ABB ABILITY SSC600 Product Manual
ABB ABILITY SSC600 Product Manual

ABB ABILITY SSC600 Product Manual

Smart substation control and protection for electrical systems
Hide thumbs Also See for ABILITY SSC600:

Quick Links

ABB ABILITY™ SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS
JANUARY 2019
PRODUCT GUIDE
SSC600
Table of Contents
loading

Summary of Contents for ABB ABILITY SSC600

  • Page 1 ABB ABILITY™ SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS JANUARY 2019 PRODUCT GUIDE SSC600...
  • Page 2: Table Of Contents

    15. Protection functions ..........11 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    SSC600 Product version: 1.0 1. Description ABB Ability™ Smart Substation Control and Protection for elec- trical systems SSC600 is a smart substation device designed for protection, control, measurement and supervision of utility substa- tions and industrial switchgear and equipment. The design of the device has been guided by the IEC 61850 standard for commu- nication and interoperability of substation automation devices.
  • Page 4: Supported Abb Solutions

    To facilitate the system engineering, ABB’s devices are neutral earthing CTs can differ from those of the phase current supplied with connectivity packages.
  • Page 5: Control

    Product Guide 1MRS758725 SSC600 Product version: 1.0 COM600S can also function as a gateway and provide seamless The device also calculates the demand value of the current over connectivity between the substation devices and network-level a user-selectable, pre-set time frame, the thermal overload of the control and management systems, such as MicroSCADA Pro and protected object, and the phase unbalance based on the ratio System 800xA.
  • Page 6: Disturbance Recorder

    Product Guide 1MRS758725 SSC600 Product version: 1.0 7. Disturbance recorder 9. Recorded data The device is provided with a disturbance recorder fuaturing up The device has the capacity to store the records of the 128 latest to 160 analog channels and 512 binary channels. The analog fault events.
  • Page 7: Condition Monitoring

    Product Guide 1MRS758725 SSC600 Product version: 1.0 10. Condition monitoring any Ethernet-based application in the standard COMTRADE file format. The device supports simultaneous event reporting to five The condition monitoring functions of the device constantly mon- different clients on the station bus. The device can exchange data itor the performance and the condition of the circuit breaker.
  • Page 8 Product Guide 1MRS758725 SSC600 Product version: 1.0 Figure 3. Parallel redundancy protocol (PRP) solution The device can be connected to Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fiber optic LC connector (1000Base-SX), depending on the product variant. The device supports the following high accuracy time synchro- nization method with a timestamping resolution of 4 μs required especially in process bus applications.
  • Page 9: Technical Data

    Product Guide 1MRS758725 SSC600 Product version: 1.0 14. Technical data Table 1. Dimensions Description Value Width 440 mm / 17.3” Height 88 mm / 3.4” Depth 220 mm / 8.6” Weight 6.0kg Mounting 2U Rack mount (19”), fits into standard 19” rack Table 2.
  • Page 10 Product Guide 1MRS758725 SSC600 Product version: 1.0 Description IEC 61850-3 Reference Requirement Test standard Test ports Mains frequency voltage 6.7.3 30 V cont. IEC 6100-4-16 300 V 1s Ripple on d.c. power supply 6.7.3 10% of Un IEC 6100-4-17 Damped oscillatory 6.7.3 2,5 kV CM IEC 6100-4-18...
  • Page 11: Protection Functions

    Product Guide 1MRS758725 SSC600 Product version: 1.0 15. Protection functions Table 12. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy PHLPTOC Depending on the frequency of the measured current: fn ±2 Hz ±1.5% of the set value or ±0.002 × In PHHPTOC and ±1.5% of set value or ±0.002 ×...
  • Page 12 Product Guide 1MRS758725 SSC600 Product version: 1.0 Characteristic Value Reset ratio Typically 0.96 Retardation time <30 ms Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±1.0% of the set value or ±20 ms Suppression of harmonics RMS: No suppression DFT: -50 dB at f = n ×...
  • Page 13 Product Guide 1MRS758725 SSC600 Product version: 1.0 Parameter Function Value (Range) Step Operating curve type EFLPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 EFHPTOC Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17...
  • Page 14 Product Guide 1MRS758725 SSC600 Product version: 1.0 Characteristic Value Operate time accuracy ±1.0% of the set value of ±20 ms Suppression of harmonics -50 dB at f = n × fn, where n = 2, 3, 4, 5,… Table 21. Admittance-based earth-fault protection (EFPADM) main settings Parameter Function Value (Range)
  • Page 15 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 24. Transient/intermittent earth-fault protection (INTRPTEF) Characteristic Value Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the measured current: fn ±2 Hz ±1.5% of the set value or ±0.002 × Uo Operate time accuracy ±1.0% of the set value or ±20 ms Suppression of harmonics...
  • Page 16 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 29. Phase discontinuity protection (PDNSPTOC) main settings Parameter Function Value (Range) Step Start value PDNSPTOC 10...100% Operate delay time PDNSPTOC 100...30000 ms Min phase current PDNSPTOC 0.05...0.30 × In 0.01 Table 30. Table 33: Residual overvoltage protection (ROVPTOV) Characteristic Value Operation accuracy...
  • Page 17 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 34. Three-phase overvoltage protection (PHPTOV) Characteristic Value Operation accuracy Depending on the frequency of the measured voltage: fn ±2 Hz ±1.5% of the set value or ±0.002 × Un Start time UFault = 1.1 × set Start value Minimum Typical Maximum...
  • Page 18 Product Guide 1MRS758725 SSC600 Product version: 1.0 Characteristic Value Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time <35 ms Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms Suppression of harmonics DFT: -50 dB at f = n ×...
  • Page 19 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 43. Three-phase underimpedance protection (UZPDIS) Characteristic Value Operation accuracy Depending on the frequency of the measured current and voltage: fn ±2 Hz ±3.0% of the set value or ±0.2 %Zb Start time Typically 50 ms 42, 43 Reset time...
  • Page 20 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 48. Three-phase inrush detector (INRPHAR) Characteristic Value Operation accuracy At the frequency f = fn Current measurement: ±1.5% of the set value or ±0.002 × In Ratio I2f/I1f measurement: ±5.0% of the set value Reset time +35 ms / -0 ms Reset ratio...
  • Page 21 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 55. Multipurpose protection (MAPGAPC) main settings Parameter Function Value (Range) Step Start value MAPGAPC -10000.0...10000.0 Operate delay time MAPGAPC 0...200000 ms Operation mode MAPGAPC 1 = Over 2 = Under Table 56. Fault locator (SCEFRFLO) Characteristic Value Measurement accuracy...
  • Page 22 Product Guide 1MRS758725 SSC600 Product version: 1.0 Characteristic Value Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time <35 ms Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms Suppression of harmonics DFT: -50 dB at f = n ×...
  • Page 23 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 65. Motor load jam protection (JAMPTOC) main settings Parameter Function Value (Range) Step Operation JAMPTOC 1 = on 5 = off Start value JAMPTOC 0.10...10.00 × In 0.01 Operate delay time JAMPTOC 100...120000 ms Table 66.
  • Page 24 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 70. Thermal overload protection for motors (MPTTR) Characteristic Value Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz Current measurement: ±1.5% of the set value or ±0.002 x In (at currents in the range of 0.01...4.00 x In) Operate time accuracy ±2.0% of the theoretical value or ±0.50 s...
  • Page 25 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 75. Stabilized and instantaneous differential protection for two-winding transformers (TR2PTDF) main settings Parameter Function Value (Range) Step High operate value TR2PTDF 500...3000 %Ir Low operate value TR2PTDF 5...50 %Ir Slope section 2 TR2PTDF 10...50% End section 2...
  • Page 26: Interconnection Functions

    Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 78. Operation characteristics Parameter Value (Range) Operating curve type 1 = ANSI Ext. inv. 2 = ANSI Very. inv. 3 = ANSI Norm. inv. 4 = ANSI Mod inv. 5 = ANSI Def. Time 6 = L.T.E.
  • Page 27: Power Quality Functions

    Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 81. Low-voltage ride-through protection (LVRTPTUV) Characteristic Value Operation accuracy Depending on the frequency of the measured voltage: fn ±2 Hz ±1.5% of the set value or ±0.002 × Un Start time Typically 40 ms 64, 65 Reset time Based on maximum value of Recovery time setting...
  • Page 28: Control Functions

    Product Guide 1MRS758725 SSC600 Product version: 1.0 18. Control functions Table 85. Autoreclosing (DARREC) Characteristic Value Operation accuracy ±1.0% of the set value or ±20 ms Table 86. Synchronism and energizing check (SECRSYN) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: fn ±1 Hz Voltage: ±3.0% of the set value or ±0.01 ×...
  • Page 29: Condition Monitoring And Supervision Functions

