ABB i-bus KNX Product Manual

ABB i-bus KNX Product Manual

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Quick Links

®
ABB i-bus
KNX
DALI-Gateway Basic DG/S x.64.1.1
Product Manual
Table of Contents
loading

Summary of Contents for ABB i-bus KNX

  • Page 1 ® ABB i-bus DALI-Gateway Basic DG/S x.64.1.1 Product Manual...
  • Page 3: Table Of Contents

    Notes ............................5 Product and functional overview ....................6 1.2.1 Emergency lighting tests......................8 General information on DALI and standards................10 ® Comparison of ABB i-bus DALI gateways .................11 Device technology ................12 Technical data ..........................13 Connection diagram ........................15 Dimension drawing ........................16 Mounting and installation ......................17...
  • Page 4 ® ABB i-bus Contents Planning and application ..............213 DALI addressing ........................213 Lamp and ballast monitoring ....................214 Exchange of DALI devices ....................... 215 Function circuit diagrams and priorities..................216 DALI dimming curve......................... 219 4.5.1 DALI (logarithmic) curve ......................219 4.5.2...
  • Page 5: General

    General General ® This manual provides detailed technical information concerning the ABB i-bus KNX DALI Gateway Basic. These are DALI gateways which have identical functions but a different number of DALI outputs. They can be used to control a variety of DALI lamps individually or in groups on a DALI output via KNX. Lots of small groups in individual offices as well as large lights for area lighting can be combined in a gateway as required.
  • Page 6: Using The Product Manual

    ABB i-bus General Using the product manual ® This manual provides detailed technical information concerning the ABB i-bus DALI Gateways Basic and their installation and programming. Device application is explained using examples. This manual is divided into the following chapters:...
  • Page 7: Notes

    ® ABB i-bus General 1.1.2 Notes Notes and safety instructions are represented as follows in this manual: Note Tips for usage and operation Examples Application examples, installation examples, programming examples Important These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury.
  • Page 8: Product And Functional Overview

    The DALI power supply for the 64 DALI devices on each output is integrated in the gateway. DALI device readdressing and assignment to DALI groups is undertaken in ETS independent ABB i- ® Tool, so that for example, a facility manger without ETS knowledge is capable of exchanging and reassigning DALI devices if maintenance is required.
  • Page 9 ® ABB i-bus General The application program has a wide range of functions: • Switching, dimming, brightness value setting • Status signaling via common or separate group objects • Status signaling for a lamp and/or ballast malfunction • Programming of individual maximum brightness/minimal dimming values (dimming thresholds) •...
  • Page 10: Emergency Lighting Tests

    ® ABB i-bus General 1.2.1 Emergency lighting tests The DG/S x.64.1.1 acts as a gateway between self-contained emergency lighting systems and a KNX building automation system. This allows DALI-based emergency lighting to IEC 62386-202 to be controlled and monitored with a KNX control panel.
  • Page 11 ® ABB i-bus General Inhibit/rest mode Rest mode is a state in which the emergency light is switched off during its emergency lighting operation. Inhibit mode is a timed emergency lighting converter state in which the emergency light does not switch to emergency operation in the event of a mains voltage failure.
  • Page 12: General Information On Dali And Standards

    ® ABB i-bus General General information on DALI and standards The requirements for modern lighting technology are extremely varied. Historically, lighting was only required for visual tasks, but nowadays there is a focus on factors such as comfort, ambience, functionality and energy saving.
  • Page 13: Comparison Of Abb I-Bus ® Dali Gateways

    ® ABB i-bus General ® Comparison of ABB i-bus DALI gateways The differences between DALI gateways DG/S1.64.1.1 DALI-Gateway, Basic, 1-fold, MDRC and DG/S 2.64.1.1 DALI-Gateway, Basic, 2-fold, MDRC are described below. The differences are listed briefly in the table below. A detailed description can be found in the chapters that follow.
  • Page 14: Device Technology

    KNX building installation. The an energy-efficient building automation ® gateway connects to the ABB i-bus system via a KNX presence detector or a KNX connection terminal on the device light controller. shoulders.
  • Page 15: Technical Data

