Hide thumbs Also See for S7-1200:
Table of Contents
Technical specifications
A.1 General technical specifications
Table A- 8
Typical performance data
Data for selecting an actuator
Continuous thermal current
Switching capacity and life of the contacts
For ohmic load
For inductive load (according to
IEC 947-5-1 DC13/AC15)
Activating a digital input
Switching frequency
Mechanical
At ohmic load
At inductive load (according to
IEC 947-5-1 DC13/AC15)
At lamp load
836
2 A max.
Voltage
Current
24 VDC
2.0 A
24 VDC
1.0 A
24 VDC
0.5 A
48 VAC
1.5 A
60 VAC
1.5 A
120 VAC
2.0 A
120 VAC
1.0 A
120 VAC
0.5 A
230 VAC
2.0 A
230 VAC
1.0 A
230 VAC
0.5 A
Voltage
Current
24 VDC
2.0 A
24 VDC
1.0 A
24 VDC
0.5 A
24 VAC
1.5 A
48 VAC
1.5 A
60 VAC
1.5 A
120 VAC
2.0 A
120 VAC
1.0 A
120 VAC
0.5 A
230 VAC
2.0 A
230 VAC
1.0 A
230 VAC
0.5 A
Possible
Max. 10 Hz
Max. 1 Hz
Max. 0.5 Hz
Max. 1Hz
Number of operating cycles (typical)
0.1 million
0.2 million
1.0 million
1.5 million
1.5 million
1.0 million
1.5 million
2.0 million
1.0 million
1.5 million
12.0 million
Number of operating cycles (typical)
0.05 million
0.1 million
0.5 million
1.0 million
1.0 million
1.0 million
0.7 million
1.0 million
1.5 million
0.7 million
1.0 million
1.5 million
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
Table of Contents
loading

Table of Contents