Set/Reset Operations - Siemens SIMATIC S5-100U System Manual

Simatic s5 series cpu 100/102/103
Hide thumbs Also See for SIMATIC S5-100U:
Table of Contents
S5-100U
8.1.2

Set/Reset Operations

Set/reset operations store the result of logic operation (RLO) formed in the processor. The stored
RLO represents the signal state of the addressed operand. Storage can be dynamic (assignment)
or static (set and reset). Table 8-2 provides an overview of the set/reset operations. Examples
follow the table.
Table 8-2. Overview of the Set/Reset Operations
Operation
Operand
S
R
=
ID
I
Q
F
EWA 4NEB 812 6120-02b
Set
The first time the program is scanned with RLO = "1", signal state
"1" is assigned to the addressed operand. An RLO change does
not affect this status.
Reset
The first time the program is scanned with RLO = "1", signal state
"0" is assigned to the addressed operand. An RLO change does
not affect this status.
Assign
Every time the program is scanned, the current RLO is assigned to
the addressed operand.
Parameter
CPU 100
0.0 to 127.7
0.0 to 127.7
0.0 to 127.7
STEP 5 Operations
Meaning
CPU 102
CPU 103
0.0 to 127.7
0.0 to 127.7
0.0 to 127.7
0.0 to 127.7
0.0 to 127.7
0.0 to 255.7
8-7