Page 1
Reference Manual 00809-0100-4100, Rev AA June 2012 Rosemount 3051 Wireless Series Pressure, Level, and Flow Solutions with WirelessHART™ Protocol...
Page 3
North American Response Center Equipment service needs. 1-800-654-7768 (24 hours—includes Canada) Outside of these areas, contact your local Emerson Process Management representative. The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
Page 4
leads can cause electrical shock. The Rosemount 3051 and all other wireless devices should be installed only after the Smart Wireless Gateway has been installed and is functioning properly. Wireless devices should also be powered up in order of proximity from the Smart Wireless Gateway, beginning with...
Page 5
Reference Manual Title Page 00809-0100-4100, Rev AA June 2012 Shipping considerations for wireless products (Lithium Batteries: Green Power Module, model number 701PGNKF): The unit was shipped to you without the Power Module installed. Please remove the Power Module from the unit prior to shipping. Each power module contains one “D”...
Page 6
Reference Manual Title Page 00809-0100-4100, Rev AA June 2012...
Reference Manual Table of Contents 00809-0100-4100, Rev AA June 2012 Contents 1Section 1: Introduction Using This Manual ............1 Models Covered .
Page 8
Table of Contents Reference Manual June 2012 00809-0100-4100, Rev AA 2.7.1 Operating Parameters ......... . . 17 Basic Setup.
Page 9
Reference Manual Table of Contents 00809-0100-4100, Rev AA June 2012 4Section 4: Commissioning Safety Messages ............47 4.1.1 Warnings ().
Page 10
Table of Contents Reference Manual June 2012 00809-0100-4100, Rev AA AAppendix A: Specifications and Reference Data Performance Specifications ..........79 A.1.1 Conformance to specification (±3s (Sigma)) .
Page 11
Reference Manual Table of Contents 00809-0100-4100, Rev AA June 2012 A.5.3 Rosemount 3051T In-Line Pressure Transmitter....101 A.5.4 Rosemount 3051CF Flowmeter Series ......105 A.5.5 Rosemount 3051L Level Transmitter .
Page 12
Table of Contents Reference Manual June 2012 00809-0100-4100, Rev AA Table of Contents...
Reference Manual Section 1: Introduction 00809-0100-4100, Rev AA June 2012 1.2.4 Rosemount 3051T Gage and Absolute Pressure Transmitter Measures gage pressure up to 10000 psi (689,5 bar). 1.2.5 Rosemount 3051L Liquid Level Transmitter Provides precise level and specific gravity measurements up to 300 psi (20,7 bar) for a wide variety of tank configurations.
Reference Manual Section 1: Introduction 00809-0100-4100, Rev AA June 2012 WirelessHART installation flowchart Figure 1-1. WirelessHART installation flowchart START HERE Configure Network ID Configure Join Configure Update Rate Bench Field Install Calibration? Mount Transmitter page 48 Configure for Configure for Configure for Verify Pressure...
Rosemount 3051CD Wireless device is illustrated in Figure X-X on page For the Rosemount 3051, pressure is applied to the isolating diaphragm(s). The oil deflects the sensor which then changes its capacitance or voltage signal. This signal is then changed to a digital signal by the Signal Processing.
1.5.3 Electrical Power Module The Rosemount 3051 Wireless Pressure Transmitter is self-powered. The power module contains one "D" size primary lithium/thionyl chloride battery (Green Power Module, model number 701PGNKF). Each battery contains approximately 5.0 grams of lithium. Under normal conditions, the battery materials are self-contained and are not reactive as long as the battery and the power module are maintained.
For inquiries outside of the United States, contact the nearest Emerson Process Management representative for RMA instructions. To expedite the return process outside of the United States, contact the nearest Emerson Process Management representative. Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard.
