Hide thumbs Also See for S7-1200:
Table of Contents
Technical specifications
A.9 Thermocouple and RTD signal modules (SMs)
System
Decimal
Hexadecimal
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
-32513
80FF
-32768
8000
In an overflow or underflow condition, analog outputs will take on the substitute value of the STOP mode.
1
Table A- 162 Analog output representation for current (SB and SM)
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-6912
E500
-6913
E4FF
-32512
8100
-32513
80FF
-32768
8000
In an overflow or underflow condition, analog outputs will take on the substitute value of the STOP mode.
1
918
± 10 V
-361.7 μ V
-7.5 V
-10 V
-11.76 V
See note 1
See note 1
0 mA to 20 mA
4 mA to 20 mA
See note 1
See note 1
See note 1
See note 1
23.52 mA
22.81 mA
20 mA
20 mA
15 mA
16 mA
723.4 nA
4 mA + 578.7 nA
0 mA
4mA
4 mA to 578.7 nA
0 mA
See note 1
See note 1
See note 1
See note 1
Voltage Output Range
Undershoot range
Underflow
Current output range
Overflow
Overshoot range
Rated range
Undershoot range
Not possible. Output value limited to 0 mA.
Underflow
System Manual, 03/2014, A5E02486680-AG
S7-1200 Programmable controller
Table of Contents
loading

Table of Contents