The removable terminal for connecting the AS-i cable is located behind the lower cover on
the front of the AS-i master CM 1243-2.
If the AS-i shaped cable is used, you can recognize the correct polarity of the cable by
means of the symbol
Information on how to remove and re-install the terminal block can be found in the system
manual "SIMATIC S7-1200 Programmable Controller" (Order No.: 6ES7298-8FA30-8AH0).
Note
Maximum current carrying capacity of the terminal contacts
The current carrying capacity of the connection contacts is max. 8 A. If this value is
exceeded on the AS-i cable, the AS-i master CM 1243-2 must not be "looped in" to the AS-
i cable, but must instead be connected via a spur line (only one connection pair assigned on
the AS-i master CM 1243-2).
Please also ensure that the cables used are suitable for operating temperatures of at least
75°C if current is being conducted via the AS-i master and currents of greater than 4
amperes are present.
You will find additional information on connecting the AS-i cable in the section "Installation,
connection and commissioning of the modules" in the manual "AS-i Master CM 1243-2 and
AS-i data decoupling unit DCM 1271 for SIMATIC S7-1200".
Terminal assignment
Label
ASI+
ASI–
972
.
Meaning
AS-i connection – positive polarity
AS-i connection – negative polarity
Functional ground
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG