Hide thumbs Also See for S7-1200:
Table of Contents
Communication
10.2 PROFINET
Table 10- 16 TUSEND and TURCV condition codes for ERROR and STATUS
ERROR
STATUS
0
0000
0
7000
0
7001
0
7002
1
8085
1
8086
1
8088
1
8089
1
80A1
1
80A4
1
80B3
538
Description
Send job completed without error (TUSEND).
New data were accepted. The current length of the received data is shown in
RCVD_LEN (TURCV).
No job processing active (TUSEND)
Block not ready to receive (TURCV)
Start of job processing, data being sent (TUSEND): During this processing, the
operating system accesses the data in the DATA send area.
Block is ready to receive, receive job was activated (TURCV).
Follow-on instruction execution (REQ irrelevant), job being processed (TUSEND):
During this processing, the operating system accesses the data in the DATA send
area.
Follow-on instruction execution, job being processed: During this processing, the
TURCV instruction writes data to the receive area. For this reason, an error could
result in inconsistent data in the receive area.
LEN parameter is greater than the largest permitted value, has the value 0 (TUSEND),
or you changed the value of the LEN or DATA parameter since the first instruction
execution (TURCV).
The ID parameter is not in the permitted address range.
LEN parameter is larger than the memory area (TUSEND) or receive area (TURCV)
specified in DATA.
Receive area is too small (TURCV).
ADDR parameter does not point to a data block.
Communications error:
The specified connection between user program and communications layer of the
operating system has not yet been established.
The specified connection between the user program and the communication layer of
the operating system is currently being terminated. Transmission (TUSEND) or a
receive job (TURCV) over this connection is not possible.
The interface is being reinitialized.
IP address of the remote connection end point is invalid; it is possible that it matches
the local IP address (TUSEND).
The set protocol variant (connection_type parameter in the connection description)
is not UDP. Please use the TSEND or TRCV instruction.
ADDR parameter: Invalid settings for port number (TUSEND)
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
Table of Contents
loading

Table of Contents