Siemens SIWAREX WP231 Manual

Siemens SIWAREX WP231 Manual

Hide thumbs Also See for SIWAREX WP231:
Table of Contents

Quick Links

SIWAREX WP231
Weighing systems
Electronic weighing system
SIWAREX WP231
Manual
07/2014
A5E31238908A-02
___________________
Introduction
___________________
Safety notes
___________________
Description
___________________
Application planning
___________________
Mounting
___________________
Connection
___________________
Commissioning
___________________
Scale parameters and
functions
___________________
Messages
___________________
Command lists
___________________
Communication
___________________
Operation requiring
verification
___________________
Technical data
___________________
Accessories
___________________
ESD guidelines
___________________
List of abbreviations
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
Table of Contents
loading

Summary of Contents for Siemens SIWAREX WP231

  • Page 1 ___________________ SIWAREX WP231 Introduction ___________________ Safety notes ___________________ Weighing systems Description ___________________ Application planning Electronic weighing system SIWAREX WP231 ___________________ Mounting ___________________ Connection Manual ___________________ Commissioning ___________________ Scale parameters and functions ___________________ Messages ___________________ Command lists ___________________ Communication ___________________ Operation requiring...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Installation guideline ....................... 25 EMC-compliant setup......................25 5.2.1 Introduction ..........................25 5.2.2 Possible effects of interference ....................25 5.2.3 Coupling mechanisms......................26 5.2.4 Five basic rules for securing EMC ..................26 Mounting on the SIMATIC S7-1200 ..................28 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 4 Activate service mode ......................52 7.6.2 Load standard parameters ..................... 52 7.6.3 Input of required parameters ....................53 7.6.4 Complete automatic calibration ....................53 7.6.5 Receive all data........................54 7.6.6 Checking the scale following calibration ................54 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 5 Low-pass filter number (commissioning) ................75 8.3.28 Mean value filter depth......................75 8.3.29 Display weighing range data ....................75 8.3.30 Interface for legal trade display ....................75 8.3.31 Firmware version SecureDisplay .................... 75 8.3.32 Minimum display size [%]......................76 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 6 8.12.1 Overview ..........................101 8.12.2 Device MAC address ......................102 8.12.3 Port MAC address ........................ 102 8.12.4 IP address ..........................102 8.12.5 Subnet mask ........................102 8.12.6 Gateway ..........................102 8.12.7 Device name ........................102 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 7 Current status of input 0, 1, 2, 3 ................... 119 8.20.7 Current status of digital output 0, 1, 2, 3 ................120 8.20.8 Refresh counter for process values ..................120 8.20.9 Current load cell signal in mV ....................120 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 8 Message list ......................... 134 9.5.1 System status message list ....................135 9.5.2 Technology error message list ..................... 135 9.5.3 Data and operating errors message list ................135 9.5.4 Messages by LEDs on the module ..................137 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 9 Table of contents Command lists ............................ 139 10.1 Overview ..........................139 10.2 Command lists ........................140 10.3 Command groups of the SIWAREX WP231 ................. 144 Communication ........................... 145 11.1 Integration in SIMATIC S7-1200 ................... 145 11.1.1 General information ......................145 11.1.2 Creating the hardware configuration ..................
  • Page 10 Assignment of data record 45 ....................126 Table 8- 25 Assignment of data record 46 ....................127 Table 8- 26 Assignment of data record 47 ....................130 Table 8- 27 Assignment of data record 48 ....................131 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 11 Commands 700 to 899: HMI display switching ................141 Table 10- 5 Commands 1000 ... : Basic functions for weighing commands ..........143 Table 10- 6 Command groups of the SIWAREX WP231 ................144 Table 11- 1 Memory requirements of the function block ................145 Table 11- 2 I/O data of function block ......................
  • Page 12 Table of contents Figure 6-1 SIWAREX WP231 connection areas ................... 29 Figure 6-2 Shielding in the screw gland ......................31 Figure 6-3 Shield connection element fitting (example) ................32 Figure 6-4 Connection of strain gauge load cell(s) with 4-wire system ............33 Figure 6-5 Connection of strain gauge load cell(s) with 6-wire system ............
  • Page 13: Introduction

    Introduction Purpose of the manual This manual contains all necessary information on the setup, installation, wiring and commissioning of the SIWAREX WP231 electronic weighing system. Basic knowledge required This manual requires basic knowledge of weighing technology. When used in the SIMATIC S7-1200, basic knowledge of the SIMATIC S7-1200 automation system and the TIA Portal are required.
  • Page 14 ● Information about field service, repairs, spare parts and lots more under "Services". Additional Support Please contact your local Siemens representative and offices if you have any questions about the products described in this manual and do not find the right answers.
  • Page 15: Safety Notes

    The device does usually not pose any risks of material damage or personal injury. Siemens provides automation and drive products with industrial security functions that support the secure operation of plants or machines. They are an important component in a holistic industrial security concept.
  • Page 16 Safety notes 2.1 General safety instructions SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 17: Description

    Description Product overview SIWAREX WP231 is a versatile and flexible weighing module that can be operated as a non- automatic weighing instrument. The electronic weighing system can be used in SIMATIC S7-1200 and uses all features of a modern automation system, such as integrated communication, operation and monitoring, the diagnostic system as well as the configuration tools in the TIA Portal.
  • Page 18: Area Of Application

    The electronic weighing system described here is the perfect solution for applications in which signals from weighing or force sensors are to be acquired and processed. The SIWAREX WP231 is a very accurate electronic weighing system. The SIWAREX WP231 is equipped for the following applications: ●...
  • Page 19: System Integration In Simatic

    SIMATIC modules. You can create customized or industry-specific solutions in no time with the help of the configuration package available under the "Ready for use" application for SIMATIC. Figure 3-1 System overview SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 20: Customer Benefits

