Siemens SINAMICS S120 System Manual

Siemens SINAMICS S120 System Manual

Grid infeed
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Quick Links

Table of Contents
loading

Summary of Contents for Siemens SINAMICS S120

  • Page 3 ___________________ Grid infeed Preface Fundamental safety ___________________ instructions ___________________ SINAMICS General information ___________________ Grid types S120 Grid infeed ___________________ Standards and directives ___________________ Function modules System Manual ___________________ Detailed descriptions of the function modules ___________________ Commissioning ___________________ Device overview ___________________ Function diagrams ___________________ Appendix...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Preface

    Detailed information on general hardware, software functions and engineering information/instructions are described in separate documentation and can obtained from the regional SIEMENS office and used as supplementary information for this documentation. Target group This document is used by system integrators and Original Equipment Manufacturers (OEMs) to operate, parameterize and commission the SINAMICS devices with the associated software functions for power infeed.
  • Page 6 The EC Declaration of Conformity for the EMC Directive and for the Low Voltage Directive can be found/obtained from the relevant regional office of the DF MC or PD LD Business Units of Siemens AG. Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 7: Table Of Contents

    Table of contents Preface ..............................5 Fundamental safety instructions ......................11 General safety instructions ..................... 11 Safety instructions for electromagnetic fields (EMF) .............. 14 Handling electrostatic sensitive devices (ESD) ..............15 Industrial security ........................16 Residual risks of power drive systems ..................17 General information ..........................
  • Page 8 Table of contents 5.3.5 Additional closed-loop controls function module ..............47 5.3.5.1 Reactive current/apparent current limits ................47 Detailed descriptions of the function modules ..................49 Additional closed-loop controls for current-controlled operation ..........49 6.1.1 Background information ......................49 6.1.2 Dynamic grid support ......................
  • Page 9 Table of contents Commissioning the grid droop control .................. 111 7.7.1 Black start in an island grid ....................111 7.7.2 Synchronizing an island grid to an external power grid ............114 7.7.3 Overview of important parameters ..................120 7.7.4 Function block diagrams ....................... 122 Commissioning of dynamic grid support ................
  • Page 10 Table of contents Active Interface Modules, liquid-cooled ................166 8.5.1 Chassis format ........................166 Liquid-cooled Active Line Modules for the grid infeed, chassis format ........ 167 8.6.1 Description ........................... 167 8.6.2 Safety information ........................ 169 8.6.3 Interface description ......................172 8.6.3.1 Overview ..........................
  • Page 11: Fundamental Safety Instructions

    Fundamental safety instructions General safety instructions DANGER Danger to life due to live parts and other energy sources Death or serious injury can result when live parts are touched. • Only work on electrical devices when you are qualified for this job. •...
  • Page 12 Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life when live parts are touched on damaged devices Improper handling of devices can cause damage. Hazardous voltages can be present at the housing or exposed components on damaged devices. •...
  • Page 13 Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life through unexpected movement of machines when using mobile wireless devices or mobile phones Using mobile wireless devices or mobile phones with a transmitter power > 1 W closer than approx.
  • Page 14: Safety Instructions For Electromagnetic Fields (Emf)

    Fundamental safety instructions 1.2 Safety instructions for electromagnetic fields (EMF) WARNING Danger to life when safety functions are inactive Safety functions that are inactive or that have not been adjusted accordingly can cause operational faults on machines that could lead to serious injury or death. •...
  • Page 15: Handling Electrostatic Sensitive Devices (Esd)

    Fundamental safety instructions 1.3 Handling electrostatic sensitive devices (ESD) Handling electrostatic sensitive devices (ESD) Electrostatic sensitive devices (ESD) are individual components, integrated circuits, modules or devices that may be damaged by either electric fields or electrostatic discharge. NOTICE Damage through electric fields or electrostatic discharge Electric fields or electrostatic discharge can cause malfunctions through damaged individual components, integrated circuits, modules or devices.
  • Page 16: Industrial Security

    Note Industrial security Siemens provides automation and drive products with industrial security functions that support the secure operation of plants or machines. They are an important component in a holistic industrial security concept. With this in mind, our products undergo continuous development.
  • Page 17: Residual Risks Of Power Drive Systems

    Fundamental safety instructions 1.5 Residual risks of power drive systems Residual risks of power drive systems The control and drive components of a drive system are approved for industrial and commercial use in industrial line supplies. Their use in public line supplies requires a different configuration and/or additional measures.
  • Page 18 Fundamental safety instructions 1.5 Residual risks of power drive systems 3. Hazardous shock voltages caused by, for example: – Component malfunctions – Influence of electrostatic charging – Induction of voltages in moving motors – Operating and/or ambient conditions outside of the specification –...
  • Page 19: General Information

    General information To assess the inverter system required, the following distinction can be made between the types of power generation: ● Power generation with rotating machines ● Power generation without rotating machines In particular, the amount of power generated depends largely on fluctuating ambient conditions, such as wind speed or exposure to sunlight.
  • Page 20 General information For power sources such as batteries, fuel cells or photovoltaic, for example, the electrical energy is converted using chemical processes or semiconductors. As a rule, the resulting DC voltage must be converted to a 3-phase AC voltage for distribution in the power grid. ①...
  • Page 21: Grid Types

    Grid types Power grid A power grid covers a wide area, is generally supraregional and comprises large power generating units (regarding the electric power). It is operated by a power supply utility, which is responsible for the grid, and therefore also grid codes. Generating units, which feed into a power grid must synchronize their voltage and frequency to that of the power grid.
  • Page 22 Grid types 3.1 Power grid Function modules for the power grid When operating a generating unit connected to a power grid, a power utility company can specify grid codes. Software functions are required to fulfill the requirements resulting from grid codes. These are defined in function modules, and must be explicitly activated. The following function modules of the Active Line Module are typically required to satisfy the requirements arising from grid codes: ●...
  • Page 23: Island Grid

    Grid types 3.2 Island grid Island grid An island grid supplies a limited area and has no connection to the public grid or to other grids. The utility company operating the grid must maintain the balance between used and generated power in the island grid; an energy storage system can be used. The company operating an island grid can define their own grid codes.
  • Page 24: Microgrid

    Grid types 3.3 Microgrid Microgrid A micro grid represents a locally constrained electrical system with several power generating units, loads and possibly energy storage systems. This can be connected to a large power grid – or can also be independently operated (i.e. an island grid with one or several power generating units).
  • Page 25: Standards And Directives

    Standards and directives When feeding electric power into a grid, different requirements can apply depending on the actual location. Frequently, the requirements depend on the particular country, and in some cases depend on the specific guidelines (grid codes) of the individual power utility company. This is complemented by the individual conditions resulting from the power generating application itself.
  • Page 26: Grid Codes/Standards

    Sinamics Active Line Modules in the booksize format with the available supplementary functions and the appropriate circuitry comply with all of the requirements of the directive, which involve the grid converter. Siemens can provide the appropriate instructions, test reports and partial declarations of conformity. Based on these, the system manufacturer can prove the conformance of his power generating unit.
  • Page 27 Siemens offers a 120 kVA grid converter – certified to CEI 0-21 – as a ready-to- connect control cabinet, based on the Sinamics S120. Higher power ratings are possible by connecting units in parallel.
  • Page 28 Standards and directives 4.5 Standards for Germany, Italy, USA Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 29: Function Modules

    Function modules The function modules, which are required to feed power into an island grid or micro grid – or to fulfill the grid code requirements of a power grid – are described in this chapter. Overview Power and island grids have different requirements relating to the open-loop and closed-loop control for grid infeeds.
  • Page 30 Function modules 5.1 Overview ● Function module for grid droop control The "Grid droop control" function module enables an island grid to be created. The inverter for feeding into the grid has the task of controlling the frequency and the voltage in the grid, and assumes an "grid former function".
  • Page 31 Function modules 5.1 Overview ● Function module dynamic grid support The "Dynamic grid support" function module allows grid faults to be ridden through and allows grid-supporting reactive currents to be injected; this is specified in many grid codes in order to clear short-circuits. Contrary to line droop operation for island grids, in this particular case, the Active Line Module is operated as grid support element with DC link voltage and grid current control.
  • Page 32 "Grid transformer" and "Dynamic grid support" modules are not required. Function modules requiring a license The function modules "Grid control" and "Dynamic grid support" must be ordered as an option for the SINAMICS S120 memory card: ● Booksize device: Licensing corresponding to the power rating and application ●...
  • Page 33: Typical Applications Of Grid Infeed To Generate Power

    Function modules 5.2 Typical applications of grid infeed to generate power Typical applications of grid infeed to generate power The function modules for grid infeed are typically required for the following applications: ● Photovoltaic (PV) inverters for power grid operation "Grid transformer"...
  • Page 34: Description Of The Function Modules

    Function modules 5.3 Description of the function modules Description of the function modules 5.3.1 Line transformer function module Task The main task of this function module is to magnetize a line transformer before connecting the power generation system to the grid. This magnetization is always necessary and expedient when the grid transformer forms part of the system and is also disconnected from the grid when the system is shut down.
  • Page 35: Identification Of The Transformer Data

    Function modules 5.3 Description of the function modules 5.3.1.2 Identification of the transformer data The main and leakage inductance of the transformer are identified – together with the phase shift and the voltage correction. 5.3.1.3 Line filter and transformer monitoring As already described, network connection regulations stipulate the provision of short-circuit current during short-term short-circuits in the power grid.
  • Page 36 Function modules 5.3 Description of the function modules Prerequisite for the operating mode "Grid control" is that the DC link voltage is specified or controlled by one of the connected power generating units (generator-inverter, battery, photovoltaic array, etc. ). Note Automatic shutdown The Active Line Module switches to this operating mode in the case of frequency faults (120% of the set upper frequency threshold p0284 –...
  • Page 37 Function modules 5.3 Description of the function modules Grid control operating mode As explained at the beginning of this Chapter, the "Line droop control" function module includes the new "Grid control" operating mode to control the grid frequency and grid voltage in an island grid.
  • Page 38 Function modules 5.3 Description of the function modules Droop function to control the frequency and voltage of the network, including load distribution Using the droop functions, is possible to establish an island grid and supply it, together with other generating units. In this case, all of the generating units in this island grid must have comparable droop functions.
  • Page 39: Black Start In An Island Grid

    Function modules 5.3 Description of the function modules 5.3.2.1 Black start in an island grid Description The "Island grid black start" function allows an autonomous island grid to be established and subsequently maintained with the grid droop control. For a black start (p5580 = 2) initially, a check is made as to whether the island grid is in a no- voltage condition.
  • Page 40: Function Module, Dynamic Grid Support

    Function modules 5.3 Description of the function modules 5.3.3 Function module, dynamic grid support The function module includes the "Dynamic grid support" function to support the grid when voltage dips occur – and the "Grid monitoring anti-islanding" function in order to detect an undesirable creation of an island grid.
  • Page 41 Function modules 5.3 Description of the function modules Example of a characteristic curve for dynamic grid support in accordance with German BDEW Guidelines for connection to medium-voltage grids Figure 5-4 Dynamic grid support with voltage control in accordance with German BDEW Guidelines Explanations for voltage control: ●...
  • Page 42 Function modules 5.3 Description of the function modules Example of a grid code: German BDEW Guidelines Figure 5-5 Limiting characteristics for the voltage characteristic at the network connection point Explanation of the voltage characteristic: ① In the area above the borderline 1, the infeed operation is stabile ②...
  • Page 43: Grid Monitoring Anti-Islanding

    Function modules 5.3 Description of the function modules NOTICE Damage to other grid components as a result of overvoltage Without using additional monitoring functions, the dynamic grid support can mean that even when a subgrid is completely isolated from the power grid (unintentional creation of an island grid), PWM/pulsed operation of the Active Line module in the disconnected subgrid is maintained.
  • Page 44: Voltage-Time Monitoring

    Function modules 5.3 Description of the function modules Function As the grid control is missing, generally the creation of an island grid quickly results in violation of the frequency and voltage limit values. As a consequence, it is detected by the frequency and voltage monitoring function.
  • Page 45: Other Monitoring Functions That Can Be Activated

    Function modules 5.3 Description of the function modules 5.3.3.5 Other monitoring functions that can be activated Monitoring additional voltage/frequency thresholds when switching on or switching on again Some individual grid codes specify that when switching on or switching on again, before the operating enable, the voltage and/or the frequency must be additionally checked.
  • Page 46 Function modules 5.3 Description of the function modules Note Definition, displacement factor cosφ Displacement factor cosφ is also defined as the cosine of the phase angle φ between the sinusoidal oscillations of the voltage and the current having the same frequency. For a more precise designation, an index is therefore added corresponding to the particular frequency or harmonic number.
  • Page 47: Additional Closed-Loop Controls Function Module

    Function modules 5.3 Description of the function modules 5.3.5 Additional closed-loop controls function module 5.3.5.1 Reactive current/apparent current limits Background Using current limits, the operating behavior of the Active Line Module can be adapted to address the requirements of an application. Current limits are available for various current types, operating states and parameter types.
  • Page 48 Function modules 5.3 Description of the function modules Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 49: Detailed Descriptions Of The Function Modules

    Detailed descriptions of the function modules Additional closed-loop controls for current-controlled operation 6.1.1 Background information The following diagram shows the control structure of a grid inverter for feeding power into a power grid, together with a typical system configuration. The function blocks added to comply with the different global grid codes are marked in gray.
  • Page 50: Dynamic Grid Support

    Detailed descriptions of the function modules 6.1 Additional closed-loop controls for current-controlled operation Figure 6-1 Additional modules for current-controlled operation 6.1.2 Dynamic grid support Background A parameterizable characteristic allows a reactive current to be specified corresponding to the deviation of the grid voltage from its rated value. This is specified in many grid codes. The background to this requirement is the inductive behavior of a grid inverter, whose most simple equivalent circuit diagram comprises a series circuit of a controlled voltage source and inductance L.
  • Page 51 Detailed descriptions of the function modules 6.1 Additional closed-loop controls for current-controlled operation Conversely, a reactive current results in a voltage change at inverter outputs u12, u23. The characteristic is selected so that the line voltage change is counteracted, therefore helping to stabilize the grid voltage (inverter acts as grid support element).
  • Page 52: Dc Component Controller

