Siemens Simantic S7-1500 Manual
Siemens Simantic S7-1500 Manual

Siemens Simantic S7-1500 Manual

Cpu 1517t-3 pn/dp (6es7517-3tp00-0ab0)
Table of Contents
loading

Summary of Contents for Siemens Simantic S7-1500

  • Page 2 ___________________ Preface ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ Wiring S7-1500 CPU 1517T-3 PN/DP Interrupts, error messages, ___________ diagnostics and system (6ES7517-3TP00-0AB0) alarms ___________________ Manual Technical specifications ___________________ Dimension drawing 12/2017 A5E36285525-AB...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 5 This information is provided by the Siemens Industry Online Support in the Internet (https://support.industry.siemens.com). Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 6: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................7 Product overview ............................. 11 New functions in firmware version V2.5 ................. 11 Applications of the S7-1500 CPU ..................12 Hardware properties ......................19 Firmware functions ......................... 21 Operator controls and display elements ................25 2.5.1 Front view of the CPU with closed front flap ................
  • Page 7: Documentation Guide

    SIMATIC S7-1500 and ET 200MP systems, e.g. diagnostics, communication, motion control, Web server, OPC UA. You can download the documentation free of charge from the Internet (http://w3.siemens.com/mcms/industrial-automation-systems-simatic/en/manual- overview/Pages/Default.aspx). Changes and supplements to the manuals are documented in a Product Information.
  • Page 8 You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en). "mySupport" - Documentation In the Documentation area in "mySupport" you can combine entire manuals or only parts of these to your own manual.
  • Page 9 Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products. You will find the application examples on the Internet (https://support.industry.siemens.com/sc/ww/en/sc/2054). TIA Selection Tool With the TIA Selection Tool, you can select, configure and order devices for Totally Integrated Automation (TIA).
  • Page 10 Documentation guide PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the PROFINET network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET network and all connected components. ● The IO check is a fast test of the wiring and the module configuration of a system.
  • Page 11: Product Overview

    Product overview New functions in firmware version V2.5 New functions of the CPUs firmware 2.5 This section lists the new features of the CPU with firmware version V2.5. You can find additional information in the sections of this manual. Table 2- 1 New functions of the CPUs with firmware version 2.5 New functions Applications...
  • Page 12: Applications Of The S7-1500 Cpu

    Product overview 2.2 Applications of the S7-1500 CPU Applications of the S7-1500 CPU Area of application SIMATIC S7-1500 is the modular control system for a wide variety of automation applications in discrete automation. The modular and fanless design, simple implementation of distributed structures, and user-friendly operation make SIMATIC S7-1500 the economic and convenient solution for a variety of tasks.
  • Page 13 Product overview 2.2 Applications of the S7-1500 CPU Performance segments of the standard, compact, fail-safe and technology CPUs The CPUs can be used for smaller and mid-range applications, as well as for the high-end range of machine and plant automation. Table 2- 2 Standard CPUs Performance segment PROFIBUS...
  • Page 14 Product overview 2.2 Applications of the S7-1500 CPU Table 2- 4 Fail-safe CPUs Performance segment PROFIBUS PROFINET PROFINET PROFINET Work Processing interfaces IO RT/IRT IO RT basic func- memory time for bit interfaces interface tionality operations CPU 1511F-1 Fail-safe CPU for small 1.225 MB 60 ns to mid-range applica-...
  • Page 15 Product overview 2.2 Applications of the S7-1500 CPU Table 2- 5 Technology CPUs Performance segment PROFIBUS PROFINET PROFINET PROFINET Work Processing interfaces IO RT/IRT IO RT basic func- memory time for bit interfaces interface tionality operations CPU 1511T-1 Technology CPU for 1.225 MB 60 ns small to mid-range...
  • Page 16 Product overview 2.2 Applications of the S7-1500 CPU Integrated Motion Control technology functions All CPUs of SIMATIC S7-1500 support Motion Control technology functions. STEP 7 offers Motion Control instructions standardized according to PLCopen for configuring and connecting a drive to the CPU. S7-1500 Motion Control supports the following technology objects: ●...
  • Page 17 Product overview 2.2 Applications of the S7-1500 CPU Other technology functions Technology modules also implement functions such as high-speed counting, position detection and measuring functions and pulse generators (PTO, PWM and frequency output). For compact CPU 1511C-1 PN and CPU 1512C-1 PN CPUs, these functions are already integrated and can be implemented without additional technology modules.
  • Page 18 Detailed information about this and a multitude of other display functions is available in the SIMATIC S7-1500 Display Simulator (http://www.automation.siemens.com/salesmaterial-as/interactive-manuals/getting- started_simatic-s7-1500/disp_tool/start_en.html). Uniform front connectors for all modules and integrated potential bridges for flexible formation of potential groups simplifies storage.
  • Page 19: Hardware Properties

    Product overview 2.3 Hardware properties Hardware properties Article number 6ES7517-3TP00-0AB0 View of the module The following figure shows the CPU 1517T-3 PN/DP. Figure 2-1 CPU 1517T-3 PN/DP Note Protective film Note that a protective film is applied to the display in the delivery state of the CPU. Remove the protective film if necessary.
  • Page 20 IO controller and is used in the process as an intelligent pre-processing unit of sub-processes Accessories You can find information on "Accessories/spare parts" in the S7-1500, ET 200MP system manual (http://support.automation.siemens.com/WW/view/en/59191792). CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0) Manual, 12/2017, A5E36285525-AB...
  • Page 21: Firmware Functions

    The system automatically generates the messages for Diagnostics function manual diagnostics the system diagnostics and outputs these messages (http://support.automation.siemens.c via a programming device/PC, HMI device, the Web om/WW/view/en/59191792) server or the integrated display. System diagnostics information is also available when the CPU is in STOP mode.
  • Page 22 RT (real time) RT prioritizes PROFINET IO telegrams over standard PROFINET function manual telegrams. This ensures the required determinism in (http://support.automation.siemens.c the automation technology. In this process the data is om/WW/view/en/49948856) transferred via prioritized Ethernet telegrams. A reserved bandwidth within the send clock is available (isochronous real time) for IRT data.
  • Page 23 S7-1500 CPUs support the controlled positioning and S7-1500 Motion Control function traveling of axes via S7-1500 Motion Control functions manual by means of the following technology objects: (http://support.automation.siemens.c om/WW/view/en/109749262) Speed-controlled axes, positioning axes, synchronized axes, external encoders, cams, cam tracks and measuring inputs.
  • Page 24 Description Additional information Integrated closed-loop PID control function manual PID Compact (continuous PID controller) • control functionality (https://support.industry.siemens.co PID 3Step (step controller for integrating actuators) • m/cs/ww/en/view/108210036) PID Temp (temperature controller for heating and • cooling with two separate actuators)
  • Page 25: Operator Controls And Display Elements

    Product overview 2.5 Operator controls and display elements Operator controls and display elements 2.5.1 Front view of the CPU with closed front flap The figure below shows the front view of the CPU 1517T-3 PN/DP. ① LEDs for the current operating mode and diagnostics status of the CPU ②...
  • Page 26 In addition to the mechanical lock, you can also block access to a password-protected CPU on the display (local lock) and assign a password for the display. You can find additional information on the display, the configurable protection levels and local locking in the S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Reference...
  • Page 27: Front View Of The Cpu Without Front Flaps

    Product overview 2.5 Operator controls and display elements 2.5.2 Front view of the CPU without front flaps The figure below shows the operator controls and connection elements of the CPU 1517T-3 PN/DP. ① Mode selector ② No function ③ PROFIBUS interface (X3) ④...
  • Page 28: Rear View Of The Cpu

    Product overview 2.6 Mode selector 2.5.3 Rear view of the CPU The following figure shows the connection elements on the rear of the CPU 1517T-3 PN/DP. ① Shield contact surfaces ② Plug-in connection for power supply ③ Plug-in connection for backplane bus ④...
  • Page 29: Wiring

    Wiring This section provides information on the pin assignment of the individual interfaces and the block diagram of the CPU 1517T-3 PN/DP. 24 V DC supply voltage (X80) The connector for the supply voltage is plugged in when the CPU ships from the factory. The following table shows the pin assignment for a 24 V DC power supply.
  • Page 30 Wiring PROFINET interface X1 with 2-port switch (X1 P1 R and X1 P2 R) The assignment corresponds to the Ethernet standard for an RJ45 plug. ● When autonegotiation is deactivated, the RJ45 socket is allocated as a switch (MDI-X). ● When autonegotiation is activated, autocrossing is in effect and the RJ45 socket is allocated either as data terminal equipment (MDI) or a switch (MDI-X).
  • Page 31 Reference You can find additional information on the topics of "Wiring the CPU" and "Accessories/spare parts" in the S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0) Manual, 12/2017, A5E36285525-AB...
  • Page 32 Wiring Assignment of the MAC addresses CPU 1517T-3 PN/DP has two PROFINET interfaces. The first interface has two ports. Each of the PROFINET interfaces has a MAC address and each of the PROFINET ports has its own MAC address. In total, the CPU 1517T-3 PN/DP has five MAC addresses. The MAC addresses of the PROFINET ports are needed for the LLDP protocol, for example for the neighborhood discovery function.
  • Page 33 Wiring Block diagram The following figure shows the block diagram of the CPU 1517T-3 PN/DP. ① Display PN X1 P1 R PROFINET interface X1 Port 1 ② RUN/STOP/MRES mode selector PN X1 P2 R PROFINET interface X1 Port 2 ③ Electronics PN X2 P1 PROFINET interface X2 Port 1...
  • Page 34: Interrupts, Error Messages, Diagnostics And System Alarms

    You can find additional information on the topic of "Interrupts" in the STEP 7 online help. You can find additional information on the topic of "Diagnostics" and "System alarms" in the Diagnostics (http://support.automation.siemens.com/WW/view/en/59192926) function manual. Status and error displays of the CPU LED display The following figure shows the LED displays of the CPU 1517T-3 PN/DP.
  • Page 35 Interrupts, error messages, diagnostics and system alarms 4.1 Status and error displays of the CPU Meaning of the RUN/STOP, ERROR and MAINT LEDs The CPU 1517T-3 PN/DP has three LEDs to signal the current operating status and diagnostics status. The following table shows the meaning of the various combinations of colors for the RUN/STOP, ERROR and MAINT LEDs.
  • Page 36 Interrupts, error messages, diagnostics and system alarms 4.1 Status and error displays of the CPU RUN/STOP LED ERROR LED MAINT LED Meaning Startup (CPU booting) Test of LEDs during startup, inserting a module. LED flashes red LED flashes yellow LED flashes yellow/green LED flashing test Meaning of LINK RX/TX LED...
  • Page 37: Technical Specifications

    Technical specifications Article number 6ES7517-3TP00-0AB0 General information Product type designation CPU 1517T-3 PN/DP HW functional status FS05 Firmware version V2.5 Engineering with V15 (FW V2.5) / V14 (FW V2.0) or higher STEP 7 TIA Portal configurable/integrated • as of version Configuration control via dataset Display...
  • Page 38 Technical specifications Article number 6ES7517-3TP00-0AB0 Work memory 3 Mbyte integrated (for program) • 8 Mbyte integrated (for data) • Load memory 32 Gbyte Plug-in (SIMATIC Memory Card), max. • Backup maintenance-free • CPU processing times for bit operations, typ. 2 ns for word operations, typ.
  • Page 39 Technical specifications Article number 6ES7517-3TP00-0AB0 Number of asynchronous error OBs • Number of synchronous error OBs • Number of diagnostic alarm OBs • Nesting depth per priority class • Counters, timers and their retentivity S7 counter 2 048 Number • Retentivity –...
  • Page 40 Technical specifications Article number 6ES7517-3TP00-0AB0 I/O address area 32 kbyte; All inputs are in the process image Inputs • 32 kbyte; All outputs are in the process image Outputs • per integrated IO subsystem 16 kbyte; 16 KB via the integrated PROFINET IO –...
  • Page 41 Technical specifications Article number 6ES7517-3TP00-0AB0 Operating hours counter Number • Clock synchronization supported • to DP, master • in AS, master • in AS, slave • on Ethernet via NTP • Interfaces Number of PROFINET interfaces Number of PROFIBUS interfaces 1.
  • Page 42 Technical specifications Article number 6ES7517-3TP00-0AB0 512; In total, up to 1 000 distributed I/O devices – Number of connectable IO Devices, can be connected via AS-i, PROFIBUS or max. PROFINET – Of which IO devices with IRT, max. – Number of connectable IO Devices for RT, max.
  • Page 43 Technical specifications Article number 6ES7517-3TP00-0AB0 – Number of IO Controllers with shared device, max. Yes; Per user program – Asset management record 2. Interface Interface types Number of ports • integrated switch • Yes; X2 RJ 45 (Ethernet) • Functionality Yes;...
  • Page 44 Technical specifications Article number 6ES7517-3TP00-0AB0 Update time for RT 1 ms to 512 ms – for send cycle of 1 ms PROFINET IO Device Services – PG/OP communication – S7 routing – Isochronous mode – Open IE communication – – –...
  • Page 45 Technical specifications Article number 6ES7517-3TP00-0AB0 Protocols Number of connections 320; via integrated interfaces of the CPU and Number of connections, max. • connected CPs / CMs Number of connections reserved for • ES/HMI/web Number of connections via integrated • interfaces 64;...
  • Page 46 Technical specifications Article number 6ES7517-3TP00-0AB0 – Equidistance 125; In total, up to 1 000 distributed I/O devices – Number of DP slaves can be connected via AS-i, PROFIBUS or PROFINET – Activation/deactivation of DP slaves OPC UA Runtime license required •...
  • Page 47 Technical specifications Article number 6ES7517-3TP00-0AB0 Status/control Status/control variable • Inputs/outputs, memory bits, DBs, distributed Variables • I/Os, timers, counters Number of variables, max. • 200; per job – of which status variables, max. 200; per job – of which control variables, max. Forcing Peripheral inputs/outputs Forcing, variables...
  • Page 48 Technical specifications Article number 6ES7517-3TP00-0AB0 Number of available Extended Motion Con- • trol resources for technology objects Required Extended Motion Control re- • sources – for each cam – for each set of kinematics Positioning axis • – Number of positioning axes at motion control cycle of 4 ms (typical value) –...
  • Page 49 1 978 g General technical specifications You can find information on the general technical specifications, such as standards and approvals, electromagnetic compatibility, protection class, etc., in the S7-1500, ET 200MP System Manual (http://support.automation.siemens.com/WW/view/en/59191792). CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0) Manual, 12/2017, A5E36285525-AB...
  • Page 50: Dimension Drawing

    Dimension drawing Dimension drawing CPU 1517T-3 PN/DP This section contains the dimension drawing of the module on the mounting rail, as well as a dimension drawing with the front panel open. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Dimension drawings for CPU 1517-3 PN/DP Figure A-1 Dimension drawing of the CPU 1517T-3 PN/DP, front and side view...
  • Page 51 Dimension drawing A.1 Dimension drawing CPU 1517T-3 PN/DP Figure A-2 Dimension drawing of the CPU 1517T-3 PN/DP, side view with open front panel CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0) Manual, 12/2017, A5E36285525-AB...

This manual is also suitable for:

Simatic s7-1500

Table of Contents