    The scope of delivery only includes the SIWAREX WP231 weighing module. Note We recommend that you use the SIWAREX WP231 configuration package for configuring the SIWAREX WP231 electronic weighing system. The configuration package is not included in the scope of delivery of the module: → Accessories (Page 175).
  • Page 21: Application Planning

    The integration in SIMATIC gives you the option to process the weight value directly in the PLC (ProgrammabelLogic Controller). The SIWAREX WP231 is calibrated at the factory. This allows for automatic calibration of the scales without the need for calibration weights and replacement of modules without the need for recalibrating the scales.
  • Page 22: Parameter Assignment Options

    The display of the current scale status can be configured. You can switch between several languages in the program. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 23: Parameter Assignment With A Simatic Panel

    All parameters can be assigned and the module put into operation using a SIMATIC HMI Panel connected to the S7-1200 CPU and the SIWAREX WP231 function and data blocks. The Ready-for-Use software is included in the scope of delivery of the configuration package.
  • Page 24 Application planning 4.2 Parameter assignment options SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 25: Mounting

    ● Interferences transported by communication cables ● Interferences having an effect via process cables ● Interferences entering the system via the power supply and/or protective ground Interferences can impair the fault-free functioning of the electronic weighing system. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 26: Coupling Mechanisms

    ● Always use shielded data cables. Always connect both ends of the data cable shielding to ground on a large area. ● Keep unshielded cable ends as short as possible. ● Always use metal/metalized connector housings only for shielded data cables. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 27 ● Create a homogeneous reference potential and ground all electrical equipment. ● Use sufficiently dimensioned equipotential bonding conductors if potential differences exist or are expected between your system components. Equipotential bonding is absolutely mandatory for applications in hazardous areas. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 28: Mounting On The Simatic S7-1200

    The load cells, power supply and serial interfaces are connected via the screw-type connectors. Use of the WP231 in the SIMATIC TIA Portal is described in detail in cc 11 of this manual: → Integration in SIMATIC S7-1200 (Page 145) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 29: Connection

    Analog output connection Ethernet interface connection ③ ⑧ Load cell connection Calibration bridge connection ④ ⑨ RS485 interface connection Mounting terminals for the calibration protec- tion plate ⑤ Digital output connection Figure 6-1 SIWAREX WP231 connection areas SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 30: Connection

    (the load cells must be connected in parallel). If the distance of a load cell to the SIWAREX WP231 or the junction box is greater than the available length of the load cell connection cable, use the SIWAREX EB extension box.
  • Page 31 We recommended that you use the cables listed in chapter → Accessories (Page 175). 4. The shield must be connected to ground directly in the vicinity of the SIWAREX WP231. The maximum distance between the SIWAREX WP231 and the load cell applies when using the recommended cables.
  • Page 32: Shield Connection

    Use only cables with protective braided shield (see recommended cables of digital load cells in chapter Accessories (Page 175)). Shielding density must be at least 80%. Figure 6-3 Shield connection element fitting (example) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 33: Figure 6-4 Connection Of Strain Gauge Load Cell(S) With 4-Wire System

    Connection 6.4 Shield connection Figure 6-4 Connection of strain gauge load cell(s) with 4-wire system SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 34: Figure 6-5 Connection Of Strain Gauge Load Cell(S) With 6-Wire System

    Connection 6.4 Shield connection Figure 6-5 Connection of strain gauge load cell(s) with 6-wire system SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 35: Connection Of Digital Outputs (4 X Dq)

    Labeling Function DQ.0 Digital output 0 DQ.1 Digital output 1 DQ.2 Digital output 2 DQ.3 Digital output 3 DQ.3L+ +24 V DC power supply for digital outputs DQ.3M Ground of power supply for digital outputs SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 36: Connection Of Digital Inputs (4 X Di)

    2M. Table 6- 4 Connection of the digital inputs Labeling Function DI.0 Digital input 0 DI.1 Digital input 1 DI.2 Digital input 2 DI.3 Digital input 3 DI.2M Reference ground potential of the digital inputs SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 37: Connection Of The Analog Output (1 X Aq)

    Assignment of the analog output to the process value as well as its response in the event of a fault is carried out during commissioning in data record 7. Table 6- 5 Connection of analog output Labeling Function Analog output + Analog output - SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 38: Connection Of Rs485 Serial Interface

    EIA-485 D- RS485 data line - for feeding in of bus signal If a SIWAREX WP231 module forms the termination of an RS485 network, insert wire jumpers between the D+‘ and T+ terminals and between the D-‘ and T- terminals for termination of the bus network.
  • Page 39: Connection Of Siebert Display Via Rs485

    Figure 6-6 Connection of Siebert display S102 The RS485 interface in the DR13 of the SIWAREX WP231 is set as follows: ● Baud rate: 9 600 bit/s ● Character parity: Even ● Number of data bits: 8 ●...
  • Page 40: Connection Of The Ethernet Interface

    The following devices can be connected to the Ethernet interface: ● PC with SIWATOOL service and commissioning program ● Operator panels or other HMI devices with Ethernet and Modbus protocol TCP/IP ● Communication partner with Modbus protocol TCP/IP SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 41: Activation Of Write Protection

    6.11 Activation of write protection In the case of an officially verified SIWAREX WP231, write protection must be provided to prevent the changing of data relevant to the calibration. Insert a wire jumper between the module terminals P and PR for this purpose.
  • Page 42: Mounting Of The Calibration Protection Plate

    6.12 Mounting of the calibration protection plate In order to operate SIWAREX WP231 with verification capability, the load cell connections must be protected against manipulation. To achieve this, mount the calibration protection plate included in the calibration set as shown in the following picture. Subsequently secure the calibration protection plate using the associated terminals (see Figure 6-1 SIWAREX WP231 connection areas (Page 29)).
  • Page 43: Commissioning

    Parameters which can be entered in % or time are preset in such a way that they provide good results for most applications. With these default parameters, commissioning can be carried out in 5 minutes (see chapter Start (Page 45)). SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 44: Factory Setting Of The Mode Selector

    ● SIWATOOL The SIWATOOL program allows you to commission the scale without an Operator Panel and without an automation system. In the event of a fault, additional SIWATOOL diagnostics functions enable fast analysis of the cause. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 45: Minute Quick Start With The Operator Panel And The Ready-For-Use Software

    Quick Start". You will be guided through the individual tasks for setting the most important parameters. The remaining parameters are factory-set in such a way that they can be used in most cases without any changes. Figure 7-1 Quick start step 1 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 46: Standard Parameter Settings

    (except the Ethernet address and Modbus parameters). Service mode must be switched on first. Resetting to the standard parameters can then be carried out. Figure 7-2 Quick start step 2 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 47: Selecting The Calibration Method

    With both methods, make sure that the mechanical properties of the scale are flawless prior to calibration. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 48: Defining The Calibration Weights

    Note that the interval between the calibration weights must be at least 2% of the nominal load of the scale. With a 1 000 kg scale, a calibration weight of at least 20 kg must therefore be used. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 49: Setting Calibration Points

    Place "Calibration weight 2" defined in step 4 on the scale construction, and execute the "Set calibration weight 2" command. 4. Calibration of the scale is now complete. Return to the start screen by clicking on the house icon. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 50: Calibrating The Scale Automatically

    If the exact characteristic values are unknown, it is permissible to also use rounded-off numbers (e.g. 1.0 mV/V, 2.0 mV/V). The nominal load of an individual load cell (not the nominal load of the complete scale!) must subsequently be defined. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 51: Performing The Automatic Calibration

    3. If a second known reference weight is available, place it on the scale in addition. Check whether the scale displays the sum of the reference weights. 4. Remove the reference weights from the scale. Check that the display is "0 kg" again. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 52: Minute Quick Setup With Siwatool

    The quick setup is based on the standard settings of the weighing module. Therefore, the standard parameter settings must be reset prior to the quick setup. Firstly, service mode is activated; the standard parameters are subsequently loaded using the "Load standard parameters (12)" command. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 53: Input Of Required Parameters

    ● Rated load of a load cell 7.6.4 Complete automatic calibration ● The scale must be empty (only mechanical dead load). ● Activate the "Automatic Calibration 82" command. ● Activate the "Shift Characteristics 81" command. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 54: Receive All Data

    3. If a second known reference weight is available, place it on the scale in addition. Check whether the scale displays the sum of the reference weights. 4. Remove the reference weights from the scale. Check that the display is "0 kg" again. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 55: Service With The Siwatool Program

    "Value" column in the tree structure. For example, if data record 3 is to be sent, right-click on "Calibration parameter (DR3)". A submenu is then opened with the option for sending the respective data record to the SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 56: Offline Parameter Assignment

    The assignment of a new IP address to a SIWAREX module is necessary if several SIWAREX modules are present in one network. The following ports are used by SIWAREX: ● SIWATOOL port: 23006 ● MODBUS TCP/IP port: 502 ● TFTP for firmware download port: 69 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 57: Entering A Known Siwarex Ip Address

    (Page 175). Install the program "Primary Setup Tool". When started, the program can determine the Siemens devices present in the network. The MAC (Media Access Control) address can be read on the front of the SIWAREX module. Every device has an MAC address which is unique worldwide.
  • Page 58: Available Help Options

    If several parameters of the data record are to be changed, they are entered consecutively. The data record is subsequently selected in the tree view and sent to the SIWAREX modules using the right mouse button. Parameters are always changed as complete data records, rather than individually. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 59: Recording Scale Traces

    Excel and then processed further. The commands for starting and stopping are present in the "Trace commands" group (yellow memory card icon) in SIWATOOL. All important measured values, messages and changes in status are recorded. Figure 7-12 Trace export SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 60: Firmware Update

    3. Call the firmware download using the function key 4. Select the current firmware file under "Firmware Download". 5. Click the "Start transfer" button. Following the transfer, the SIWAREX module must be switched off and then on again. This activates the new firmware. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 61: Figure 7-13 Downloading The Firmware With Siwatool

    Commissioning 7.7 Service with the SIWATOOL program Figure 7-13 Downloading the firmware with SIWATOOL SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 62: Reading Out The Saved Scale Logs

    You can read out the logs with SIWATOOL using the "Logs" button A new window is opened, and all logs present in the weighing module are read out using "Refresh". You can subsequently save these in EXCEL or .csv format. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 63: Scale Parameters And Functions

    When it receives new parameters, the SIWAREX module runs a validation check. In the event of a parameter assignment error, the data record is not applied (not saved) by the SIWAREX module and a data/operator error is reported. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 64: Dr 2 Command Code

    (Page 68) Unit of Maximum length and actual UBYTE[2] 04.04 1011 weight head- length of string for unit of weight (e.g.: g, kg, t, ...) Unit of Unit of weight CHAR[4] "kg••" 1012 weight (Page 68) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 65 0: Autom. zero adjustment off 1036.14 zero adjust- 1: Autom. zero adjustment on ment (Page 70) Subtractive / Subtractive / additive tare de- 1036.13 additive tare vice device 0: Subtractive tare device (Page 70) 1: Additive tare device SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 66 Positive range of the semi- FLOAT 100.0 1046 positive zero automatic zeroing [in % of setting limit maximum weighing range] (semi- (positive + negative zero setting automatical- limit must not exceed 4% with ly) (Page 72) country code "OIML") SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 67 FW version SecureDis- SecureDisplay playHeader Firmware FW version of the SecureDis- CHAR[12] 1065 version play used on the HMI SecureDis- play (Page 75) Reserve Reserve UBYTE[2] 1071 Reserve Reserve CHAR[20] 1072 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 68: Scale Name