    ["Verfahren und Vorrichtung zur Ausregelung von Verzerrungen im Magnetisierungsstrom eines Transformators, der mit einem selbstgeführten Stromrichter mit abschaltbaren Leistungshalbleiterschaltern verknüpft ist", EP0896420, H. Weiss, Siemens AG]: A DC current component in the phase currents shifts the magnetic operating point of a transformer.
  • Page 53: Negative Sequence System Current Controller

    Detailed descriptions of the function modules 6.1 Additional closed-loop controls for current-controlled operation When the magnetizing inductance of the transformer is not known (type plate, data sheet), then the magnetizing inductance can also be measured (p5480 = 11). It should be taken into account that the identification result r5491, especially for transformers with low magnetizing current (large magnetizing inductance L ) is very sensitive with respect to disturbing...
  • Page 54: Grid-Friendly Transformer Magnetization

    Detailed descriptions of the function modules 6.1 Additional closed-loop controls for current-controlled operation In most applications, a setpoint other than zero does not make sense. During an FRT, a possibly required non-symmetrical support current is directly injected internally (p5509[8]). In the default setting of the dynamic grid support with p5500.3 = 1, the negative sequence system control is automatically activated, in order to guarantee current symmetry even for 2- phase grid faults.
  • Page 55: Controls For Grid Droop Operation

    Detailed descriptions of the function modules 6.2 Controls for grid droop operation The status is displayed in r5482 and r5499. If a transformer is not being used, a 1:1 transformer can be parameterized (for example, to still be able to use other functions such as the DC component controller etc.). Controls for grid droop operation 6.2.1 Background information...
  • Page 56 Detailed descriptions of the function modules 6.2 Controls for grid droop operation Figure 6-2 Basic control concept Overview In island grid operation, a generating system must play its role in maintaining the voltage and frequency (grid former). Stiffly impressing voltage and frequency would be conceivable using inverters.
  • Page 57 Detailed descriptions of the function modules 6.2 Controls for grid droop operation the generator inductances in the island grid. The downstream voltage controller ensures a steady-state accuracy of the voltage amplitude at the connection terminals, and therefore compensates the impedance of the inverter generating system. Figure 6-3 Grid droop control Droop characteristics f...
  • Page 58 Detailed descriptions of the function modules 6.2 Controls for grid droop operation control. At the same time, a DC component controller suppresses possible DC fault components in the phase voltages, which would otherwise result in transformer saturation effects and power oscillations in the grid. Providing high short-circuit currents to clear grid faults (trip fuses) is another important requirement placed on power generating systems.
  • Page 59: U-F Droop Control

    Detailed descriptions of the function modules 6.2 Controls for grid droop operation 6.2.2 U-f droop control Background The load equalization (balancing) between the power generating units in the grid, which is required for stable operation at an operating point with common frequency and amplitude, is preferably realized using droop characteristics (see the following diagrams).
  • Page 60 Detailed descriptions of the function modules 6.2 Controls for grid droop operation Figure 6-5 Common operating point of several power generating units in the grid Typically, the primary control in grids is a fast P control, which cannot control system deviations down to zero.
  • Page 61 Detailed descriptions of the function modules 6.2 Controls for grid droop operation ● The harmonic content of the output voltage depends very heavily on the modulation depth r0074, i.e. the ratio of the voltage at the AC terminals of the inverter with respect to the DC link voltage.
  • Page 62: Damping Power Oscillations

    Detailed descriptions of the function modules 6.2 Controls for grid droop operation Note Regarding the current limits (e.g. for heavy-duty drive starting, when transformers are switched-in as well as for grid short-circuits) with p5478, see Chapter Commissioning active, reactive and apparent current limiting (Page 132). 6.2.3 Damping power oscillations When several power generating units operate in a grid, power oscillations and undesirable...
  • Page 63: Dc Component Controller

    Detailed descriptions of the function modules 6.3 Supplementary functions 6.2.4 DC component controller Application Regarding the background information, please refer to the section on the DC component control in current-controlled operation, see DC component controller (Page 52). Contrary to this, the DC component control in the grid controlled operation is generally mandatory, especially if the island grid contains transformers.
  • Page 64: Transformer Model And Identification

    Detailed descriptions of the function modules 6.3 Supplementary functions The administration parameters for this can be found starting at p0150[0]ff, the VSM measured values are then available in index 0 of parameter p5460. Voltages u12 /u23 must be sensed using an additional VSM10 if the "Island grid synchronization"...
  • Page 65: Back-To-Back Operation Of Active Line Modules

    Detailed descriptions of the function modules 6.4 Back-to-back operation of Active Line Modules Back-to-back operation of Active Line Modules Frequency of the power grid Frequency of the island grid Line filter of the power grid Line filter of the island grid Figure 6-6 Back-to-back operation - diagram showing the principle of operation Back-to-back operation of Active Line Modules designates the connection between two...
  • Page 66 Detailed descriptions of the function modules 6.4 Back-to-back operation of Active Line Modules Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 67: Commissioning

    Commissioning The functions for grid infeed as well as island grid operation were described in the previous chapters. Reference was also made to the parameter settings required. The steps obtained for commissioning typical system configurations are shown in tabular form based on two application examples. Individual aspects are then separately discussed, for example setting transformer parameters.
  • Page 68: Preconditions

    Software ● STARTER with Version 4.4 or higher SSP for SINAMICS V4.7 ● SINAMICS S120 firmware version 4.7 or higher ● Memory card for CU320-2 with one of the options: – Booksize device: Licensing corresponding to the power rating and application –...
  • Page 69: Basic Commissioning

    Commissioning 7.3 Basic commissioning Basic commissioning When commissioning offline with the STARTER, you must select the infeeds on the basis of their article numbers. 7.3.1 Infeed units in the chassis format Table 7- 1 Article numbers for infeed units in the chassis format for grid voltages 3 AC 380 ... 480 V Active Line Module Grid voltage Rated power at 3 AC 400 V...
  • Page 70: Commissioning Example For An Infeed With Voltage And Frequency Control For An Island Grid

    Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Commissioning example for an infeed with voltage and frequency control for an island grid. 7.4.1 Design Generator plant In the example, the electrical power generated by a rotating generator is fed into an island grid.
  • Page 71: General Information

    (see Notes for commissioning systems for operation on grids with low short- circuit power (fault level) and variable grid parameters (Page 138)). Note Description of the commissioning process The basic steps when commissioning a SINAMICS S120 are contained in the Commissioning Manual. Note Access level Some of the parameters to be set are accessible only under access level 4 (Service).
  • Page 72: Function Modules For Creating A Line Infeed In An Island Grid

    Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. 7.4.3 Function modules for creating a line infeed in an island grid In the project, click on "INFEED" under "Infeeds" and then select "Properties...". ●...
  • Page 73: Adapting The Topology And The Vsm10 Assignments

    Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. 7.4.5 Adapting the topology and the VSM10 assignments Double-click on "Topology" in the project; the topology view appears. The topology looks like this after the above commissioning steps, for instance: Figure 7-2 Topology The numbers in brackets to the right of the components in the topology view are the...
  • Page 74: Performing Additional Parameter Settings In The Expert List

    Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. 7.4.6 Performing additional parameter settings in the expert list The following table provides an overview of the most important adjustable parameters with typical values and notes for an island grid application. This overview should provide help when commissioning the system.
  • Page 75 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Value Comment p1810.4 Inhibit wobbulation (sweep) amplitude (access level 4) Depending on the filter being used: For standard Active Interface Modules: Yes Using this bit, the wobbulation function is controlled for regular current-controlled operation (no grid droop operation).
  • Page 76 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Value Comment p5401[1] e.g. 1 BI: Grid droop control activation - static setpoint activation For p5401[1] = 1, droop characteristics p5405ff and p5415ff are active. For stable generator operation, the setting for the no-load points for voltage and frequency must match the actual operating point of the island grid (especially the load distri- bution between several power generating units).
  • Page 77 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Value Comment p5416[0] e.g. 0 Line droop control voltage droop supplementary setpoint In island grids with several power generating units, the no-load voltage is dynami- cally adapted to the instantaneous load and power generating conditions using a higher level island grid control.
  • Page 78 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Value Comment p5436 DC component controller P gain Especially if an island grid contains transformers or line motors, it is absolutely necessary that this control is activated to prevent DC components in the AC cur- rent.
  • Page 79 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Value Comment p5481[1] e.g. 0.7 s Transformer magnetization times: Circuit breaker bounce time If the time set is less than the actual bounce time, extremely high currents can occur when the pulses are enabled, which can damage the circuit breaker.
  • Page 80 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Value Comment p5494[0] e.g. 93 % Magnetizing scale values The adjustable parameter defines the percentage of the rated voltage for trans- former magnetization. In practice, the ideal value of 100 % is generally not re- quired.
  • Page 81 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Value Comment p5581[1] e.g. 1 s Island grid times, black start circuit breaker bounce time Sets the bounce time for the circuit breaker on the grid side of the grid transform- An interruption-free connection between the grid and transformer is only ensured after the bounce time has elapsed.
  • Page 82 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Table 7- 5 Parameter settings for the drive device "MOTORINVERTER" Parameter Value Comment p1200[0] e.g. 1 Flying restart operating mode in DDS 0 Flying restart always active, start in setpoint direction "Flying restart always active"...
  • Page 83: Signal Interfaces

    Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. 7.4.7 Signal interfaces Description The following signals are required by the drive unit for operation and/or provided for monitoring purposes. Signals transferred to the drive unit This involves a list of typical signals for communication with the higher-level control system.
  • Page 84 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Drive Object Signal Type Unit p5480 INFEED Transformer magnetization mode Integer, 16-bit 0 = deactivated 1 = normal operation Notice: When magnetization is deactivated, with the DC link precharged, the circuit breaker is controlled independent of the operating state of a trans- former that may be available.
  • Page 85 Commissioning 7.4 Commissioning example for an infeed with voltage and frequency control for an island grid. Parameter Drive Object Signal Type Unit r2139.3 INFEED Fault active 1 signal: Fault active 0 signal: Fault not active The 1 signal is set if a fault occurs in one or more drive objects r2139.7 INFEED...
  • Page 86: Commissioning Example Of An Infeed With Dynamic Grid Support For A Power Grid

    Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Commissioning example of an infeed with dynamic grid support for a power grid 7.5.1 Design Photovoltaic plant The example shows a photovoltaic plant feeding the electrical energy generated into a power grid.
  • Page 87 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Line fault Fault ride through in accordance with grid codes, occurs automatically via the grid inverter according to the required parameter settings. Block diagram Figure 7-3 Infeed to a power grid Table 7- 8 Components for infeed to a power grid...
  • Page 88: General Information

    (see Notes for commissioning systems for operation on grids with low short- circuit power (fault level) and variable grid parameters (Page 138)). Note Description of the commissioning process The basic steps when commissioning a SINAMICS S120 are contained in the Commissioning Manual. Note Access level Some of the parameters to be set are accessible only under access level 4 (Service).
  • Page 89: Function Modules For Creating A Line Infeed In A Power Grid

    Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid 7.5.3 Function modules for creating a line infeed in a power grid In the project, click on "INFEED" under "Infeeds" and then select "Properties...". ● Under the "Function modules" tab, select the "Grid transformer" and "Dynamic grid support"...
  • Page 90: Adapting The Topology And The Vsm10 Assignments

    Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid 7.5.5 Adapting the topology and the VSM10 assignments Double-click on "Topology" in the project; the topology view appears. The topology looks like this after the above commissioning steps, for instance: Figure 7-4 Topology The numbers in brackets to the right of the components in the topology view are the...
  • Page 91 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Parameter settings for "INFEED" drive unit In the project, right click on "INFEED" under "Infeeds" and then select "Expert list". Table 7- 9 Parameter settings for "INFEED" drive unit Parameter Value Comment...
  • Page 92 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Parameter Value Comment DC link control p3410 Infeed identification method – identification (ID) off p3415[0] 10,00 % Infeed excitation current L identification – run 1 Amplitude of the measured currents for identifying the DC link capacitance For grids with low fault level (short-circuit rating), we recommend reducing the measuring current to 10 % (possibly down to 7 %) in order to ensure stable grid...
  • Page 93 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Parameter Value Comment p5486[0] e.g. 10000 V Transformer rated voltage on the primary side, infeed transformer Enter the rated voltage at the connection point on the power grid side of the infeed transformer.
  • Page 94 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Parameter Value Comment p5501 e.g. 1 BI: Dynamic grid support activation Signal to activate the dynamic grid support. A difference to normal operation of the Active Line Module when using p5501 = 1 only becomes effective if the grid voltage lies outside the selected tolerance band p5505[0, 2]: In this particular case (r5502.1 = 1) an additional reactive power is injected into the grid, whose magnitude with p5506 depends...
  • Page 95 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Parameter Value Comment p5509[5] e.g. 85 % Dynamic grid support scaling values, current limiting scaling Important note: This limit for the Active Line Module apparent current becomes effective when dynamic grid support is activated (p5501 = 1) –...
  • Page 96: Additional Parameter Settings For Grid Monitoring

    Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid 7.5.7 Additional parameter settings for grid monitoring The grid monitoring comprises three components, which can be set using configuration parameter p5540: 1. Monitoring of the grid voltage and frequency (activated using p5540.0). Initiation of fault message F6851 when limits p5543 and p5544 are exceeded.
  • Page 97 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Parameter settings for grid monitoring In the project, right click on "INFEED" under "Infeeds" and then select "Expert list". Table 7- 10 Parameter settings for "INFEED" drive unit Parameter Value Comment...
  • Page 98 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid As an alternative to the grid monitoring with threshold values for voltage and frequency (p5543, p5544) as mentioned above, flexibly adaptable grid protection can be implemented using characteristics, as shown in the subsequent table.
  • Page 99 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Parameter Value Comment p5555[0] e.g. 0.5 Hz Sets the activation frequency thresholds for HFRT (high frequency ride through) of a grid fault for FRT (fault ride through) grid monitoring. The setting is made as difference to the rated frequency p0211 p5555[1] e.g.
  • Page 100: Signal Interfaces

    Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid 7.5.8 Signal interfaces Description The following signals are required by the drive unit for operation and/or provided for monitoring purposes. Signals transferred to the drive unit This involves a list of typical signals for communication with the higher-level control system.
  • Page 101 Commissioning 7.5 Commissioning example of an infeed with dynamic grid support for a power grid Signals transferred from the drive unit This involves a list of typical signals for communication with the higher-level control system. Table 7- 13 Signals transferred from the drive unit Parameter Drive Object Signal...
  • Page 102: Commissioning The Grid Transformer

    Commissioning 7.6 Commissioning the grid transformer Commissioning the grid transformer 7.6.1 Commissioning grid-friendly transformer magnetization DRIVE-CLiQ topology The following DRIVE-CLiQ topology must be used so that auto-commissioning will work. If a different DRIVE-CLiQ topology is selected, the user must assign all the VSM10s manually in the offline configuration using the STARTER tool.
  • Page 103 Commissioning 7.6 Commissioning the grid transformer pulse inhibit for the ALM). After the debounce time has elapsed, then controlled ALM operation is automatically assumed. Note If, already in the synchronous state, the application requires a long wait time for the circuit breaker to close, then the feedback signal of the switch can be used for the enable p5483.
  • Page 104 Commissioning 7.6 Commissioning the grid transformer The characteristic number (0; 5 etc.) in the vector diagram specifies by which multiple of 30° the vector of the secondary voltage lags with respect to the primary voltage with the associated connection designation. The direction of rotation of the vector is counterclockwise.
  • Page 105 Commissioning 7.6 Commissioning the grid transformer 4. DC link capacitance and grid inductance: Parameter p5580 (island grid black start mode) must be set to p5580 = 0. Switching on the Active Line Modules with p3410 = 5 executes an identification of the line inductance and DC link capacitance.
  • Page 106 Commissioning 7.6 Commissioning the grid transformer Operation on weak grids A "weak grid" is involved if the system fault level (RSC = relative short circuit power) at the connection point is less than 10. For instance, this is frequently the case if the rating of the feeding grid transformer is less than the connection value of the Active Line Module.
  • Page 107 Commissioning 7.6 Commissioning the grid transformer Island grid with special topologies Grid without circuit breaker If, in an individual case, the circuit breaker between the Active Line Module/Active Interface module and grid can be eliminated, or if the circuit breaker is not controlled from the SINAMICS system, and it can be guaranteed that the voltage is the same at both sides of the switch using the appropriate external systems, then island grid operation can also be implemented without having to use a 2nd VSM.
  • Page 108: Overview Of Important Parameters

    Commissioning 7.6 Commissioning the grid transformer 7.6.2 Overview of important parameters Grid-friendly transformer magnetization ● p5480 Transformer magnetization mode ● p5481[0...2] Transf magnetization times ● r5482 Line synchronization state ● p5483 BI: Line circuit breaker enable ● p5484[0...2] Transf magnetization controller dynamic performance ●...
  • Page 109 Commissioning 7.6 Commissioning the grid transformer ● r6316 CO: Grid PLL2 line phase angle measured ● p6420[0...1] Phase shift input voltage VSM to converter ● p6421[0...1] Line supply voltage sensing gain adaptation ● p6422 Line supply voltage rotating field direction ●...
  • Page 110: Function Block Diagrams

    Commissioning 7.6 Commissioning the grid transformer Others ● p5406[0...1] CI: Line droop control frequency droop supplementary setpoint ● p5416[0...1] CI: Line droop control voltage droop supplementary setpoint 7.6.3 Function block diagrams ● 7987 Negative sequence system controller ● 7988 Island grid black start sequence control ●...
  • Page 111: Commissioning The Grid Droop Control

    Commissioning 7.7 Commissioning the grid droop control Commissioning the grid droop control For commissioning the grid droop control, reference is made to Chapter Commissioning example for an infeed with voltage and frequency control for an island grid. (Page 70) and the general function chapter (Function module for grid droop control (Page 35)).
  • Page 112 Commissioning 7.7 Commissioning the grid droop control 9. r5482 = 108: Black start complete grid check It is checked as to whether voltage and frequency of the island grid lie within the permissible tolerance limits (p0282 < r0072[2] < p0281 and p0285 < r0066[1] < p0284). 10.r5482 = 109: Black start completed Settings The island grid black start is configured using p5580.
  • Page 113 Commissioning 7.7 Commissioning the grid droop control ● Corresponding to function diagram FP7990, different measuring tasks are uniquely assigned to the various VSM10 devices; it is not permissible to change this assignment. For an assignment of the various VSM10, see the diagram in the subsequent chapter, the assignment of the VSM10 to the numbers in the diagram are as follows: ③...
  • Page 114: Synchronizing An Island Grid To An External Power Grid

    Commissioning 7.7 Commissioning the grid droop control 7.7.2 Synchronizing an island grid to an external power grid Configuration Figure 7-7 Configuration for the infeed in an island grid with coupling to the power grid – example, chassis format devices Table 7- 14 Components for the infeed in an island grid with coupling to the power grid Number Description...
  • Page 115 Commissioning 7.7 Commissioning the grid droop control Synchronization sequence 1. r5482 = 1: Wait The start is realized using a 1 signal at binector input p5583[0]. The grid control must be active (r5402.1 = 1). The infeed must be switched-on (the pulses must be enabled). It is not permissible that the circuit breaker is closed, as the feedback signal is realized using binector input p5583[1].
  • Page 116 Commissioning 7.7 Commissioning the grid droop control Additional parameter settings for synchronizing an island grid to an external grid The following table provides an overview of the most important adjustable parameters with typical values and notes for an application involving synchronizing an island grid to an external grid.
  • Page 117 Commissioning 7.7 Commissioning the grid droop control Parameter Value Comment CI: Transformer primary voltage signal source - island grid transformer u23 p5487[3] e.g. INFEED.r5462[1] Signal source for the measured conductor-conductor voltage at the grid discon- nector (9) for internal conversion to the connection point of the Active Line Module.
  • Page 118 Commissioning 7.7 Commissioning the grid droop control Damping grid oscillations A good damping is achieved, for example with the setting p5413 = 50 % x p5407 and p5414 = 10 % x p5409. Damping can be additionally or alternatively increased using DT1 filter p5476. Notes ●...
  • Page 119 Commissioning 7.7 Commissioning the grid droop control ● Frequently, the correct parameterization of the phase shift (p6420[0, 1]) results in problems. A check without additional measuring equipment is only possible if the circuit breaker to the island grid or to the external grid is closed. For instance, the first case can be created using a black start.
  • Page 120: Overview Of Important Parameters