Power Module should be stored in a clean and dry area. For maximum battery life, storage temperature should not exceed 30° C. Emerson Process Management Instrument and Valve Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.2.1 Warnings ( ) Explosions can result in death or serious injury. Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are installed in accordance with intrinsically safe or nonincendive field wiring practices.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 Field Hook-up Figure 2-1 on page 11 illustrates the wiring for a field hook-up with a Field Communicator or AMS. The Field Communicator or AMS may be connected at “COMM” on the transmitter terminal block.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.4.2 Configure Update Rate Fast Keys 2, 1, 2 The Update Rate is the frequency at which a new measurement is taken and transmitted over the wireless network. This by default is 1 minute. This may be changed at commissioning, or at any time via AMS Wireless Configurator.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 Review Configuration Data The following is a list of factory default configurations that can be viewed by using the Field Communicator or AMS. Follow the steps below to review the transmitter configuration information.
Page 26
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 Final Assembly Number Universal Field Device Software Hardware Descriptor Message Date Model Number I Model Number II Model Number III SI Unit Restriction Country Device ID Configuration...
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.5.3 Review Sensor Information Fast Keys 2, 2, 4, 4 To view sensor information: From the Home screen, select 2: Configure. Select 2: Manual Setup. Select 4: Device Information. Select 4: Sensor. Select from the corresponding number to view each field: Measurement Type Module Type...
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 Field Communicator 1. Join Device to Network 1. Network ID 1. Configure Update Rate 2. Configure Update Rate 2. Join Device to Network 1. Active Alerts 2. Message 1 3. Zero Trim 3.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 Check Output Before performing other transmitter operations, ensure that the transmitter is operating properly by checking the operating parameters. 2.7.1 Operating Parameters Fast Keys 3, 2 The pressure output value in both engineering units and percent of range will reflect the applied pressure even when the applied pressure is outside of the configured range as long as the applied pressure is between the upper and lower range limit of the transmitter.
Page 30
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 From the Home screen, select 2: Configure. Select 2: Manual Setup. Select 2: Pressure. Select 1: Unit to select from the following engineering units: torr inHg mbar ...
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.8.2 Set Transfer Function Fast Keys 2, 2, 2, 2 The 3051 Wireless has two output settings: Linear and Square Root. Activate the square root output option to make output proportional to flow. As input approaches zero, the 3051 Wireless automatically switches to linear output in order to ensure a more smooth, stable output near zero (see Figure...
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.8.3 Damping Fast Keys 2, 2, 2, 3 The Damping command introduces a delay in processing which increases the response time of the transmitter; smoothing variations in output readings caused by rapid input changes. In the 3051 Wireless pressure transmitter, damping only takes effect when the device is placed in high power refresh mode and during calibration.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 LCD Display 2.9.1 LCD Display Configuration Fast Keys 2, 1, 4 The LCD display indicates output and abbreviated diagnostic messages. Note Use Rosemount Wireless LCD Part Number: 00753-9004-0002. The LCD display features a four-line display and a bar graph. The first line of five characters displays the output description, the second line of seven digits displays the actual value, the third line of six characters displays engineering units and the fourth line displays “Error”...
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.10 Detailed Setup 2.10.1 Configure Process Alarms Fast Keys 2, 1, 5 Alerts allow the user to configure the transmitter to output a HART message when the configured data point is exceeded. A process alert will be transmitted continuously if the set points are exceeded and the alert mode is ON.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.10.2 Sensor Temperature Unit Fast Keys 2, 2, 3, 1, 1 The Sensor Temperature Unit command selects between Celsius and Fahrenheit units for the sensor temperature. The sensor temperature output is accessible via HART only. To select the sensor temperature unit: From the Home screen, select 2: Configure.
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 2.12 Advanced Functions for HART Protocol 2.12.1 Saving, Recalling, and Cloning Configuration Data Fast Keys left arrow, 1, 2 Use the cloning feature of the Field Communicator or the AMS “User Configuration” feature to configure several 3051 Wireless transmitters similarly.
Page 38
Reference Manual Section 2: Configuration 00809-0100-4100, Rev AA June 2012 When finished, the Field Communicator informs you of the status. Repeat Steps through configure another transmitter. Note The transmitter receiving cloned data must have the same software version (or later) as the original transmitter.
The information in this section covers installation considerations. A Quick Installation Guide (document number 00825-0100-4100) is shipped with every transmitter to describe basic installation and startup procedures. Dimensional drawings for each Rosemount 3051 Wireless variation and mounting configuration are included in Appendix A: Specifications and Reference Data.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 3.2.1 Warnings ( ) Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation. Explosions can result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Considerations 3.3.1 General Measurement performance depends upon proper installation of the transmitter and impulse piping. Mount the transmitter close to the process and use a minimum of piping to achieve best performance.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 3.3.4 Environmental Access requirements and cover installation on page 31 can help optimize transmitter performance. Mount the transmitter to minimize ambient temperature changes, vibration, mechanical shock, and to avoid external contact with corrosive materials. Appendix A: Specifications and Reference Data lists temperature operating limits.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Installation Procedures For dimensional drawing information refer to “Dimensional Drawings” on page Process Flange Orientation Mount the process flanges with sufficient clearance for process connections. For safety reasons, place the drain/vent valves so the process fluid is directed away from possible human contact when the vents are used.
Page 44
Alloy K-500 Head Marking Bolt Installation Only use bolts supplied with the Rosemount 3051 or sold by Emerson Process Management as spare parts. When installing the transmitter to one of the optional mounting brackets, torque the bolts to 125 in-lb. (0,9 N-m). Use the following bolt installation procedure: Finger-tighten the bolts.
Page 45
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Impulse Piping The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements. There are five possible sources of error: leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and density variations between the legs.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Mounting Requirements Refer to Figure 3.4.2 for examples of the following mounting configurations: Liquid Flow Measurement Place taps to the side of the line to prevent sediment deposits on the process isolators. ...
Page 47
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Failure to install proper flange adapter o-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique o-ring grooves. Only use the o-ring that is designed for its specific flange adapter, as shown below.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 3.4.3 Consider Housing Rotation The housing can be rotated to improve field access to wiring or to better view the optional LCD display. Perform the following procedure: Figure 3-3. Housing rotation A.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 3.4.5 Power Module Installation Figure 3-4. Power Module A. Housing rotation screw (5/64-inch hex wrench required) To make connections, perform the following procedure: Remove the housing cover on the Power Module compartment side. The Power Module supplies all power to the transmitter.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Remove the back cover and Power Module. Remove the transmitter cover opposite the field terminal side. Do not remove the instrument covers in explosive environments when the circuit is live. Engage the four-pin connector into the LCD display and snap into place.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Figure 3-6. Integral Manifold Designs 3.5.1 Rosemount 305 Integral Manifold Installation Procedure To install a 305 Integral Manifold to a 3051 Wireless transmitter: Inspect the Teflon sensor module O-rings. If the O-rings are undamaged, reusing them is recommended.
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Place transmitter into holding fixture. Apply appropriate thread paste or tape to threaded instrument end of the manifold. Count total threads on the manifold before starting assembly. Start turning the manifold by hand into the process connection on the transmitter. Note If using thread tape, be sure the thread tape does no strip when the manifold assembly is started.
Page 53
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 In normal operation the two block valves between the process and Drain/ instrument ports will be open and the Drain/ Vent Vent equalizing valve will be closed. Valve Valve Equalize (closed) Isolate Isolate...
Page 54
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Five-valve Natural Gas configurations shown: In normal operation, the two block valves between the process and instrument ports will be open, and the Test Test equalizing valves will be closed. (Plugged) (Plugged) Equalize...
Page 55
Reference Manual Section 3: Installation 00809-0100-4100, Rev AA June 2012 Open the equalize valve on the low pressure (downstream) side of the Test Test transmitter. The manifold is (Plugged) (Plugged) now in the proper Equalize Equalize configuration for zeroing the (open) (open) transmitter.
Note The Rosemount 3051 Wireless and all other wireless devices should be installed only after the Smart Wireless Gateway has been installed and is functioning properly. Wireless devices should also be powered up in order of proximity from the Smart Wireless Gateway, beginning with the closest device to the Smart Wireless GatewaySmart.