    Trade scales requiring official calibration are subject to certain restrictions. The restrictions in accordance with the OIML directive are activated by entering "1" for OIML R76. Enter "0" to deactivate the restrictions (function available soon). SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 69: Minimum Weighing Range

    The function can, however, be limited by setting a maximum and minimum weight for zero by power-on. See the section on maximum and minimum weights for zero by power-on. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 70: Zero By Power-On When Tare ≠ 0

    250 % of the maximum weighing range. The current tare value is deleted if you switch between additive and subtractive taring. NOTICE There is no automatic evaluation of whether there is sufficient load cell measuring range capacity for an additive tare. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 71: Weight Simulation

    If zero by power-on upon supply voltage ON is enabled, you can limit the effect of this function. The limitation is based not on the actual weight, but rather on the weight which the scales would display had there been no zeroing. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 72: Maximum Negative Zero Setting Limit (Semi-Automatically)

    (time of scale calibration). For legal trade scales, the limitation is a maximum of 4 % of the weighing range between the negative and positive weight for zeroing. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 73: Standstill Range

    (standstill time). Standstill monitoring is used in static scale mode (with the following commands: zeroing, taring). The current weight can only be registered in legal trade applications if standstill is reached. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 74: Standstill Waiting Time

    8.3.25 Low-pass filter number The number of the filter defines the effect of damping. The values 2, 4, 6, 8, and 10 can be set. The higher the selected filter number, the higher the effect. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 75: Low-Pass Filter Limit Frequency (Commissioning)

    The version of the SecureDisplay software is entered in the "FW-Version SecureDisplay" Parameter. If the version is not entered correctly, a scale value is not output on the SecureDisplay, and the display indicates "Start Up". SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 76: Minimum Display Size [%]

    "SecureDisplay". If the zoom factor for the minimum display size does not correspond to the smallest zoom factor stored in the "DisplayCali.xlm" file in the display unit, the weight value is hidden and the text "Start Up" is displayed. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 77: Calibration Procedure

    Load cell characteristic value Digits (approx.) at nominal load 1 mV/V 1 000 000 2 mV/V 2 000 000 4 mV/V 4 000 000 The diagram below illustrates the relationship between calibration digits and the calibration weight. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 78 The same applies when you change a weighing module. Note Two working points are usually sufficient for determining the scales' characteristic curve. An additional working point is only required for non-linear systems. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 79 Calibration weight 2 placed onto e.g. 80 kg Approx. 1 650 000 scale Nominal weight of load cell 100 kg Approx. 2 000 000 +10 % Rated weight + approx. 10 % Approx. 110 kg Approx. 2 200 000 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 80: Automatic Calibration

    Automatic calibration requires the following criteria: ● Correct mechanical installation of the scale ● Scale is empty (only mechanical installation (= dead load) present on the cells) ● Installed load cells are evenly loaded ● There are no shunt circuits SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 81: Dr 4 Output Of Calculated Calibration Digits

    Reserve 2 Reserve USHORT 1211 Reserve 3 Reserve FLOAT 1212 8.5.1 Calibration digits 0, 1, 2 (calculated) The calculation is based on the parameters from DR 10 and is executed using command no. 82 or 83. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 82: Dr 5 Zeroing Memory

    Depends 1228 (Page 83) during automatic calibra- on specifi- on specifi- tion cation in cation in DR 3 DR 3 Reserve 1 Reserve SHORT 1230 Reserve 2 Reserve USHORT 1231 Reserve 3 Reserve FLOAT 1232 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 83: Effective Tare Weight - From Specification 1, 2 Or 3

    The characteristic curve of the scales is determined during calibration. When there is no load, the main display returns "0". The dead load is the weight of the empty scales, i.e. the weight of the scales themselves. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 84: Dr 6 Limit Value Settings

    Limit value 1 Switch-off point for limit FLOAT maxi- maxi- 1244 ON, limit value 1 (% of measuring value 2 ON, range) num- number limit value 1 range OFF, limit range value 2 OFF (Page 86) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 85 Time for delayed switch- TIME maxi- 1258 limit value on of "Empty" in ms "Empty" ON number (Page 87) range+ Reserve 2 Reserve USHORT 1260 Reserve 3 Reserve USHORT 1261 Reserve 4 Reserve FLOAT 1262 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 86: Limit Value 1 On, Limit Value 2 On, Limit Value 1 Off, Limit Value 2 Off

    If the weight reaches the specified switch value, a delay time (defined in ms) is launched. Once the delay time is over, the limit switch changes status provided the weight still reaches the specified switch value. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 87: Limit Value "Empty" On

    If the weight reaches the specified switch value for scales status "empty", a delay time (defined in ms) is launched. Once the delay time is over, the switch for "empty" status changes status provided the weight still reaches the specified switch value. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 88: Dr 7 Interface Parameters

    >1 transition) Input filtering 0: 0.2 ms USHORT 2 1308 (hardware set- 1: 0.2 ms ting) (Page 92) 2: 0.4 ms 3: 0.8 ms 4: 1.6 ms 5: 3.2 ms 6: 6.4 ms 7: 12.8 ms SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 89 1314.5 Bit 12 Reserve 1314.4 Bit 13 Reserve 1314.3 Bit 14 Reserve 1314.2 Bit 15 Reserve 1314.1 Analog output 0: 0 … 20 mA USHORT 2 1315 range (Page 94) 1: 4 … 20 mA SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 90 1325.7 Bit 10 Reserve 1325.6 Bit 11 Reserve 1325.5 Bit 12 Reserve 1325.4 Bit 13 Reserve 1325.3 Bit 14 Reserve 1325.2 Bit 15 Reserve 1325.1 Reserve 1 Reserve LONG 1326 Reserve 2 Reserve FLOAT 1328 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 91: Assignment For Digital Input 0, 1, 2, 3

