Thermocouple Signal Boards (Sbs); Sb 1231 1 Analog Thermocouple Input Specifications - Siemens S7-1200 System Manual

Hide thumbs Also See for S7-1200:
Table of Contents
A.12.4

Thermocouple signal boards (SBs)

A.12.4.1

SB 1231 1 analog thermocouple input specifications

Note
To use this SB, your CPU firmware must be V2.0 or higher.
Table A- 222 General specifications
Technical data
Order number
Dimensions W x H x D (mm)
Weight
Power dissipation
Current consumption (SM Bus)
Current consumption (24 VDC)
Table A- 223 Analog inputs
Technical data
Number of inputs
Type
Range
Nominal range (data word)
Overrange/underrange (data word)
Overflow/underflow (data word)
Resolution
Temperature
Voltage
Maximum withstand voltage
Noise rejection
Common mode rejection
Impedance
Accuracy
Repeatability
Measuring principle
Module update time
Cold junction error
Isolation (field side to logic)
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
SB 1231 AI 1 x 16 bit Thermocouple
6ES7 231-5QA30-0XB0
38 x 62 x 21
35 grams
0.5 W
5 mA
20 mA
SB 1231 AI 1x16 bit Thermocouple
1
Floating TC and mV
See Thermocouple filter selection table (Page 954).
0.1° C / 0.1° F
15 bits plus sign
±35 V
85 dB for the selected filter setting
(10 Hz, 50 Hz, 60 Hz, 400 Hz)
> 120 dB at 120 VAC
≥ 10 M Ω
See Thermocouple selection table (Page 954).
±0.05% FS
Integrating
See Thermocouple filter selection table (Page 954).
±1.5° C
500 VAC
Technical specifications
A.12 Analog signal boards (SBs)