June 2012 Network Status If the Rosemount 3051 Wireless was configured with the Network ID and Join Key and sufficient time for network polling has passed, the transmitter should be connected to the network. To verify connectivity, open the Smart Wireless Gateway’s integral web interface and navigate to the Explorer page.
Page 61
Reference Manual Section 4: Commissioning 00809-0100-4100, Rev AA June 2012 Figure 4-1. Diagnostic Screen Sequence Network Join Device ID Network ID Status Device Status S u p l y i d - 1 2 n e t w k n e t w k A b c d e 7.
Reference Manual Section 4: Commissioning 00809-0100-4100, Rev AA June 2012 A green status indicator means that the device is working properly. A red indicator means that there is a problem with either the device or its communication path. For more detail on a specific device, click on the tag name.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Table 5-1. Recommended Calibration Tasks Transmitter Bench Calibration Tasks Field Calibration Tasks Set output configuration parameters: Reconfigure parameters if 3051CD 3051CG necessary. Set the range points. 3051L 3051TG, Range b.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Sensor trim is a two-point sensor calibration where two end-point pressures are applied, and all output is linearized between them. Always adjust the low trim value first to establish the correct offset.
5.2.5 Line Pressure Effect (Range 2 and Range 3) The following specifications show the static pressure effect for the Rosemount 3051 Range 2 and Range 3 pressure transmitters used in differential pressure applications where line pressure exceeds 2000 psi (138 bar).
Page 67
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Applying high static pressure to the 3051 Wireless Range 4 and Range 5 pressure transmitters causes a systematic shift in the output. This shift is linear with static pressure; correct it by performing the “Sensor Trim”...
Page 68
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 LT = LRV + S x (LRV) x P Where: LT = Corrected Low Trim Value LRV = Lower Range Value –(Span shift per specification) Static Line Pressure HT = URV + S x (URV) x P Where: HT =...
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 LCD Screen Messages 5.3.1 Startup Screen Sequence The following screens will display when the Power Module is first connected to the Rosemount 3051 Wireless. All Segments On: used to visually X X X X X determine if there are any bad X X X X x x x...
Page 70
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 S N S R SV Screen - sensor temperature 2 5. 0 0 value d e g c D E V TV Screen - device temperature 2 5. 2 5 value d e g c S u p l y...
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 5.3.2 Diagnostic Button Screen Sequence The following five screens will display when the device is operating properly and the Diagnostic Button has been pressed. Device Information - Tag: user A b c d e entered tag which is eight characters long - will not display if...
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Diagnostic Button Screen 5: S u p l y voltage reading at the power supply terminals 7. 2 1 v o l t s 5.3.3 Network Diagnostic Status Screens These screens display the network status of the device.
Page 73
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Diagnostic Button Screen 4.4: the device is in a n e t w k disconnected state and requires a “Force Join” command to join the network D I S C N T Diagnostic Button Screen 4.5: the device is N E T w K searching for the Network...
Page 74
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Diagnostic Button Screen 4.9: the device has joined n e t w k a network and has been fully configured and has multiple parents Operation and Maintenance...
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 5.3.4 Device Diagnostic Screens The following screens will show the device diagnostics depending on the state of the device. Device Information - Status: there is a critical error which may D E V prevent the device from operating correctly.
Page 76
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 S u p l y QV Screen - voltage reading at the 7. 2 1 power supply terminals v o l t s P R C N T Percent Range Screen - percent 7.
Page 77
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Diagnostic Button Screen 7.1: the terminal voltage has dropped s u p l y below level of operating limit. Replace the Power Module (Part Number: 701PGNKF) f a i l u r Diagnostic Button Screen 7.2: the terminal voltage is below the recommended operating range -...
Page 78
Reference Manual Section 5: Operation and Maintenance 00809-0100-4100, Rev AA June 2012 Diagnostic Button Screen 9.2: configuration of the transmitter is invalid such that non-critical operation of the device may be c o n f g affected - check the extended configuration status to identify which configuration item(s) need w a r n...
Electrical shock can result in death or serious injury. Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock. Table 6-1. Rosemount 3051 Wireless Device Status Information Device Status Description Recommended Action...
Page 81
Reference Manual Section 5: Troubleshooting 00809-0100-4100, Rev AA June 2012 Device Status Description Recommended Action Reset the device Electronics Warning The device has detected an electronics error that does not currently impact the device Reconfirm all configuration items in the device measurement reading.
Page 82
Reference Manual Section 6: Troubleshooting 00809-0100-4100, Rev AA June 2012 Device Status Description Recommended Action Verify that the process variable is within user HI Alarm The primary variable has surpassed the user defined limit. specified limits Reconfirm the user defined alarm limit If not needed, disable this alert Verify that the process variable is within user LO Alarm...
Page 83
Reference Manual Section 5: Troubleshooting 00809-0100-4100, Rev AA June 2012 Table 6-2. Rosemount 3051 Wireless Troubleshooting Symptom Recommended Actions Transmitter will not respond to changes in Check test equipment applied pressure Check impulse piping or manifold for blockage Verify applied pressure is within sensor limits...
Reference Manual Section 6: Troubleshooting 00809-0100-4100, Rev AA June 2012 Disassembly Procedures 6.3.1 Removing from Service Follow these steps: Follow all plant safety rules and procedures. Isolate and vent the process from the transmitter before removing the transmitter from service. Remove the transmitter from the process connection.
Reference Manual Section 5: Troubleshooting 00809-0100-4100, Rev AA June 2012 6.3.2 Removing the electronics board The Wireless electronics board is located in the electronics compartment. To remove the assembly, perform the following procedure. Remove the housing cover opposite the field terminal side. Remove the LCD Display, if applicable.
Reference Manual Section 6: Troubleshooting 00809-0100-4100, Rev AA June 2012 Figure 6-1. Sensor module connector view Wireless Housing 6.3.3 Removing the sensor from the housing Note To prevent damage to the senser module cable, disconnect it from the PlantWeb assembly before you remove the senser module from the housing.
Reference Manual Section 5: Troubleshooting 00809-0100-4100, Rev AA June 2012 Reassembly procedures Reassembly procedures Inspect all cover and housing (non-process wetted) O-rings and replace if necessary. Lightly grease with silicone lubricant to ensure a good seal. Carefully tuck the cable connector completely inside the internal black cap. To do so, turn the black cap and cable counterclockwise one rotation to tighten the cable.
Page 88
Reference Manual Section 6: Troubleshooting 00809-0100-4100, Rev AA June 2012 Note If you are replacing the o-rings, be careful not to scratch the o-ring grooves or the surface of the isolating diaphragm when removing the damaged o-rings. Install the process connection. Possible options include: Coplanar Process Flange: –...
Reference Manual Section 5: Troubleshooting 00809-0100-4100, Rev AA June 2012 6.5.3 Installing drain/vent valve Apply sealing tape to the threads on the seat. Starting at the base of the valve with the threaded end pointing toward the installer, apply five clockwise turns of sealing tape. Tighten the drain/vent valve to 250 in-lb.
Page 90
Reference Manual Section 6: Troubleshooting 00809-0100-4100, Rev AA June 2012 Troubleshooting...
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Appendix A Specifications and Reference Data Performance Specifications ..........page 79 Functional Specifications .
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 A.1.3 Reference Accuracy Models 3051 Standard Enhanced 3051 3051C Ranges 2-4 ±0.065% of span + 0.04% of span For spans less than 10:1, For spans less than 10:1 ...
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Ranges 2-3 ±1.60% of Flow Rate at 8:1 flow turndown 3051CFC Compact Orifice Flowmeter – Conditioning Option C Ranges 2-3 =0.4 ±1.75% of Flow Rate at 8:1 flow turndown ...
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 A.1.6 Long Term Stability Models Long Term Stability 3051C Ranges 2-5 ±0.125% of URL for 5 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure. 3051CD, 3051CG Low/Draft Range ±0.2% of URL for 1 year...
