A.1 General technical specifications
Electromagnetic compatibility
Electromagnetic Compatibility (EMC) is the ability of an electrical device to operate as
intended in an electromagnetic environment and to operate without emitting levels of
electromagnetic interference (EMI) that may disturb other electrical devices in the vicinity.
Table A- 2
Immunity per EN 61000-6-2
Electromagnetic compatibility - Immunity per EN 61000-6-2
EN 61000-4-2
Electrostatic discharge
EN 61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity test
EN 61000-4-4
Fast transient bursts
EN 6100-4-5
Surge immunity
EN 61000-4-6
Conducted disturbances
EN 61000-4-11
Voltage dips
Surge immunity
Wiring systems subject to surges from lightning strike coupling must be equipped with
external protection. One specification for evaluation of protection from lightning type surges
is found in EN 61000-4-5, with operational limits established by EN 61000-6-2. S7-1200 DC
CPUs and signal modules require external protection to maintain safe operation when
subject to surge voltages defined by this standard.
Listed below are some devices that support the needed surge immunity protection. These
devices only provide the protection if they are properly installed according to the
manufacturer's recommendations. Devices manufactured by other vendors with the same or
better specifications can also be used:
● Supply Voltage, 24 VDC: DEHN, Inc., Type BVT AD 24, Part Number 918 402
● Digital Inputs, 24 VDC: DEHN, Inc., Type DCO RK E 24, Part Number 919 988
● Digital Outputs, 24 VDC: DEHN, Inc., Type DCO RK E 24, Part Number 919 988
● Analog Inputs: DEHN, Inc., Type BXT ML4 BD12, Part Number 920 342
● Analog Outputs: DEHN, Inc., Type DCO RK E 12, Part Number 919 987
● Ethernet: DEHN, Inc., Type DPA M CAT6 RJ45S 48, Part Number 929 100
● RS-232: DEHN, Inc., Type DCO RK E 12, Part Number 919 987
● RS-485: DEHN, Inc., Type BXT ML2 BE HFS 5, Part Number 920 270
● Relay Outputs: None required
832
8 kV air discharge to all surfaces
6 kV contact discharge to exposed conductive surfaces
80 to 1000 MHz, 10 V/m, 80% AM at 1 kHz
1.4 to 2.0 GHz, 3 V/m, 80% AM at 1 kHz
2.0 to 2.7 GHz, 1 V/m, 80% AM at 1 kHz
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to I/O
AC systems - 2 kV common mode, 1 kV differential mode
DC systems - 2 kV common mode, 1 kV differential mode
For DC systems, refer to Surge immunity below
150 kHz to 80 MHz, 10 V RMS, 80% AM at 1kHz
AC systems
0% for 1 cycle, 40% for 12 cycles and 70% for 30 cycles at 60 Hz
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG