Siemens SIREC D200 Quick Start Manual
Siemens SIREC D200 Quick Start Manual

Siemens SIREC D200 Quick Start Manual

Display recorder
Hide thumbs Also See for SIREC D200:

Quick Links

s
Quick Start Guide - SIREC D200 Display Recorder
1. Connections
D200 rear panel
3
1
2
Slot B
4
(CH9 - 14)
Slot G
7
6
5
24Vdc TX
USB
RS485
Slot A
8
(CH1-3/CH1-6)
ETHERNET
24V TX Power Supply 2-way conn (5), RS485 Modbus port (6)
and USB port (7) are all on the Comms option card
Analogue Input - 3 or 6 channel. D200 = Slot A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
- +
*
- +
*
- +
*
CH1
CH2
CH3
Analogue Input board - 6 ch expansion (option). D200 = Slot B
1 2 3 4 5 6 7 8 9
10 11 12
*
*
*
*
- +
- +
- +
- +
CH9 CH10 CH11 CH12
Card
3 CH.
6 CH.
A
1-3
B
mV, V
T/C Passive
Ohms
3 wire R/T
Relay Alarm - 4 or 8 channel (option). D200 = Slot G
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO
Digital Input/Output - 8 channel (option). D200 = Slot G
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16
NO C NO C NO C NO C NO C NO C NO C NO C
Key: NO = Normally Open, C = Common, NC = Normally Closed,
A5E01040182-01; 43-TV-25-40 Iss.1 GLO Oct 06 UK
1) Earth/ground
2) 24VDC Inst. power (option)
3) AC supply 100-250VAC
4) CJC Connector (option)
5) 24V TXP Supply (option)
6) RS485 port (option)
7) USB host (option)
8) Ethernet connection (std)
- +
*
- +
*
- +
*
CH4
CH5
CH6
13 14 15 16 17 18
CJC
*
- +
*
- +
CH13 CH14
9 CH.
12 CH.
1-6
1-3
1-6
9-14
9-14
T/C Active
Current
(Slot B only)
4 wire R/T
2 wire R/T
Input across NO, C

2. Setup Menu

Select the Menu button
from the Process Screen
Configure
Setup
Options
Select Options in Credits menu, tick firmware
options to enable. Go to Finish and Commit
General
Inputs
All Analogue Inputs default to 12V
Field IO
Select Input channel
• Setup input Type. V, A, Ohms, RT, TC
• Select Sample Rate
• Select Range / RT / TC Type
Use Back button to return to Setup Menu
Pens
By default Pen 1 displays
Analogue Input 1, Pen 2
Pens
displays Analogue 2 etc.
Select Pen
• Setup Scale
• Set Alarms, if required
• Setup Logging (required to Log and
Save data in memory)
Use Back button to return to Setup Menu
Localization
Settings for Language and Time Zones, etc.
General
Settings
(Main Menu > Configure)
Settings
Finish
Edit
Factory
Credits
Analogue In
Back
Localisation
Set Date
and Time
Set Time
Commit