Emerson FB2200 Flow Computer
Quick Start Guide
Remote Automation Solutions
Table of Contents
loading

Summary of Contents for Emerson FB2200

  • Page 1 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Emerson FB2200 Flow Computer Quick Start Guide Remote Automation Solutions...
  • Page 2: Device Safety Considerations

    Our full-time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or email us at [email protected].
  • Page 3: Safety First

    Performing this operation in a hazardous area could result in an explosion. Important Use only batteries supplied with the flow computer or sold by Emerson as spare parts for this ▪ flow computer. If you substitute a battery you obtain elsewhere you will void your certification unless it is the identical part from the same manufacturer as that supplied with the flow computer from Emerson.
  • Page 4: Required Tools

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Required Tools Certain tools and equipment are required for installing and servicing the flow computer. Table 1: Required Tools Tool Torque wrench For bolting/mounting the flow computer 2.5 mm Hexagonal wrench...
  • Page 5: Opening/Closing The Enclosure

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Opening/Closing the Enclosure The enclosure opens/closes differently, depending upon whether you have the compression- molded fiberglass enclosure or the aluminum enclosure. DANGER EXPLOSION HAZARD: Never remove covers(s) in a hazardous location. Removing cover(s) in a hazardous location could result in an explosion.
  • Page 6: Bolting Considerations

    Only use bolts supplied with the flow computer or sold by Emerson as spare parts. Refer to the figure below for common flow computer assemblies with the bolt length required for proper flow computer installation.
  • Page 7 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Carbon steel bolts do not require lubrication. Stainless steel bolts are factory-coated with a lubricant to ease installation. Do not apply any additional lubricant when installing either type of bolt.
  • Page 8: Pole Mounting - Aluminum Enclosure

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Pole Mounting – Aluminum Enclosure DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion.
  • Page 9: Pole Mounting -Fiberglass Enclosure

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Pole Mounting –Fiberglass Enclosure DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion.
  • Page 10 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Grounding DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion. The flow computer includes a ground stud on the bottom of the battery box enclosure.
  • Page 11: Wiring Communications

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Wiring Communications DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion. Notes You do not need to add termination resistors; you can configure termination through ◼...
  • Page 12 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 RS-422 port on other device RS-485 port on other device...
  • Page 13 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 COM2, COM3 RS-232 port on other device RS-485 port on other device...
  • Page 14 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Ethernet The Ethernet port is a standard 8-pin 10/100Base-T RJ-45 modular connector located on the bottom right side of the CPU enclosure. Ethernet Port Notes The default IP address for the port is 192.168.1.10.
  • Page 15 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Wiring I/O DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion. Notes You should terminate all shields at chassis ground.
  • Page 16 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Optional Expansion I/O Board Wiring Field Device Power Supply 30Vdc Max 500 mA load max Open Drain Type or Open Collector Device (Externally Powered) Dry contact Low Side Switch High Side Switch...
  • Page 17 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 RTD Wiring Note The default configuration is 4-wire RTD; you can change the configuration in FBxConnect.
  • Page 18 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019...
  • Page 19: Wiring Power

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Wiring Power DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion. The flow computer accepts DC power with an input voltage range from 10.5 to 30V. The amount of power required depends on installed options.
  • Page 20 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Solar Power (Internal Regulator) For the solar panel option using a solar regulator built into the flow computer enclosure, connect the pre-wired cable to the solar panel. Solar Panel Conduit Fast acting 6.3A one time fuse...
  • Page 21 If you are using your own external solar regulator/30W solar panel not purchased through Emerson, you can use this section as an example of a typical installation. You should also consult the manufacturer’s instructions for your solar panel/solar regulator.
  • Page 22 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Remove the junction box cover. Use a utility knife to remove the knock-outs (Item 2) in the junction box (Item 1) and feed the wires from the solar regulator into the junction box, and through the solar regulator lock nut (Item 3).
  • Page 23 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Battery Wires from the Flow Computer to 30W Solar Panel Battery wires from the flow computer...
  • Page 24 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Connect the wires as shown. Replace the junction box cover. Connections from Flow Computer Battery to 30W Solar Panel Fast acting 6.3A one time fuse Conduit Battery Replace the junction box cover.
  • Page 25: Installing The Main Battery Pack

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Installing the Main Battery Pack DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion.
  • Page 26 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Open the enclosure. Captive fastening screws...
  • Page 27 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Loosen the two captive fastening screws at the top of the battery compartment and carefully rotate the electronics assembly towards you to reveal the inside of the battery compartment. A strap prevents the front of the compartment from rotating too far forward.
  • Page 28 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 The battery cable inside the battery compartment is divided into two branches, each with its own pair of connectors. Take either pair of connectors and connect them to the battery; the red (positive) wire connector attaches to the red connection point on the battery and the black (negative) wire connector attaches to the black connection point on the battery.
  • Page 29 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Secure the battery in the battery compartment so that it does not move around. How you do this depends on the battery compartment configuration. If the battery compartment includes a strap for holding the battery, see Securing the Battery with a Strap;...
  • Page 30 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Battery Strap Pick up the battery and carefully ease it into the battery compartment with the writing on the battery facing out and the connectors on the upper right-hand side. Nothing (including the strap) can be behind the battery.
  • Page 31 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Carefully push the battery under the solar regulator (if present) and against the back of the compartment, now strap it in tightly by pulling the ends of the strap. Battery Pack Attached to Compartment The strap includes a narrow opening into which you can slide the other end of the strap to help you tighten it.
  • Page 32 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Securing the Battery to the Pad For this type of battery compartment, a hook-and-loop pad on the back of the battery secures the battery to the back of the battery compartment.
  • Page 33 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Powering Up/Powering Down the Flow Computer DANGER EXPLOSION HAZARD: Do not attempt to connect power or disconnect power from the unit in a hazardous area. Ensure the area is non-hazardous. Failure to do so could result in an explosion.
  • Page 34: Installing Field Tools Configuration Software

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Installing Field Tools Configuration Software You install Field Tools software (which includes FBxConnect) on your PC to configure the device. Important Field Tools (including FBxConnect) is available as a free software download to registered ▪...
  • Page 35 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 After software installation re-boot, start Field Tools from either the Windows Start Programs menu or (if you created it) from the desktop icon. Log onto Field Tools. Important The first time you login with Field Tools, complete the User Name field with the default admin and leave the Password field blank.
  • Page 36: Setup Wizard

    Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Establishing a Connection and Launching the Setup Wizard CAUTION When making multiple FBxConnect connections to the same device (as with a remote and a local connection), be aware that the changes one connection makes to the device may not be immediately visible to other connections and may even require the other connections to restart FBxConnect before changes become visible.
  • Page 37 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Choose FBx as the Device platform. Choose a Connection Type ▪ For serial: choose the PC Comm port (or the port for the USB/serial adapter). For WiFi: choose the default WiFi Network. The format for the WiFi Network (SSID) is ▪...
  • Page 38 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Click Connect. Field Tools activates the connection and automatically launches the FBxConnect tool. When prompted, enter admin for both the Username and Password. Important When you finish initial configuration activities, be sure you change the password for the admin user.
  • Page 39 Emerson FB2200 Flow Computer Quick Start Guide D301788X012 March 2019 Click Initial Setup to launch the setup wizard. Follow the on-screen instructions to configure the device. Click Next (or Apply) to proceed through pages of the wizard or click Previous to return to a previous page. When you are...
  • Page 40 Emerson Automation Solutions Remote Automation Solutions Emerson FZE P.O. Box 17033 © 2018-2019 Remote Automation Solutions, a business unit of Emerson Automation Jebel Ali Free Zone – South 2 Solutions. All rights reserved. Dubai U.A.E. This publication is for informational purposes only. While every effort has been made to ensure...