INSTALLATION
INSTRUCTIONS
Magnetic Flowmeter
Models 10D1475/1476/1477
PN25001A
loading

Summary of Contents for ABB 10D1475

  • Page 1 INSTALLATION INSTRUCTIONS Magnetic Flowmeter Models 10D1475/1476/1477 PN25001A...
  • Page 2 INSTALLATION INSTRUCTIONS GENERAL This installation instruction literature serves as a guide for proper in- stallation of the associated magnetic flowmeter. A more detailed de- scription of installation procedures will be found in the Instruction Bulletin provided for the particular magnetic flowmeter primary. FIGURE 1.
  • Page 3: Tips & Techniques

    INSTALLATION INSTRUCTIONS TIPS & TECHNIQUES FIGURE 2. Recommended Piping Diagram Mounting hardware (supplied by ABB) consists of: studs, nuts, gas- kets and adapter(s).Check itemized packing list to be certain that all items listed have been received.
  • Page 4: Conduit Connections

    This tag highlights the installation techniques necessary for depend- able service from your ABB Magnetic Flowmeter. By observing and performing these operations, your meter warranty remains valid and satisfactory performance is assured. Coverage of all recommenda- tions given in this instruction is provided in detail within the Instruction Manual which accompanies your meter.
  • Page 5: Mounting Procedure

    INSTALLATION INSTRUCTIONS MOUNTING PROCEDURE INSTALLATION OF 1/10 - 3/8 INCH METERS • Align flange adapter on meter body, as shown below. • Install a gasket at meter inlet and outlet, as applicable for meter type. Observe flow direction arrow. • Insert meter with (with gaskets) between pipe flanges.
  • Page 6 INSTALLATION INSTRUCTIONS INSTALLATION OF 1/2 - 4 INCH METERS • Install a gasket at meter inlet and outlet, as applicable for meter type. • Insert meter (with gaskets) between pipe flanges. • Insert two lower mounting studs with adaptor sleeves between pipe flanges.
  • Page 7: Grounding Procedure

    ( Refer to FIGURE 6 ) • Customer must supply install bonding strap (e.g., 1/2" copper braid) from meter body to an external earth ground. FIGURE 6. Grounding Procedure, Conductive Pipeline NOTE Refer to appropriate Instruction Bulletin supplied by ABB for electrical interconnection diagram(s).
  • Page 8 • Refer to Figure 8 for optional grounding ring dimensions. FIGURE 7. Grounding Procedure, Non-Conductive Pipeline NOTE Refer to applicable Instruction Bulletin supplied by ABB for electrical interconnection diagram(s).
  • Page 9 • The grounding ring material must be con- ductive and not sub- ject chemical reaction with the me- tered fluid. • Grounding rings are available from ABB (2 required). ( Refer to FIGURE 8 ) FIGURE 8. Outline Dimensions of Accessory Grounding Rings...
  • Page 10 The Company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. © 2004 ABB Inc. Printed in USA ABB Inc. ABB Instrumentation Ltd ABB Instrumentation S.p.A ABB Automation Products GmbH 125 East County Line Road Howard Road, St.