ≤ Ta ≤ +60 °C/+70 °C) Ex iaD 20 T69 °C /T79 °C (-50 °C ≤ Ta ≤ +60 °C/+70 °C) Ex iaD/ibD 20/21 T69 °C (-50 °C ≤ Ta ≤ +60 °C) Special Conditions for Safe Use (X): 1.
  • Page 41 February 2019 Quick Start Guide Safety parameters 42.4 V 23 mA 7.25 nF Negligible HART Safety parameters 32 V 21 mA 0.7 W 4.95 nF Negligible Fieldbus 9.11 Technical Regulations Customs Union (EAC) 9.11.1 EM Technical Regulations Customs Union (EAC) Flameproof Certificate RU C-SE.AA87.B.00802 Ga/Gb Ex db ia IIC T4….T1 X, (-40 °C ≤...
  • Page 42 Quick Start Guide February 2019 Special Conditions for Safe Use (X): 1. See certificate for Specific Conditions. 9.13 Republic of Korea 9.13.1 EP Flameproof HART Certificate KTL 15-KB4BO-0297X Markings Ex d ia IIC T4 Ga/Gb Special Conditions for Safe Use (X): 1.
  • Page 43 February 2019 Quick Start Guide 9.16 Uzbekistan 9.16.1 Safety (import) Certificate UZ.SMT.01.342.2017121 9.17 Combinations Combination of E1, E5 and E6 Combination of E1, E5 and E7 Combination of E1, E6 and E7 Combination of E5, E6 and E7 Combination of I1, I5 and I6 Combination of I1, I5 and I7 Combination of I1, I6 and I7 Combination of I5, I6 and I7...
  • Page 44 Quick Start Guide February 2019 Note Housing material A, Aluminum, is not to be used on open decks. 9.18.3 SDN Det Norske Veritas Germanischer Lloyd (DNV GL) Type Approval Certificate TAA000020G Intended Use DNV GL rules for classification – Ships, offshore units, and high speed and light craft Table 9-1: Application Location classes...
  • Page 45 February 2019 Quick Start Guide 9.18.7 QT Safety-certified to IEC 61508 with certificate of FMEDA data Certificate exida ROS 13-06-005 C001 R1.3 9.18.8 Suitable for intended use Compliant with NAMUR NE 95, version 22.01.2013 “Basic Principles of Homologation” 9.19 Pattern Approval GOST Belarus Certificate RB-03 07 2765 10...
  • Page 46 Quick Start Guide February 2019 Table 9-2: Conduit Plug Thread Sizes Thread Identification mark M20 x 1.5 ½ - 14 NPT ½ NPT Table 9-3: Thread Adapter Thread Sizes Male thread Identification mark M20 x 1.5 – 6g ½- 14 NPT ½...
  • Page 47: Installation Drawings

    February 2019 Quick Start Guide 9.21 Installation drawings Figure 9-1: 9240030-936 - System Control Drawing for Hazardous Location Installation of Intrinsically Safe FM Approved Apparatus Quick Start Guide...
  • Page 48 Quick Start Guide February 2019 Figure 9-2: 9240030-937 - Installation Drawing for Hazardous Location Installation of Intrinsically Safe CSA Approved Apparatus Rosemount 5300 Level Transmitter...
  • Page 49 February 2019 Quick Start Guide Figure 9-3: D9240030-938 - Installation Drawing for Hazardous Location Installation of Intrinsically Safe ATEX and IECEx Approved Apparatus Quick Start Guide...
  • Page 50 Quick Start Guide February 2019 Figure 9-4: 9240031-957 - Installation Drawing Exn Rosemount 5300 Level Transmitter...
  • Page 51: Eu Declaration Of Conformity

    February 2019 Quick Start Guide 9.22 EU Declaration of Conformity Figure 9-5: EU Declaration of Conformity Quick Start Guide...
  • Page 52 Quick Start Guide February 2019 Rosemount 5300 Level Transmitter...
  • Page 53 February 2019 Quick Start Guide Quick Start Guide...
  • Page 54 Quick Start Guide February 2019 Rosemount 5300 Level Transmitter...
  • Page 55 February 2019 Quick Start Guide 9.23 China RoHS List of Model Parts with China RoHS Concentration above MCVs 含有 管控物 超 的部件型号列表 China RoHS Hazardous Substances / 有害物 Hexavalent Polybrominated Polybrominated Part Name 部件名称 Lead Mercury Cadmium 汞 Chromium biphenyls diphenyl ethers (PBDE) (Pb)
  • Page 56 The Emerson logo is a Facebook.com/Rosemount trademark and service mark of Emerson Electric Youtube.com/user/ Co. Rosemount is mark of one of the Emerson RosemountMeasurement family of companies. All other marks are the Google.com/+RosemountMeasurement property of their respective owners.