    0 … 1F Bit no. of the status flags from byte 0 .. 3 from data record 30 Control of output via data record 18 Control of output via SIMATIC S7 I/O Code FF Output always disabled SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 92: Response Of Digital Outputs To Faults Or Simatic Stop

    Value of DQ 2 following fault NOTICE Risk to the plant If an output is set following a fault (operating error), this can pose a risk for the plant. Ensure that the parameters are correctly set. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 93: Analog Output Range

    8.8.10 End value for the analog output This parameter defines the specified value at which 20 mA is output. The value can be greater or less than the start value. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 94: Output Value Following Fault Or Simatic Stop

    Recording every 10 s 8.8.13 Trace storage method This parameter is used to specify the response of the trace memory. Value Response Trace recording runs as circulating memory Trace is stopped when the trace memory is full SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 95: Dr 8 Date And Time

    1331 Application Information about which applica- USHORT 1332 tion the DR belongs to Version iden- Information on current data record USHORT 65635 1333 tifier version Date and time SIMATIC DTL format DTL#1970- 1334 01-01- 00:00:00.0 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 96: Dr 9 Module Information

    OS version String header UBYTE[2] 1365 header OS version Reference V - Release CHAR[2] 'V ' 1366 (loader) - B - Test designation etc. OS version e.g. version n USHORT 'V ' 1367 (loader) - designation SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 97 8.10 DR 9 module information Variable Note Type Length Default Min. Max. Modbus (bytes) registers DRAM Flash memory USHORT 1368 memory Flash memory MRAM memory USHORT 1369 MRAM Memory type USHORT 1370 memory Reserve 1 FLOAT 1371 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 98: Dr 10 Load Cell Parameters

    (Page 100) Reserve Reserve FLOAT 1414 Reserve Reserve FLOAT 1416 Reserve 2 Reserve SHORT 1418 Reserve 3 Reserve USHORT 1419 Reserve 4 Reserve FLOAT 1420 Parameter for calculation of calibration points with theoretical calibration SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 99: 50/60 Hz Toggling

    Rated load of a load cell The rated load of a load cell is required for checking the maximum weighing range of the scales. The rated load is entered in the specified units of weight. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 100: Dr 12 Ethernet Parameters

    USHORT Subnet mask n.n.n.x USHORT Gateway Gateway x.n.n.n USHORT Gateway n.x.n.n USHORT Gateway n.n.x.n USHORT Gateway n.n.n.x USHORT Device name Current device name header UBYTE[2] (Page 102) Current device name CHAR[32] Reserve 1 Reserve SHORT SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 101: Device Mac Address

    Assign the subnet mask of your network. 8.12.6 Gateway If a gateway is used between the SIWAREX WP231 and the communication partner, enter the gateway address here. If a gateway is not present, enter the IP address of the SIWAREX module.
  • Page 102: Overview

    1: 2 stop bits (Page 105) Bit 3 Reserve 1564.13 Bit 4 Reserve 1564.12 Bit 5 Reserve 1564.11 Bit 6 Reserve 1564.10 Bit 7 Reserve 1564.9 Bit 8 Reserve 1564.8 Bit 9 Reserve 1564.7 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 103: 8.13 Dr 13 Rs485 Parameters

    RS485 baud rate This parameter defines the baud rate for the RS485 interface. Value Baud rate 1 200 bps 2 400 bps 9 600 bps 19 200 bps 38 400 bps 57 600 bps 115 000 bps SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 104: Rs485 Character Parity

    This parameter defines the Modbus address (1 to 230) for communication via the RS485 interface with the Modbus protocol. 8.13.8 Decimal place for Siebert indicator A fixed decimal place must be specified if a Siebert indicator is used. The following values are permitted: 0 ... 4 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 105: Dr 14 Simatic Interface Parameters

    Selection of USHORT 1575 process value 2 (S7 I/O inter- face): Code for selection of process variable to be updated Reserve 1 Reserve SHORT 1576 Reserve 2 Reserve USHORT 1577 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 106: Selection Of Process Value 1, 2

    Bit 1 = status DI 1 Bit 2 = status DQ 2 Bit 2 = status DI 2 Bit 3 = status DQ 3 Bit 3 = status DI 3 See also Information about previous versions (Page 17) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 107: Dr 15 Tare Settings

    Up to three tare weights can be entered. If a tare weight is to be applied, it must be enabled with the corresponding command. The tare weights may not exceed the maximum values specified in data record DR 3. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 108 Scale parameters and functions 8.15 DR 15 tare settings SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 109: Dr 16 Simulation Value

    Only use weight simulation values which are within the measuring range of the scales. The word "TEST" is displayed on the main display during simulation and a status bit is set. From the start of simulation onward, all parameterized limits, inputs and outputs etc. refer to the simulation weight. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 110: Dr 17 Analog Output Control Specifications

    SHORT 1606 Reserve 2 Reserve USHORT 2 1607 8.17.2 Analog output specification The value to be entered must be between the start value (Page 94) and the end value (Page 94) of the analog output. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 111: Dr 18 Digital Output Control Specifications

    2=1 -> DA2 output enabled (only applies if output is assigned code 21, see DR 7) Specification for digital 1612.13 output 3=1 -> DA3 output enabled (only applies if output is assigned code 21, see DR 7) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 112: Specification For Digital Output 0, 1, 2, 3

    1613 8.18.2 Specification for digital output 0, 1, 2, 3 Digital outputs 0 to 3 can be controlled using data record 18 with this parameter. This function can be used for commissioning purposes, for example. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 113: Dr 30 Current Process Values

    1 Reserve 3004.12 Waiting for Set if module is waiting for 3004.11 standstill standstill to execute com- mand Standstill Set if standstill condition is 3004.10 3004.9 Empty Set if "Empty" condition is 3004.8 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 114 Taring or zeroing timeout 3007.15 2002 Trace overloaded 3007.14 2003 Zeroing not possible 3007.13 Gross process Gross weight (process value) FLOAT 3008 weight (Page 116) Net process Net weight (process value) FLOAT 3010 weight (Page 116) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 115: Gross Process Weight