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA A.1.9 Ambient Temperature Effect per 50°F (28°C) Models Ambient Temperature Effect (for 3051 and enhanced 3051) 3051C Ranges 2-5 ±(0.0125% URL + 0.0625% span) from 1:1 to 5:1 ±(0.025% URL + 0.125% span) from 5:1 to 150:1 Range 1 ±(0.1% URL + 0.25% span) from 1:1 to 30:1...
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Functional Specifications A.2.1 Service Liquid, gas, and vapor applications. Specifications and Reference Data...
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA A.2.2 Range and Sensor Limits Table A-1. 3051CD, 3051CG, 3051CF, and 3051L range and sensor limits Minimum Span Range and Sensor Limits Lower (LRL) 3051CD 3051CD Differential 3051CG, Upper 3051CF...
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Wireless Self-Organizing Networks Output IEC 62591 (WirelessHART) 2.4 GHz DSSS Local Display The optional five-digit LCD can display user-selectable information such as primary variable in engineering units, percent of range, sensor module temperature, and electronics temperature. Display updates at up to once per minute.
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table A-3. 3051L and level flange rating limits Standard Type CS Rating SST Rating ANSI/ASME Class 150 285 psig 275 psig ANSI/ASME Class 300 740 psig 720 psig ANSI/ASME Class 600 1480 psig...
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table A-4. 3051 process temperature limits 3051CD, 3051CG, 3051CF, 3051CA Silicone Fill Sensor with Coplanar Flange –40 to 250 °F (–40 to 121 °C) (2)(3) with Traditional Flange –40 to 300 °F (–40 to 149 °C) with Level Flange –40 to 300 °F (–40 to 149 °C)
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Process Flanges and Adapters Plated carbon steel, SST cast CF-8M (cast version of 316 SST, material per ASTM-A743), C-Type cast alloy CW12MW, or cast alloy M30C Wetted O-rings Glass-filled PTFE or Graphite-filled PTFE A.4.3 Rosemount 3051L process wetted parts...
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Dimensional Drawings Dimensions are in inches (millimeters). Process adapters (option D2) and Rosemount 305 integral manifolds must be ordered with the transmitter 3051 Wireless Housing with In-Line and Coplanar SuperModule Platform Specifications and Reference Data...
Page 106
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table A-8. 3051L Dimensional Specifications Except where indicated, dimensions are in inches (millimeters). Flange Bolt Circle Outside Extension O.D. Pipe Thickness Diameter Diameter Bolt Hole Diameter Gasket Class Size Bolts...
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA A.5.1 Ordering Information A.5.2 Rosemount 3051C Coplanar Pressure Transmitter This ordering table contains the following Rosemount 3051C configurations: Configuration Transmitter Output Code ® 4-20 mA HART -3051 -Enhanced 3051 ™...
Page 108
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 1. 3051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 109
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 1. 3051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 110
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 1. 3051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 111
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 1. 3051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 (14)Not available with Alternate Process Connection; DIN Flanges and Level Flanges. Specifications and Reference Data...
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA A.5.3 Rosemount 3051T In-Line Pressure Transmitter This ordering table contains the following Rosemount 3051T configurations: Configuration Transmitter Output Code ® 4-20 mA HART -3051 -Enhanced 3051 ™ fieldbus OUNDATION Profibus...
Page 114
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 2. 3051T In-Line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 115
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 2. 3051T In-Line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 116
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 (7)Not available with Alloy C-276 isolator (3 code), tantalum isolator (5 code), all Cast Alloy C-276 flanges, all plated CS flanges, all DIN flanges, all Level flanges, assemble-to manifolds (S5 and S6 codes), assemble-to seals (S1 and S2 codes), assemble-to primary elements (S3 and S4 codes), surface finish certification (Q16 code), and remote seal system report (QZ code).
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA A.5.4 Rosemount 3051CF Flowmeter Series This ordering table contains the following Rosemount 3051CF configurations: Configuration Transmitter Output Code ® 4-20 mA HART -3051 -Enhanced 3051 ™ fieldbus OUNDATION Profibus (1)The enhanced 4-20 mA HART device can be ordered with Transmitter Output option code...
Page 118
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 119
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 120
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 121
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 122
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 123
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 124
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Additional Information Dimensional Drawings: 3 Rosemount 3051CFC Compact Flowmeter Table 4. Rosemount 3051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 125
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 4. Rosemount 3051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 126
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 4. Rosemount 3051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 127
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA (3)Not available with Primary Element Technology P. (4)Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limitsapply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
Page 128
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Rosemount 3051CFP Additional Information Integral Dimensional Drawings: page 93 Orifice Flowmeter Table 5. Rosemount 3051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 129
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 5. Rosemount 3051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 130
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 5. Rosemount 3051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 131
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 5. Rosemount 3051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 132
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 (6)Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA A.5.5 Rosemount 3051L Level Transmitter This ordering table contains the following Rosemount 3051L configurations: Configuration Transmitter Output Code ® 4-20 mA HART -3051 -Enhanced 3051 ™ fieldbus OUNDATION Profibus (1)The enhanced 4-20 mA HART device can be ordered with Transmitter Output option code...
Page 134
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 6. Rosemount 3051L Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 135
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 6. Rosemount 3051L Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 136
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 6. Rosemount 3051L Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Page 137
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Table 6. Rosemount 3051L Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Options Standard configuration Unless otherwise specified, transmitter is shipped as follows: Engineering units Differential/Gage: O (Range 0, 1, 2, and 3) psi (Range 4 and 5) Absolute/3051TA: psi (all ranges) Low Limit: 0 (engineering units above)
Page 139
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Other seals Refer to Product Data Sheet 00813-0100-4016 for additional information. Output information Output range points must be the same unit of measure. Available units of measure include: Pressure O@4 °C g/cm...
Page 140
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Austenitic 316 Stainless Steel Bolts ASTM A 193, Grade B7M Bolts Alloy K-500 Bolts Rosemount 3051C Coplanar Flange and 3051T bracket option Bracket for 2-in. Pipe or Panel Mounting For use with the standard Coplanar ...
Page 141
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Stainless Steel B1 Bracket with SST Bolts B1 bracket in stainless steel with Series 300 stainless steel bolts Stainless Steel B3 Bracket with SST Bolts B3 bracket in stainless steel with Series 300 stainless steel bolts ...
Page 142
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Table 9. Transmitter options weights Code Option lb (kg) J, K, L, M Stainless Steel Housing(T) 3.9 (1,8) J, K, L, M Stainless Steel Housing (C, L, H, P) 3.1 (1,4) LCD Display for Aluminum Housing 0.5 (0,2)
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Spare parts Silicone Fill Model 3051C Sensor Modules (Min. Span/Range) Part Number Note: One spare part is recommended for every 50 transmitters. Note: Listed by Range and Process Isolator Order Numbers. –3 to 3/0.1 inH2O, Range 0 (includes Traditional SST flange and SST bolts).
Page 144
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 –2000 to 2000/20 psi, Range 5 316L SST 03031-1045-2052 Alloy C-276 03031-1045-2053 Alloy 400 03031-1045-2054 Tantalum 03031-1045-2055 Gold-plated Alloy 400 03031-1045-2056 Gold-plated 316 SST 03031-1045-2057 Silicone fill Rosemount 3051C gage and differential sensor modules (Min.
Page 145
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Range 4 –14.2 to 300 psi/3 psi -300 to 300 psi/3 psi 316L SST 03031-1045-2042 Alloy C-276 03031-1045-2043 Alloy 400 03031-1045-2044 Tantalum 03031-1045-2045 Gold-plated Alloy 400 03031-1045-2046 Gold-plated 316 SST 03031-1045-2047 Range 5...
Page 146
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Range 4, 0 to 400 psia/40 psia 316L SST 03031-2020-0042 Alloy C-276 03031-2020-0043 Alloy 400 03031-2020-0044 Gold-plated Alloy 400 03031-2020-0046 Gold-plated 316 SST 03031-2020-0047 Silicone Fill Rosemount 3051T Sensor Modules (Min. Span/Range) Part Number Note: One spare part is recommended for every 50 transmitters.
Page 148
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Gage pressure range Range 1 0-0.3/30 psia Aluminum, 316L SST Isolator –18 NPT Female 03031-3112-3012 –14 NPT Female 03031-3102-1012 A DIN 16288 Male 03031-3132-3012 Aluminum, Alloy C-276 Isolator –18 NPT Female 03031-3112-3013 –14 NPT Female...
Page 149
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA SST, 316L SST Isolator –18 NPT Female 03031-3111-3032 –14 NPT Female 03031-3101-3032 SST, AlloyC-276 Isolator –18 NPT Female 03031-3111-3033 –14 NPT Female 03031-3101-3033 Range 4 0-40/4,000 psia Aluminum, 316L SST Isolator –18 NPT Female 03031-3112-3042...
Page 150
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 LCD Display Part number LCD Display for 3051 Wireless with Polymer Housing LCD Display for 3051 WirelessHART 03151-9010-0001 Electrical housings Part number Standard - Polymer Engineered Polymer Housing covers (include o-ring) Part number Wireless Battery Cover - Polymer...
Page 151
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Flange adapter kits (each kit contains parts for one DP transmitter or two GP/AP transmitters) Part number CS bolts, glass-filled PTFE O-Rings SST adapters 03031-1300-0002 Cast Alloy C-276 adapters 03031-1300-0003 Alloy 400 adapters 03031-1300-0004...
Page 152
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 O-Ring packages (package of 12) Part number Electronics housing, cover 03031-0232-0001 Electronics housing, module 03031-0233-0001 Process flange, glass-filled PTFE (White) 03031-0234-0001 Process flange, graphite-filled PTFE (Black) 03031-0234-0002 Flange adapter, glass-filled PTFE (Light Brown) 03031-0242-0001 Flange adapter, graphite-filled PTFE (Black)
Page 153
Appendix A: Specifications and Reference Data Reference Manual June 2012 00809-0100-4100, Rev AA Drain/Vent valve kits (each kit contains parts for one transmitter) Part number Differential Drain/Vent Kits 316 SST stem and seat kit 01151-0028-0022 Alloy C-276 stem and seat kit 01151-0028-0023 Alloy K-500 stem and Alloy 400 seat kit 01151-0028-0024...
Page 154
Reference Manual Appendix A: Specifications and Reference Data 00809-0100-4100, Rev AA June 2012 Specifications and Reference Data...
RF spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.
Reference Manual Appendix B: Product Certifications 00809-0100-4100, Rev AA June 2012 B.1.6 North American certifications Factory Mutual (FM) approvals FM Intrinsically Safe, Non-Incendive, and Dust Ignition-proof. Intrinsically Safe for Class I/II/III, Division 1, Groups A, B, C, D, E, F, and G. Zone Marking: Class I, Zone 0, AEx ia llC Temperature Codes T4 (T = -50 to 70 °C)
Reference Manual Appendix B: Product Certifications 00809-0100-4100, Rev AA June 2012 B.1.9 Japanese Certifications TIIS Intrinsic Safety Ex ia IIC T4 Certificate Description TC18649 2051_CD/CG/LD/LG TC18650 2051_CA/TA/TG/LA TC18657 2051FA/SFC/SFP B.1.10 China (NEPSI) Certifications China Intrinsic Safety Certificate No. (manufactured in Chanhassen, MN): GYJ081078 Certificate No.
Page 158
Reference Manual Appendix B: Product Certifications 00809-0100-4100, Rev AA June 2012 Product Certifications...
Page 160
June 2012 Standard Terms and Conditions of Sale can be found at www.rosemount.com/terms_of_sale The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount. the Rosemount logotype, and SMART FAMILY are registered trademarks of Rosemount Inc. Coplanar is a trademark of Rosemount Inc.