    Product Guide 1MRS758725 SSC600 Product version: 1.0 19. Condition monitoring and supervision functions Table 88. Circuit-breaker condition monitoring (SSCBR) Characteristic Value Current measuring accuracy ±1.5% or ±0.002 × In (at currents in the range of 0.1…10 × In) ±5.0% (at currents in the range of 10…40 × In) Operate time accuracy ±1.0% of the set value or ±20 ms Travelling time measurement...
  • Page 30: Other Functions

    Product Guide 1MRS758725 SSC600 Product version: 1.0 Characteristic Value Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,… RMS: No suppression Table 95. Sequence voltage measurement (VSMSQI) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz At voltages in range 0.01…1.15 ×...
  • Page 31: Whmi

    Product Selection Tool (PST), a Next-Generation Order Number Tool, supports order code creation for ABB Distribution Automa- tion IEC products with emphasis on but not exclusively for the Relion product family. PST is an easy to use, online tool always containing the latest product information.
  • Page 32: Tools

    Product Guide 1MRS758725 SSC600 Product version: 1.0 24. Tools The protection device is delivered as a preconfigured unit. The de- fault parameter setting values can be changed from the frontpanel user interface (local HMI), the Web browser based user interface (Web HMI) or Protection and Control IED Manager PCM600 in combination with the IED-specific connectivity package.
  • Page 33: References

    Product version: 1.0 services can be deactivated according to the required system setup. 26. References The www.abb.com/substationautomation portal provides informa- tion on the entire range of distribution automation products and services. The latest relevant information on the REF615 protection and control IED is found on the product page.
  • Page 34 Product Guide 1MRS758725 SSC600 Product version: 1.0 Function IEC 61850 IEC 60617 IEC-ANSI Negative-sequence overcurrent protection MNSPTOC1 I2>M (1) 46M (1) for machines Loss of load supervision LOFLPTUC1 3I< (1) 37 (1) Motor load jam protection JAMPTOC1 Ist> (1) 51LR (1) Motor start-up supervision STTPMSU1 Is2t n<...
  • Page 35: Order Form

    Product Guide 1MRS758725 SSC600 Product version: 1.0 Function IEC 61850 IEC 60617 IEC-ANSI Three-phase voltage measurement VMMXU1 3U (1) 3V (1) Residual voltage measurement RESVMMXU1 Uo (1) Vn (1) Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1) Three-phase power and energy measure- PEMMXU1 P, E (1)
  • Page 36 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 112. Order code Order code digits Allowed Name Character Code Description 10 11 12 Transformer A-9 or A-Z Application Transformer Application Package for 2 feeders Package Transformer Application Package for 4 feeders None Motor Applica- A-9 or A-Z...
  • Page 37: Application Packages

    Product Guide 1MRS758725 SSC600 Product version: 1.0 29. Application Packages 29.1 Base App Base application package is always included in SSC600 and contains following functions instances. Amount of circuit breaker control functions and SMV receiver functions depends on the Digit 9 selection.
  • Page 38 Product Guide 1MRS758725 SSC600 Product version: 1.0 Table 117. Measurement Function Name IEC 61850 Name Number of Instances Three-phase current measurement CMMXU Sequence current measurement CSMSQI Residual current measurement RESCMMXU Three-phase voltage measurement VMMXU Residual voltage measurement RESVMMXU Sequence voltage measurement VSMSQI Three-phase power and energy measure- PEMMXU...
  • Page 39 Product Guide 1MRS758725 SSC600 Product version: 1.0 Function Name IEC 61850 Name Number of Instances Create events based on Integer MVI4GAPC values, four channel Analogue value scaling and event SCA4GAPC creation, four channel Function related to SMV stream SMVRECEIVE 5...20 receiver Received GOOSE Binary infor- GOOSERCV_BIN...
  • Page 40 Product Guide 1MRS758725 SSC600 Product version: 1.0 29.3 Advanced Feeder Application Package Advanced Feeder Application Package can be selected with order code Digit 5, and it can be selected for 5,10,15 or 20 feeders. The size of the package impacts the number of available function instances.
  • Page 41 Product Guide 1MRS758725 SSC600 Product version: 1.0 29.5 Motor Application Package Motor Application Package can be selected with order code Digit 8, and it can be selected for 5,10,15 or 20 feeders. The size of the package impacts the number of available function instances. The content of the package is described in the table below.
  • Page 42 ABB Distribution Solutions Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 Fax +358 10 22 41094 www.abb.com/mediumvoltage © Copyright 2019 ABB. All rights reserved. Specifications subject to change without notice.