    Commissioning 7.7 Commissioning the grid droop control 7.7.3 Overview of important parameters Grid control ● r0206[0...4] Rated power unit power ● r0207[0...4] Rated power unit current ● p0210 Device supply voltage ● P0211 Rated grid frequency ● p1300[0...n] Open-loop/closed-loop control operating mode Grid droop control ●...
  • Page 121 Commissioning 7.7 Commissioning the grid droop control ● p5427 Line droop control voltage control integration time ● p5428[0...3] Line droop control voltage control short circuit ● r5429 Line droop control voltage control output Black start synchronization ● p5580 Island grid black start mode ●...
  • Page 122: Function Block Diagrams

    Commissioning 7.7 Commissioning the grid droop control Harmonics controller ● p5440 Harmonics controller bandpass filter activation ● p5441[0...3] Harmonics controller bandpass filter gain ● p5442[0...3] Harmonics controller bandpass filter mid-frequency ● p5443 Harmonics controller bandpass filter gain total Current hysteresis controller ●...
  • Page 123: Commissioning Of Dynamic Grid Support

    Commissioning 7.8 Commissioning of dynamic grid support Commissioning of dynamic grid support For commissioning the dynamic grid support, reference is made to Chapter Commissioning example of an infeed with dynamic grid support for a power grid (Page 86) and the general function chapter (Function module, dynamic grid support (Page 40)).
  • Page 124 Commissioning 7.8 Commissioning of dynamic grid support Example for monitoring the voltage dip In the following example, the parameterization of a monitoring characteristic is shown for the voltage according to the following diagram. The individual characteristic required depends on the country-specific grid codes and the specifications of the individual power utility company: ●...
  • Page 125: Commissioning The Frequency-Time Monitoring

    Commissioning 7.8 Commissioning of dynamic grid support Notes ● The times in p5553[x] must be entered in ascending order. For example, for simply parameterizing steps, the same consecutive times are permissible. ● The time in p5553[9] defines the maximum duration of a fault ride through and must therefore always be defined.
  • Page 126 Commissioning 7.8 Commissioning of dynamic grid support Example for frequency-time monitoring In the following example, the parameterization of a monitoring characteristic is shown for the grid frequency according to the following diagram. The individual characteristics required depend on the country-specific grid codes and the specifications of the individual power utility company: ●...
  • Page 127: Commissioning Additional Monitoring Functions

    Commissioning 7.8 Commissioning of dynamic grid support Times in s Frequency values in Hz Low frequency (LFRT) p5558[0] = 0.00 p5559[0] = -1.6 p5558[1] = 0.20 p5559[1] = -1.6 p5558[2] = 0.20 p5559[2] = -1.1 p5558[3] = 0.70 p5559[3] = -1.1 p5558[4] = 0.70 p5559[4] = -0.6 p5558[5] = 1.50...
  • Page 128: Overview Of Important Parameters

    Commissioning 7.8 Commissioning of dynamic grid support 7.8.5 Overview of important parameters Parameters for dynamic grid support ● p5500 Dynamic grid support configuration ● p5501 BI: Dynamic grid support activation ● r5502.0...4 CO/BO: Dynamic grid support status word ● p5503[0...1] CI: Dynamic grid support current signal source ●...
  • Page 129: Function Block Diagrams

    Commissioning 7.8 Commissioning of dynamic grid support Parameters for grid monitoring anti-islanding function ● p5540 Line monitoring configuration ● p5541 BI: Line monitoring activation ● r5542.0...14 CO/BO: Line monitoring status word ● p5543[0...3] Line monitoring voltage threshold ● p5544[0...3] Line monitoring frequency threshold ●...
  • Page 130: Commissioning Cos Phi Display

    Commissioning 7.9 Commissioning cos phi display Commissioning cos phi display Preconditions ● For the cosφ calculation function, when commissioning, the Active Line Module function module "Supplementary module cosinus phi" must be activated. This means that additional parameters p3473 to p3479 are available. If a second VSM10 is to be used to display cosφ, then the grid transformer function module should also be activated.
  • Page 131 Commissioning 7.9 Commissioning cos phi display ● Corresponding to the selected configuration, the signal sources for the current and voltage actual values must be parameterized for the cosφ measuring point in p3473 and p3474. ● The measured value is displayed as amount (r3478) and sign (r3477). Especially for r3478 = 1, even minimum phase shifts of the currents cause the sign to change.
  • Page 132: Commissioning Supplementary Controls

    Commissioning 7.10 Commissioning supplementary controls Overview of important parameters ● p3473[0...3] CI: cos phi signal source current indication ● p3474[0...3] CI: cos phi signal source voltage indication ● p3475[0...1] cos phi display configuration ● p3476[0...1] cos phi display smoothing time ●...
  • Page 133: Active Current Limiting

    Commissioning 7.10 Commissioning supplementary controls 7.10.2 Active current limiting The limits for the active current can be set to different values for the two energy flow directions "motoring" and "generating". If the motoring current limit is reached, then less active current is injected into the DC link than is specified by the active current setpoint.
  • Page 134: Current Limiting For Dynamic Grid Support

    Commissioning 7.10 Commissioning supplementary controls 7.10.4 Current limiting for dynamic grid support Depending on the grid codes of the power utility company, special requirements apply to power generating systems regarding the current characteristic during a grid fault. Generally, a certain participation in the short-circuit current is specified, i.e. impressing a defined reactive current during a grid fault.
  • Page 135 Commissioning 7.10 Commissioning supplementary controls ● The priority for providing reactive power for dynamic grid support can be briefly automatically deactivated if the DC link voltage comes close to the upper shutdown limit. In order to avoid a protective shutdown, the reactive current is reduced via p5508 – and the full active power is available to reduce the DC link voltage down to zero.
  • Page 136: Apparent Current Limiting For Grid Droop Control

    (p5509[7] = p5509[8] = p5509[11] = 0). Using these pre-settings, a grid fault is ridden through in an almost no-current condition. The local Siemens office can be contacted regarding any deviation from the presettings. Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 137: Overview Of Important Parameters

    Commissioning 7.10 Commissioning supplementary controls 7.10.7 Overview of important parameters Parameters for the Vdc actual value filter 5 ● p1656 Signal filter activation ● p1677 Vdc actual value filter 5 type ● p1678 Vdc actual value filter 5 denominator natural frequency ●...
  • Page 138: Notes For Commissioning Systems For Operation On Grids With Low Short-Circuit Power (Fault Level) And Variable Grid Parameters

    Commissioning 7.11 Notes for commissioning systems for operation on grids with low short-circuit power (fault level) and variable grid parameters 7.11 Notes for commissioning systems for operation on grids with low short-circuit power (fault level) and variable grid parameters Especially in island grids, test grids or when connecting to long grid cables, frequently – in comparison to the Active Line Module rated power –...
  • Page 139: Device Overview

    A description for the CU320-2 PN and CU320-2 DP Control Units is provided in Control Units and Additional System Components Manual (http://support.automation.siemens.com/WW/view/en/99679173). Voltage Sensing Module VSM10 You can find a description of the VSM10 Voltage Sensing Module in the Control Units and Additional System Components Manual (http://support.automation.siemens.com/WW/view/en/99679173).
  • Page 140: Chassis Format

