Installation Instructions - Sanyo SPW-CR1503GDYH8 Technical Data & Service Manual

W-eco multi system series
Table of Contents

4. Installation Instructions

4-1. Selecting the installation site
Indoor Unit
AVOID:
areas where leakage of flammable gas may be
expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room
directly. This may cause "sweating" on the air
discharge ports, causing them to spray or drip.
2
Iocations where the remote controller will be splashed
with water or affected by dampness or humidity.
installing the remote controller behind curtains or
furniture.
DO:
select an appropriate position from which every corner
of the room can be uniformly cooled.
select a location where the ceiling is strong enough to
support the weight of the unit.
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation difference
above or below the outdoor unit and within a total
tubing length from the outdoor unit as detailed in Table
1-20.
allow room for mounting the remote controller about
1m off the floor, in an area that is not in direct sunlight
nor in the flow of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor
to the ceiling is greater than 3 m. (for SL type, greater
than 3.5 m)
Floor-Standing, Concealed Floor-Standing Type
min.
10 cm
Horizontal view
min.
10 cm
min. 100 cm
min. 100 cm
Vertical view
Design of W-ECO MULTI SYSTEM
Ceiling-Mounted Type
min. 25 cm
NOTE
The rear of the indoor unit can be installed flush
against the wall.
min. 50 cm
Concealed-Duct Type
2-Way, 4-Way Semi-Concealed Type
1-Way Semi-Concealed & Slim Type
Semi-Concealed Type
Ceiling
min. 5 cm
Obstacle
Air
discharge
Air
intake
min. 5 cm
Side view
Wall-Mounted Type
min.
15 cm
0754_M_I
II - 24
Ceiling
Wall
min. 25 cm
Front view
Air
discharge
Air intake
Side view
1174_T_I
Semi-Concealed Slim Type
Wall
100
cm
20
cm
100
Wall
cm
0770_AS_I
min.15 cm
min.
15 cm
0771_K_I
Front View
TD831077
20
cm
20
cm
1175_X_S