Hide thumbs Also See for S7-1200:
Table of Contents
Technical specifications
A.7 Digital signal modules (SMs)
Model
Switching delay (max.)
Maximum relay switching frequency
Lifetime mechanical (no load)
Lifetime contacts at rated load
Behavior on RUN to STOP
Number of outputs on simultaneously
Cable length (meters)
Table A- 135 SM 1223 DI 8 x 120/230 VAC, DQ 8 x Relay (6ES7 223-1QH32-0XB0)
Table A- 136 Connector Pin Locations for SM 1223 DI 8 x 120/240 VAC, DQ 8 x Relay (6ES7 223-
906
SM 1223 DI 8 x 120/230 VAC / DQ 8 x Relay
10 ms
1 Hz
10,000,000 open/close cycles
1000,000 open/close cycles
Last value or substitute value (default value 0)
500 m shielded, 150 m unshielded
1QH32-0XB0)
Pin
X10
1
L+ / 24 VDC
2
M / 24 VDC
3
1N
4
DI a.0
5
DI a.1
6
DI a.2
7
DI a.3
4 (no adjacent points) at 60 °C horizontal or 50 °C vertical
8 at 55 °C horizontal or 45 °C vertical
X11
GND
No connection
No connection
No connection
2N
1L
DI a.4
DQ a.0
DI a.5
DQ a.1
DI a.6
DQ a.2
DI a.7
DQ a.3
X12
No connection
No connection
2L
DQ a.4
DQ a.5
DQ a.6
DQ a.7
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
X13