    "Decimal places for process values" (Page 71) parameter. 8.19.4 Tare process weight The current tare weight. Values are rounded as specified in data record DR 3 with the "Decimal places for process values" (Page 71) parameter. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 116: Gross / Net Weight

    1 each time. Once the counter reaches the value 65536, it starts again from zero. The counter can be used as a time stamp for data record DR 30. 8.19.11 Last report ID The last generated report ID is displayed. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 117: Dr 31 Advanced Current Process Values

    Current status of input 2 3312.14 3 (Page 119) Current status of input 3 3312.13 Bit 4 Reserve 3312.12 Bit 5 Reserve 331211 Bit 6 Position of DIP switch 1 3312.10 Bit 7 Position of DIP switch 2 3312.9 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 118: Unfiltered Digit Value

    The current digit value for the digital-to-analog converter for the analog output. The resolution of the analog output is 16 bit. 8.20.6 Current status of input 0, 1, 2, 3 This parameter allows you to check the current status of the digital inputs. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 119: Current Status Of Digital Output 0, 1, 2, 3

    1 each time. Once the counter reaches the value 65536, it starts again from zero. The counter can be used as a time stamp for data record DR 30. 8.20.9 Current load cell signal in mV Display of currently measured signal voltage of the load cell(s) in mV. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 120 Command not possible because not at 3504.5 standstill 5104 Command not possible because range is 3504.4 exceeded 5105 Load cell parameter not plausible 3504.3 Reserve 3504.2 5107 Shifting characteristic not possible 3504.1 5199 Error in command to DI 3505.11 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 121 USHORT 3511 error code tion at the SIWATOOL interface (Page 123) Error code Synchronous error code caused by com- USHORT 3512 following mand at the DI commands at digital input (Page 123) Reserve USHORT 3513 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 122: 8.21 Dr 32 Display Of Data And Operator Errors

    SIWATOOL interface. 8.21.6 Error code following commands at digital input The error code is displayed here of the error which was triggered last as a result of a command via the digital input. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 123: Dr 34 Ascii Main Display Value

    Maximum length and actual length UBYTE[2] 16.2 4004 string header of string Content of For legal trade display of weight CHAR[16] " " 4005 main display with increased resolution, ... (see as ASCII below) string (Page 125) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 124: Content Of Main Display As Ascii String

    Tare display activated (pt) • •kg• Tare display activated • • • • • • •kg• NET = net B = gross T = tare pT = preset tare (tare setting active) S = sum SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 125: Dr 45 Protocol Request

    The protocol ID of the protocol to be displayed in data record 46 is entered at this point. The report ID to be read is also used for reading of the report for legal trade use by means of the SecureDisplay. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 126: Dr 46 Protocol Contents

    Tare identifier Tare identifier CHAR[2] " " No entry: Scale was not tared when logging T: Scale was tared with manual tare when logging pT: Scale was tared with tare specification from DR15 when logging SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 127: Oldest Protocol Id

    Gross / net identifier The identifier provides information on whether a gross weight or net weight was logged for the selected ID. 8.24.6 G/N weight The G/N weight of the selected log is displayed here. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 128: Unit Of Weight

    The tare identification of the selected log is displayed here. The identification shows whether the tare has been entered by the user (semi-automatically) or whether it is a specified tare. 8.24.9 Date, time The date and time of the selected log are displayed here. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 129: Dr 47 Logbook

    6923 String header for new SW String header UBYTE[2] 10.10 6928 version New SW version New FW version, e.g. V1.01.04 CHAR[10] " " 6929 CRC16 Checksum of logbook entry USHORT 6934 Reserve Reserve USHORT 6935 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 130: Dr 48 Date And Time 2 (For Modbus)

    Month Month USHORT 6965 Day in month USHORT 6966 Hour Hour USHORT 6967 Minute Minute USHORT 6968 Second Second USHORT 6969 Millisecond Millisecond USHORT 6970 Day of the Day of the week USHORT 6971 week SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 131 Scale parameters and functions 8.26 DR 48 date and time 2 (for Modbus) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 133: Messages

    ● Output of the message buffer to the SIWATOOL program (takes place automatically) ● Output by means of function block as bit field in Scale data block ● Output by means of data records DR 30 and DR 32 in case of communication with a Modbus master SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 134: Evaluating Messages With The Help Of Siwatool

    All messages of the SIWAREX module can be completely detected and processed in the controller with the help of the SIWAREX WP231 function block. The messages can be evaluated directly in a signaling system by means of a bit signaling area in the scale data block.
  • Page 135: System Status Message List

    Command code or data record is not known with current application 5002 Command or data change not possible 5002 The command or changing of data is not possible due to write protec- because write protection is active tion. The data record was rejected. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 136 7017 MAC address cannot be changed 7017 7018 Error in IP mask 7018 The specified IP addresses (DR12) are not plausible. 7019 RS485 parameter error 7019 The specified RS485 interface parameters (DR13) are not plausible. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 137: Messages By Leds On The Module

    Not used LED 14 Not used LED 15 Not used LED 16 Analog output active Analog output faulty Line 2 LED 1 LINK LAN connection exists LED 2 Rx/Tx LAN communication active LED 3 Not used SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 138 RS485 communication active LED 12 Not used LED 13 DQ.0 Digital output 0 active LED 14 DQ.1 Digital output 1 active LED 15 DQ.2 Digital output 2 active LED 16 DQ.3 Digital output 3 active SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 139: Command Lists

    → Table 10-4 Commands 700 to 899: HMI display switching (Page 141) → Table 10-5 Commands 1000 ... : Basic functions for weighing commands (Page 143) → Table 10-6 Command groups of the SIWAREX WP231 (Page 144) See also Command lists (Page 140)
  • Page 140: Command Lists

