Siemens HS-MC Series Installation Instructions

Siemens HS-MC Series Installation Instructions

Multi-candela four wire horn strobe appliances wall mount version

Quick Links

IMPORTANT – All audible and visual signaling appliances must be
installed in accordance with all applicable national and local fire alarm
codes and any other required regulatory agencies.
Series HS-MC Multi-Candela Horn Strobe provides four selectable
candela settings (15, 30, 75, 110). The HS-MC allows for independent
operation of the strobe circuit and the horn circuit. It is the ideal choice
for retrofit applications as well as new installations.
appliance is UL Listed under Standard 1971 for Signaling Appliances
for the Hearing Impaired and UL Standard 464 for Audible Signal
Appliances. The HS-MC is also ULC Listed under Standard CAN/ULC-
S526-02 for Visual Signaling Appliances and Standard CAN/ULC-
S525-99 for Audible Signaling Appliances for Fire Alarm Systems. It is
listed for indoor use only and can be mounted to double-gang, 4"
backbox, 100mm European backbox or MT-SUR-BOX surface
backbox (See wiring and mounting information).
listed for wall mounting only. The HS-MC appliance uses a xenon
flashtube with solid state circuitry enclosed in a polycarbonate lens to
provide maximum visibility and reliability for effective visible signaling.
Siemens Series HS appliances provide a selectable continuous or
Code 3 horn tone and non-synchronized strobe when connected
directly to a Fire Alarm Control Panel (FACP). They can also provide a
synchronized Code 3 (or March Time) horn tone and synchronized
strobe when connected to a notification appliance circuit running the
Siemens sync protocol. HS appliances can be field set for High (HI),
medium (MED) dBA or low (LO) dBA sound output. .
SPECIFICATIONS:
Model*
HS-MC
Description
Low
Continuous Horn
Medium
High
Low
Code 3 Horn or
Medium
March Time**
High
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
INSTALLATION INSTRUCTIONS
MULTI-CANDELA FOUR WIRE HORN STROBE APPLIANCES
The HS-MC
This appliance is
Table 1: UL/ULC Listed Models and Ratings
Operating Voltage (Special Application)
Per UL 1971
(VDC/VRMS)
16.0-33.0
Table 2: dBA Sound Output for 24VDC Models
Reverberant Per UL 464
Volume
16.0VDC
80
85
88
75
80
84
**Available in sync mode only.
(WALL MOUNT VERSION)
NOTE: The Code 3 temporal pattern (1/2 second on, 1/2 second off,
1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is
specified by ANSI and NFPA 72 for standard emergency evacuation
signaling.
evacuation signaling and not for any other purpose.
The HS-MC is designed for use with either filtered DC or unfiltered full-
wave-rectified (FWR) input voltage.
compatibility with standard reverse polarity supervision of circuit wiring
by an FACP.
NOTE: All Canadian Installations should be in accordance with the
Canadian Standard for the Installation of Fire Alarm Systems –
CAN/ULC-S524-01 and Canadian Electrical Code, Part 1.
acceptance is subject to authorities having jurisdiction (AHJ).
NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation
Guidelines in using fewer, higher intensity strobes within the same
protected area.
NOTE: Refer to P/N 315-096363 for the maximum number of
appliances on a single notification appliance circuit.
Voltage Range Per
CAN/ULC-S526-02
(VDC/VRMS)
*Available in red and white.
24VDC
33.0VDC
83
86
88
91
91
93
79
82
84
86
87
89
The Code 3 Horn should be used only for fire
All inputs are polarized for
Strobe
Candela
(cd)
20.0-31.0
15/30/75/110
Anechoic dBA @ 10 Ft. Per CAN/ULC-S525-99
20.0VDC
24VDC
88
90
93
95
97
99
88
90
93
95
97
99
Final
31.0VDC
91
97
100
91
97
100
P84391-003B
Sheet 1 of 4
loading

Summary of Contents for Siemens HS-MC Series

  • Page 1 Code 3 (or March Time) horn tone and synchronized strobe when connected to a notification appliance circuit running the Siemens sync protocol. HS appliances can be field set for High (HI), medium (MED) dBA or low (LO) dBA sound output. .
  • Page 2 HS-MC Appliances. Be sure to add the currents for any other appliances powered by the same source and to include any required safety factors. Note: These notification appliances are UL Listed as “Special Application”. They are intended to be used only with Siemens notification appliance circuits.
  • Page 3 Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. Siemens Building Technologies, Inc. P84391-003B Sheet 3 of 4...
  • Page 4 RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE Hz AT THE OPERATING VOLTAGE OF THE STROBES. SIEMENS ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS, CODES AND GUIDELINES.