    The temperature signaling contact must also be connected to the Active Line Module. You can find a description of the air-cooled Active Interface Modules in the Booksize power units manual (http://support.automation.siemens.com/WW/view/en/99687925). 8.3.2 Chassis format Active Interface Modules are used in conjunction with the Active Line Modules in chassis format.
  • Page 141 Device overview 8.3 Active Interface Modules, air-cooled Note The general data in the SINAMICS Low Voltage Engineering Manual should be carefully observed. Especially for island grids and weak grids, a grid analysis should be performed with the following content: • Analysis of the complete drive system, including diesel engines, with statements regarding the total harmonic distortion factor (T ) –...
  • Page 142: Air-Cooled Active Line Modules For The Grid Infeed, Chassis Format

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.1 Description The self-commutating infeed / regenerative feedback units act as step-up converters and generate a stabilized DC link voltage that is 1.5x greater than the rated line supply voltage. In this way, the connected Motor Modules are isolated from the line voltage.
  • Page 143 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Active Infeed components An Active Infeed comprises an Active Interface Module and an Active Line Module. The bypass contactor is fitted in the relevant Active Interface Module on Active Infeeds which feature an Active Line Module of frame size GX.
  • Page 144 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Parallel connection of Active Line Modules to increase power rating To increase the power and for redundancy, it is possible to connect up to four Active Line Modules each with the same output rating and type in parallel.
  • Page 145: Safety Information

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.2 Safety information WARNING Danger to life if the fundamental safety instructions and remaining risks are not carefully observed If the fundamental safety instructions and remaining risks in Chapter 1 are not observed, accidents involving severe injuries or death may occur.
  • Page 146 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format WARNING Danger to life due to high leakage currents caused by an interrupted external protective conductor The drive components conduct a high leakage current via the protective conductor. Touching conductive parts when the protective conductor is interrupted can result in death or serious injury.
  • Page 147 Damage or malfunctions can occur on the devices or system when DRIVE-CLiQ cables are used that are either incorrect or have not been approved for this purpose. • Only use suitable DRIVE-CLiQ cables that have been approved by Siemens for the particular application.
  • Page 148: Interface Description

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.3 Interface description 8.4.3.1 Overview Figure 8-3 Active Line Module, frame size GX Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 149 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Figure 8-4 Active Line Module, frame size JX Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 150: Connection Example

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.3.2 Connection example Figure 8-5 Active Line Module connection diagram Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 151: Line/Load Connection

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.3.3 Line/load connection Table 8- 2 Line/load connection of the Active Line Module Terminals Technical data U1, V1, W1 Voltage: 3 AC power input 3 AC 320 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 % •...
  • Page 152: X9 Terminal Strip

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.3.4 X9 terminal strip Table 8- 3 Terminal strip X9 Terminal Signal name Technical data P24V Voltage: 24 V DC (20.4 ... 28.8 V) Current consumption: max. 1.7 A Bypass contactor control for Active Interface Module, X609:11 for Active Interface Module, X609:12...
  • Page 153 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format WARNING Risk of death from electric shock in the event of voltage flashovers at the temperature sensor Voltage flashovers in the signal electronics can occur in motors without safe electrical separation of the temperature sensors.
  • Page 154: X42 Terminal Strip

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.3.6 X42 terminal strip Table 8- 5 Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module Terminal Function Technical data P24L Voltage supply for Control Unit, Sensor Module, and Terminal Module (18 to 28.8 V) Maximum load current: 3 A Max.
  • Page 155: Significance Of The Leds On The Control Interface Module In The Active Line Module

    Flashing There is a fault. If the LED continues to flash after you have performed a light POWER ON, please contact your Siemens service center. WARNING Risk of death when live parts of the DC link are touched Irrespective of the state of the LED "DC LINK", hazardous DC link voltages can always be present.
  • Page 156: Dimension Drawing

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.4 Dimension drawing Dimension drawing, frame size GX The minimum clearances for cooling are indicated by the dotted line. Figure 8-6 Dimension drawing Active Line Module, frame size GX Front view, side view Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 157 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Dimension drawing, frame size JX The minimum clearances for cooling are indicated by the dotted line. Figure 8-7 Dimension drawing Active Line Module, frame size JX Side view, rear view Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 158: Electrical Connection

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.5 Electrical connection Adjusting the fan voltage (-T10) The power supply for the device fans (1 AC 230 V) in the Active Line Module (-T10) is taken from the line supply using transformers.
  • Page 159 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format WARNING Risk of fire due to overheating when the device fan voltage is insufficient If the terminals are not reconnected to the actual line voltage, this can lead to overheating with a risk of personal injury due to smoke and fire.
  • Page 160: Technical Data

    Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format 8.4.6 Technical data Table 8- 11 Technical data for Active Line Modules, 3 AC 320 ... 480 V with supplements for operation with 3 AC 320 V for photovoltaic applications Article number 6SL3330–...
  • Page 161 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Article number 6SL3330– 7TE35– 7TE41– 7TE41– 0AA4 0AA4 4AA4 Sound pressure level (1 m) at 50/60 Hz dB(A) 69 / 73 71 / 73 71 / 73 Line/load connection Flat connector for screw Max.
  • Page 162 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Table 8- 12 Technical data for Active Line Modules, 3 AC 500 V ... 690 V Article number 6SL3330– 7TG41– 7TG41– 0AA4 3AA4 Rated power - For I (50 Hz, 690 V) 1100 1400...
  • Page 163 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Article number 6SL3330– 7TG41– 7TG41– 0AA4 3AA4 Max. cable length (total of all motor cables and DC link) - Shielded 2250 2250 - Unshielded 3375 3375 Degree of protection IP00 IP00 Dimensions...
  • Page 164 Device overview 8.4 Air-cooled Active Line Modules for the grid infeed, chassis format Overload capability The Active Line Modules have an overload reserve. The criterion for overload is that the drive is operated with its base load current before and after the overload occurs (a load duration of 300 s is used as a basis here).
  • Page 165: Permissible Range For The Step-Up Factor

    When using the Active Line Module, the power must be derated depending on the ambient temperature, installation altitude and the cosφ. Also refer to the Low Voltage Engineering Manual: LV Engineering Manual (http://support.automation.siemens.com/WW/view/en/83180185) An application description is available to determine the available reactive power: Application description reactive power compensation (http://support.automation.siemens.com/WW/view/en/105643094)
  • Page 166: Active Interface Modules, Liquid-Cooled

    ● Associated connection elements (pressure hose, cable, hose connections) You can find descriptions for the liquid-cooled Active Interface Modules in the Chassis power units manual liquid cooled (http://support.automation.siemens.com/WW/view/en/92544333). Note The general data in the SINAMICS Low Voltage Engineering Manual should be carefully observed.
  • Page 167: Liquid-Cooled Active Line Modules For The Grid Infeed, Chassis Format

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.1 Description The self-commutating infeed / regenerative feedback units act as step-up converters and generate a stabilized DC link voltage that is 1.5x greater (factory setting) than the rated line supply voltage.
  • Page 168 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Active Infeed components An Active Infeed comprises an Active Interface Module and an Active Line Module. In the case of an Active Infeed with an Active Line Module of frame sizes HXL or JXL, the bypass contactor is not included in the associated Active Interface Module, but must be provided separately.
  • Page 169: Safety Information

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.2 Safety information WARNING Danger to life if the fundamental safety instructions and remaining risks are not carefully observed If the fundamental safety instructions and remaining risks in Chapter 1 are not observed, accidents involving severe injuries or death may occur.
  • Page 170 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format WARNING Danger to life due to high leakage currents caused by an interrupted external protective conductor The drive components conduct a high leakage current via the protective conductor. Touching conductive parts when the protective conductor is interrupted can result in death or serious injury.
  • Page 171 Damage or malfunctions can occur on the devices or system when DRIVE-CLiQ cables are used that are either incorrect or have not been approved for this purpose. • Only use suitable DRIVE-CLiQ cables that have been approved by Siemens for the particular application.
  • Page 172: Interface Description

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.3 Interface description 8.6.3.1 Overview Figure 8-11 Active Line Module, frame size HXL Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 173 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Figure 8-12 Active Line Module, frame size JXL Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 174: Connection Example

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.3.2 Connection example Figure 8-13 Example connection of Active Line Module Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 175: Line/Load Connection

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.3.3 Line/load connection Table 8- 15 Line/load connection of the Active Line Module Terminals Technical data U1, V1, W1 Voltage: 3 AC power input 3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 % •...
  • Page 176: X41 Ep Terminal / Temperature Sensor Connection

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Note Looping through the supply voltage The two "P24 V" or "M" terminals are jumpered in the connector. This ensures that the supply voltage is looped through, even when the connector is removed. 8.6.3.5 X41 EP terminal / temperature sensor connection Table 8- 17...
  • Page 177: X42 Terminal Strip

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format NOTICE Risk of motor overheating for incorrectly connected KTY temperature sensor A KTY temperature sensor connected with incorrect polarity cannot detect if the motor overheats. • Make sure that you connect the KTY temperature sensor with the correct polarity. Note The temperature sensor connection can be used for motors that are equipped with a KTY84- 1C130 or PTC probe in the stator windings.
  • Page 178: Drive-Cliq Interfaces X400, X401, X402

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.3.7 DRIVE-CLiQ interfaces X400, X401, X402 Table 8- 19 DRIVE-CLiQ interfaces X400, X401, X402 Signal name Technical data Transmit data + Transmit data - Receive data + Reserved, do not use Reserved, do not use Receive data -...
  • Page 179: Meaning Of The Leds On The Control Interface Module In The Active Line Module

    Flashing There is a fault. If the LED continues to flash after you have performed a light POWER ON, please contact your Siemens service center. WARNING Danger of death when live parts of the DC link are touched Irrespective of the state of the "DC LINK" LED, hazardous DC-link voltages can always be present.
  • Page 180: Dimension Drawing

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.4 Dimension drawing Dimension drawing for frame size JXL The mandatory cooling clearances are indicated by the dotted line. Figure 8-14 Dimension drawing Active Line Module, frame size HXL Front view, side view Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 181 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Figure 8-15 Dimension drawing Active Line Module, frame size JXL, article number 6SL3335-7TG41- 3AA4. Front view, side view Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 182 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Figure 8-16 Dimension drawing Active Line Module, frame size JXL, article number 6SL3335-7TG41- 6AA4. Front view, side view Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 183: Installation

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.5 Installation Figure 8-17 Crane lifting lugs / screw coupling points for mechanical support Crane lifting lugs Active Line Modules are fitted with crane lifting lugs as standard when shipped. The units can be hoisted using these lugs and transported from the pallet to the installation location.
  • Page 184 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format NOTICE Damage to the device due to improper transport Improper transport can cause mechanical loads on the housing or busbars which can result in damage to the device. •...
  • Page 185 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Figure 8-18 Protection guard Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 186: Technical Specifications

    Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format 8.6.6 Technical specifications Table 8- 23 Technical data for Active Line Modules, 3 AC 500 V ... 690 V Article number 6SL3335– 7TG35–8AA4 7TG41–3AA4 7TG41-6AA4 Rated power - At I (50Hz 690V) 1400...
  • Page 187 This value applies to the water coolant option; for other coolant types, see Chapter "Cooling circuit and coolant proper- ties" in the SINAMICS S120 Power Units Chassis Liquid Cooled Manual. To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
  • Page 188 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Overload capability The Active Line Modules have an overload reserve. The criterion for overload is that the drive is operated with its base load current before and after the overload occurs (a load duration of 300 s is used as a basis here).
  • Page 189: Permissible Range For The Step-Up Factor

    When using liquid-cooled Active Line Module, the power must be derated depending on the coolant temperature, the ambient temperature, installation altitude and the cosφ. Also refer to the Low Voltage Engineering Manual: LV Engineering Manual (http://support.automation.siemens.com/WW/view/en/83180185) An application description is available to determine the available reactive power: Application description reactive power compensation (http://support.automation.siemens.com/WW/view/en/105643094)
  • Page 190 Device overview 8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 191: Function Diagrams

    An overview of the function charts for the grid infeed is shown in the following. They are arranged in the schematic according to the function modules described above. The function diagrams for the corresponding firmware versions are included in the "SINAMICS S120/S150 List Manual". Table 9- 1 Line transformer Function diagram No.
  • Page 192 Function diagrams Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 193: A Appendix

    Appendix Glossary List of the abbreviations used in the document AISL Anti-islanding Fault ride through Circuit breaker HFRT High frequency ride through HVRT High voltage ride through LFRT Low frequency ride through LVRT Low voltage ride through Maximum power point Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 194: Cable Lugs

    Appendix A.2 Cable lugs Cable lugs Chassis format devices The cable connections on the devices are designed for cable lugs according to DIN 46234 or DIN 46235. For connection of alternative cable lugs, the maximum dimensions are listed in the table below.
  • Page 195 Appendix A.2 Cable lugs Booksize format devices The directives when using cable lugs are provided in Booksize power units manual (http://support.automation.siemens.com/WW/view/en/99687925). Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 196 Appendix A.2 Cable lugs Grid infeed System Manual, 04/2015, A5E03347436A...
  • Page 197: Index

    Index Active Interface Module, 139 Grid control, 36 Active Interface Modules Grid infeed applications, 33 Liquid-cooled, 166 Grid monitoring anti-islanding, 43 Active Interface Modules, air-cooled, 140 Grid-friendly transformer magnetization, 34, 102 Active Line Modules, 142, 167 Dimension drawing, 156, 180 Step-up factor, 165, 189 Identification of the transformer data, 35 Installation...
  • Page 198 Index Power grid, 21 Protection guard, 184 Residual risks of drive systems, 17 Safety instructions Active Line Modules, 145, 169 Electromagnetic fields, 14 Electrostatic sensitive devices, 15 General safety instructions, 11 Step-up factor, 165, 189 Technical data Active Line Modules, 160, 186 Transformer magnetization, 34 VSM topology, 102 Grid infeed...

Table of Contents