    (0 kg) and shifts the complete characteristic without changing the gradient. The com- mand can be used, for example, in order to compensate parts used for mounting calibration weights on the scale at the end of the calibration. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 141 Enable standard display gross/net (main dis- play and SecureDisplay) N process value (no write protec- Display net process weight on main display, tion) only permitted if OIML is not set as the regula- tion code (main display and SecureDisplay) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 142 The logbook entry after the last read entry is entry displayed on the SecureDisplay. Display log entry (DS46) The log entry requested in DS45 is displayed on the SecureDisplay, for duration of 10 s. Reserve Reserve Reserve SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 143 Tare specification 2 valid Activate specification tare weight 2 1015 Tare specification 3 valid Activate specification tare weight 3 1016 SIMATIC tare specification Specified tare weight from SIMATIC I/O interface See also Integration in SIMATIC S7-1200 (Page 145) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 144: Command Groups Of The Siwarex Wp231

    Command lists 10.3 Command groups of the SIWAREX WP231 10.3 Command groups of the SIWAREX WP231 The following commands can be triggered in the scale data block DB_SCALE in the area CMD1 to CMD3: Table 10- 6 Command groups of the SIWAREX WP231...
  • Page 145: Communication

    Integration in SIMATIC S7-1200 11.1.1 General information A SIWAREX WP231 occupies 32 bytes each in the I/O areas of the CPU. The maximum number of SIWAREX WP231 weighing modules is defined as follows: S7-1212 CPU → up to two WP231 weighing modules S7-1214 CPU →...
  • Page 146: Creating The Hardware Configuration

    11.1.2 Creating the hardware configuration Starting with TIA Portal V12, the SIWAREX WP231 is integrated as standard in the hardware profile as an S7-1200 technology module. For TIA Portal V11, an HSP is available for integration at: Hardware Support Package (http://support.automation.siemens.com/WW/view/de/73514020)
  • Page 147 Figure 11-3 Start address of module in TIA Portal Figure 11-4 HW ID of module in TIA Portal Diagnostic interrupts can be optionally enabled or deactivated in the module properties. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 148: Calling Of Function Block

    ● Start address SIWAREX WP231: 68 (see → Creating the hardware configuration (Page 146)) ● HW ID SIWAREX WP231: 271 (see → Creating the hardware configuration (Page 146)) ● Instance data block number of SIWAREX WP231 function block: DB231 The function block can be integrated at the desired position in the user program using drag and drop.
  • Page 149: Working With The Function Block

    2 or 1 for processing of the respective command. Note Cyclic triggering of the CMD1 command mailbox makes it impossible to send commands in mailbox 2 or 3. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 150 The new calibration weight is now present in the SIWAREX and can be used. Service mode for the module should subsequently be switched off again using command "2". This procedure for reading and writing data records is identical for all data records. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 151: I/O Interface Of Function Block

    Specification for analog output if this has assigned "S7 interface" as source in data record 7. DIGIT_OUTPUT (UINT) Specifications for digital outputs if these have been assigned as function "S7 interface" in data record 7. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 152: Error Codes Of Function Block

    Synchronous data operation error has occurred bo_StartUp Startup synchronization of module running Note If execution of the function block is faulty, the variables shown do not correspond to the actual status in the module. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 153: Communication Via Modbus

    Modbus RTU or the Ethernet interface with Modbus TCP/IP. It is possible to use both interfaces for the communication. Note The SIWAREX WP231 is designed for use in secure (closed) networks and does not have any protection against unauthorized data traffic. The following chapters describe the specifications for handling communication. The following functions can be executed: ●...
  • Page 154: Data Record Concept

    Command mailbox 1: Highest priority Variable Note Type Modbus registers CMD1_CODE Code of command to be executed USHORT CMD1_TRIGGER Trigger for starting the command USHORT CMD1_STATUS 0=job running; 1=job finished (1 cycle) USHORT CMD1_QUIT 0=no error; <>0=error code USHORT SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 155: Reading Registers

    A current measured value is to be read out from DR 30. ⇒ The register can be directly requested because its contents are automatically refreshed in the SIWAREX module at the specified measuring rate of 100 Hz and are always available up-to-date. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 156: Writing Registers

    (from the area of data/operator errors). You can find all further command numbers in chapter → Command lists (Page 139). In addition, an online document is available for working with SIWAREX WP231 and Modbus → Modbus communication of WP231 (http://support.automation.siemens.com/WW/view/de/77913998).
  • Page 157: Operation Requiring Verification

    The software must be installed on the HMI prior to the verification. The DisplayCali.xml file can be used to parameterize the selectable display sizes and positions on the HMI. You can find a complete description of the software installation in the information "SIWAREX SecureDisplay". SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 158: Parameterization Of The Scale

    The calibration labels are edited based on the templates from the calibration set, and subsequently printed. The fields in the calibration labels can already be provided with the corresponding values prior to the verification. The protective foil is attached during the verification. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 159: Verification

    SecureDisplay are retained Display previous logbook entry in the logbook. It is not possible to down- load the firmware following verification of Display next logbook entry the scale with the jumper for write protec- tion inserted. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 160: Checking Of Parameters Relevant To The Device

    – The version of the SecureDisplay is then shown on the display. 2. Checking of the firmware ID of the SIWAREX WP231 evaluation electronics The firmware ID of the SIWAREX WP231 evaluation electronics must agree with the requirements in the EC construction license. The currently valid version can be called on the SecureDisplay.
  • Page 161 Only the software downloads for the legal trade display SecureDisplay are retained in the logbook. It is no longer possible to download the firmware for the SIWAREX WP231 evaluation electronics following verification of the scale with the jumper for write protection inserted.
  • Page 162 The telegram address (No. 01) must be set on the Siebert display S102. Checking is carried out in accordance with the specifications in the Instruction Manual "Siebert series S102 - digital displays for Siemens Siwarex". SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 163: Technical Data

    Typical power loss of the module 4.5 W Power supply from SIMATIC S7 backplane bus Table 13- 2 Technical specifications: Power supply from SIMATIC S7 backplane bus Current consumption from S7-1200 backplane bus Typically 3 mA SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 164 Relative accuracy! (Absolute accuracy is only reached by calibration on-site with calibration stand- ard) Accuracy for module replacement or theoretical calibration decisive Value valid at sensor; voltage drops on cables are compensated up to 5 V SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 165 Refresh rate (FW) Switching delay typ. 25 µs turn on typ. 150 µs turn off RDSON < 0.25 Ω Short-circuit proof Electrical isolation 500 V AC Cable length (meter) Max. 500 m shielded, 150 m unshielded SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 166 390 Ω / 220 Ω / 390 Ω Electrical isolation 500 V AC Transfer protocol ASCII for remote display from Siebert and Modbus RTU) Cable length ≤ 115 kbps max. 1 000 m (fieldbus cable 2-wire, shielded, e.g. 6XV1830-0EH10) SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 167: Table 13- 10 Technical Specifications

    Cat-5e UTP cable • (unshielded) max. 100 m Cat-5e SF/UTP • cable (shielded) Dimensions and weights Table 13- 10 Technical specifications: Dimensions W x H x D 70 x 100 x 75 mm Weight 300 g SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 168: Table 13- 11 Technical Specifications: Mechanical Requirements And Data

    Free fall IEC 61131-2 For devices < 10 kg: • In product packaging: • IEC 60068-2-31: 300 mm drop height Test Ec, procedure 1 In shipping package: • 1.0 m drop height per 5 attempts • SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 169: Electrical, Emc And Climatic Requirements

    CSA C22.2, No. 142 1 500 V AC (shield and signals) UL508 Additional electrical circuits: Test voltage: 500 V AC or 707 V DC Test duration: ≥ 1 minute Short circuit current: ≥ 5 mA SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 170: Table 13- 13 Requirements: Interference Emission In Industrial Area In Accordance With En 61000-6-4

    0.15 ... 0.5 MHz: 53 dB (μA) to 43 dB (μA) Q • 40 dB (μA) to 30 dB (μA) M • 0.5 ... 30 MHz: 43 dB (μA) to 30 dB (μA) M • SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 171: Table 13- 14 Requirements: Interference Immunity In Industrial Area In Accordance With En 61000-6-2

    AD24V, Dehn&Söhne) NOTICE Radio interference is possible This is a device of class A. The device may cause radio interference in residential areas. Implement appropriate measures (e.g.: use in 8MC cabinets) to prevent radio interference. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 172: Table 13- 15 Operating Conditions In Accordance With Iec 60721

    13.2 Electrical, EMC and climatic requirements Ambient conditions The use of SIWAREX WP231 is intended under the following conditions in SIMATIC S7- 1200. Additionally observe the operating conditions of the S7-1200 system. Table 13- 15 Operating conditions in accordance with IEC 60721...
  • Page 173: Approvals

    "Product Information - Use of SIWAREX modules in a Zone 2 Hazardous Area (http://support.automation.siemens.com/WW/llisapi.dll?aktprim=100&lang=en&referer=%2f WW%2f&func=cslib.cssearch&nodeid0=4000024&viewreg=WW&siteid=csius&extranet=sta ndard&groupid=4000002&objaction=cssearch&content=adsearch%2Fadsearch%2Easpx)". Note The currently valid approvals for SIWAREX WP231 are to be found on the module rating plate. → CE approval (http://support.automation.siemens.com/WW/view/de/65692972) → cULus approval (http://support.automation.siemens.com/WW/view/de/74442065)
  • Page 174 Technical data 13.3 Approvals SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 175: Accessories

    SIWAREX WP231 manual Free download from the Internet WP231 manuals in various languages (http://support.automation.siemens.com/WW/view/de/6 4722267/133300) SIWAREX WP231 "Ready for use" Free download from the Internet "Ready for use" (http://support.automation.siemens.com/WW/view/de/6 4722267/133100) Ethernet patch cable CAT5 To connect the SIWAREX to a PC (SIWATOOL), SIMATIC CPU, panel, etc.
  • Page 176 Accessories Ordering data Description Order No. Digital remote display The digital remote displays can be connected directly to the SIWAREX WP231 through the RS485 interface. Suitable remote display: S102 Siebert Industrieelektronik GmbH Postfach 1180 D-66565 Eppelborn, Germany Tel.: 06806/980-0 Fax: 06806/980-999 Internet: http://www.siebert-group.com/en...
  • Page 177: Esd Guidelines

    Anyone who is not connected to the electrical potential of their surroundings can be electrostatically charged. The figure below shows the maximum electrostatic voltage which may build up on a person coming into contact with the materials indicated. These values correspond to IEC 801-2 specifications. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 178 In this way, the discharged energy can not affect the sensitive devices. Discharge your body before you start taking any measurements on a module. Do so by touching grounded metallic parts. Always use grounded measuring instruments. SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 179: List Of Abbreviations

    Preset tare (predefined tare weight with manual taring) Random access memory Programmable logic controller STEP 7 Programming device software for SIMATIC S7 Tare weight Technology module Touch Panel (SIMATIC) Universal Data Type (S7) Write protection Load cell(s) Numerical range SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 180 List of abbreviations SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 181: Index

    Index Additional Support, 14 Customer Support Hotline, 13 ESD guidelines, 177 Guidelines ESD guidelines, 177 Hotline, 13 Internet, 14 Scope of delivery, 20 Service, 14 Support, 14 SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...
  • Page 182 Index SIWAREX WP231 Manual, 07/2014, A5E31238908A-02...

Table of Contents