    ® ABB i-bus Device technology Technical data KNX DALI gateway DALI Single-Master Controller EN 62386 Parts 101ed2 and 103ed1 Supply Gateway supply voltage 100 – 240 V AC Voltage range 85…265 V AC, 50/60 Hz 110…240 V DC DG/S 1.64.1.1 DG/S 2.64.1.1...
  • Page 16 Note ETS and the current version of the device application program are required for programming. The current version of the application program is available for download at www.abb.com/knx. After import into ETS, it is available there under ABB/Illumination/DALI. The device does not support the locking function of a KNX device in ETS. Using a BCU code to inhibit access to all the project devices has no effect on this device.
  • Page 17: Connection Diagram

    ® ABB i-bus Device technology Connection diagram Label carrier KNX programming push button KNX programming LED (red) KNX connection Cover cap Gateway supply voltage DALI output (1 x DG/S 1.64.1.1, 2 x DG/S 2.64.1.1) Operation LED (green) Manual operation DALI status LED A / B (yellow) DALI devices (DALI device type 0 and 1) DG/S x.64.1.1 | 2CDC507164D0201 15...
  • Page 18: Dimension Drawing

    ® ABB i-bus Device technology Dimension drawing DG/S x.64.1.1 16 2CDC507164D0201 | DG/S x.64.1.1...
  • Page 19: Mounting And Installation

    ® ABB i-bus Device technology Mounting and installation The gateways are modular installation devices for installation in the distribution board on 35 mm mounting rails to EN 60715. They can be installed in any mounting position. Electrical connection is via screw terminals. Connection to the KNX is via the supplied KNX connection terminal.
  • Page 20 ® ABB i-bus Device technology Manual operation The gateways have a manual operation option to switch DALI lamps on and off at the outputs. However this excludes DALI single battery lamps, which cannot be manually operated. Supplied state The device is supplied with the physical address 15.15.255. The application program is preloaded.
  • Page 21: Description Of Inputs And Outputs

    The initialization phase will terminate if more than 64 DALI devices are connected and the information ® will be displayed by group objects on the KNX or in the ABB i-bus Tool. The initialization phase starts automatically after download, gateway supply voltage recovery and KNX bus voltage recovery.
  • Page 22: Manual Operation

    ® ABB i-bus Device technology Manual operation The device has one/two push buttons for manual switching of the DALI outputs. For manual operation to work properly, the KNX and the gateway must be supplied with power. Manual operation is mainly used to check that the wiring of the DALI line is correct and to detect faulty DALI devices which are not responding to broadcast commands.
  • Page 23 ® ABB i-bus Device technology Triggering DALI addressing via the push button: • Press push button for longer than five seconds. This will not exit the current mode but will trigger DALI addressing. The yellow DALI LED flashes. DALI devices without addresses are assigned the first free address.
  • Page 24: Display Elements

    ® ABB i-bus Device technology 2.6.1 Display elements On the front of the DALI gateway there is a green operation LED (ON) and a yellow DALI LED for each output. The LEDs indicate the following: DALI • Lights up green if the gateway supply voltage and KNX voltage is available and the device is ready for operation.
  • Page 25: Commissioning

    ETS and the gateway. This cuts programming time by more than half, particularly in the case of a full download. Corresponding system devices such as line couplers and interfaces must also support long frames. We recommend the ABB LK/S 4.2 Line Coupler, IPR/S 3.1.1 IP Router or IP Interface IPS/S 3.1.1 or later.
  • Page 26: Overview

    ® ABB i-bus Commissioning Overview In addition to the KNX voltage the KNX DALI gateway requires a gateway supply voltage to generate the DALI voltage for full function capability. For the gateway supply voltage range, please refer to Technical data, p. 13. The KNX voltage is sufficient for KNX programming with ETS.
  • Page 27 ® ABB i-bus Commissioning Parametrization options Em lighting Group Ballast converter Minimal dimming/maximum brightness values (dimming   thresholds) Switch functions   Turn on brightness   Dimming speed for turn on/off   Switch telegram and status Dimming ...
  • Page 28 ® ABB i-bus Commissioning Parametrization options continued Em lighting Group Ballast converter Other functions   Reaction on KNX voltage failure/recovery   Reaction on DALI voltage failure/recovery   Power-On level   Characteristic correction   Partial failure function ...
  • Page 29: Parameters

    ® ABB i-bus Commissioning Parameters This chapter describes the parameters of the KNX DALI Gateways DG/S x.64.1.1 using the parameter windows. The parameter windows feature a dynamic structure which means that further parameters or entire parameter windows are enabled depending on the parametrization and function of the groups.
  • Page 30: General Parameter Window

    ® ABB i-bus Commissioning 3.2.1 General parameter window Global parameter settings for the whole device are made in this window. Inactive wait state on KNX recovery Options: 2…255 s When in wait state, the gateway does not send any KNX telegrams. Incoming telegrams are received, and updated in the background.
  • Page 31 ® ABB i-bus Commissioning Limit number of KNX telegrams Options: This parameter limits the device generated bus load. This limit relates to all telegrams sent by the device. • Yes: Limits the number of telegrams. Selection of Yes option: Dependent parameters:...
  • Page 32 ® ABB i-bus Commissioning Enable manual operation. Obj "Disable manual operation/Status" Options: Linked group object: Disable manual operation/Status This parameter disables or enables the push button on the front of the DG/S. If manual operation is enabled, it can be disabled or enabled by the Disable manual operation/Status group object.
  • Page 33 ® ABB i-bus Commissioning Reset from manual operation to KNX operation Options: Via buttons and automatically Via push button These parameters define how and when the system exits manual operation. • Via buttons and automatically: You can exit manual mode by pressing (>...
  • Page 34 ® ABB i-bus Commissioning Enable Group object "In operation" Options: Linked group object: In operation The In operation group object indicates the presence of the DG/S on the KNX. This cyclic telegram can be monitored by an external device. If a telegram is not received, the device may be defective or the KNX cable to the transmitting device may be interrupted.
  • Page 35 ® ABB i-bus Commissioning Enable Group object "Request status values" Options: Linked group object: Request status values All status messages can be requested via this group object provided that they are set to After a change or on request or On request.
  • Page 36 ® ABB i-bus Commissioning Enable Group object "Gateway supply voltage fault" Options: Linked group object: Gateway supply voltage fault • Yes: The Gateway supply voltage fault group object is enabled. As soon as the device supply voltage is interrupted, the Gateway supply voltage fault group object sends a telegram with the value 1 on the KNX.
  • Page 37: Dali Output X Parameter Window

    If this DALI device does not yet have a group address (it is new from the factory), it will also receive the group assignment. If another group assignment exists in ® the DALI device, a conflict will be indicated in the ABB i-bus Tool. This can be remedied with the ®...
  • Page 38 ® ABB i-bus Commissioning • No: The DG/S does not assign DALI addresses, either in normal mode or on gateway supply voltage recovery. If a DALI device without an address has been installed, the DG/S can only control it using a broadcast telegram (manual operation).
  • Page 39 Yes: DALI group control is supported on the DALI output. Corresponding parameter windows and ® group objects are enabled. DALI groups are compiled with DALI devices via the ABB i-bus Tool. There are 16 DALI groups available per DALI output. Individual DALI groups can be selected in the Group x parameter window.
  • Page 40 Yes: Individual device control is supported on the DALI output. Corresponding parameter windows and ® group objects are enabled. DALI addressing can be flexibly handled in the ABB i-bus Tool. Up to 64 DALI devices can be connected to each output. Individual DALI devices can be hidden in the A ballasts parameter window to provide a clear, compact parameter structure.
  • Page 41 DALI addressing for the emergency lighting converters can be flexibly ® handled in the ABB i-bus Tool. Up to 64 DALI emergency lighting converters can be connected to each output. Individual DALI emergency lighting converters can be hidden in the A lighting converter parameter window to provide a clear, compact parameter structure.
  • Page 42: Output Parameter Window

    ® ABB i-bus Commissioning 3.2.3 X Output parameter window Parameter settings for the DALI output are made in this window. Note The DALI output is usually controlled by broadcast commands, i.e. a DALI command controls all the DALI devices at once. This requires no DALI device/group address.
  • Page 43 ® ABB i-bus Commissioning Name (max 40 characters) Options: Channel A The output can be assigned a name with a maximum of 40 characters. The name is stored in the ETS database, and also stored in the gateway by downloading the application.
  • Page 44 ® ABB i-bus Commissioning Dim period to reach turn on brightness Options: Fixed fade time Can be changed via object "Flexible time for dimming/fade time" This group object defines whether the dimming time can be changed via KNX. • Fixed fade time: Dimming time is permanently set and cannot be changed via the KNX.
  • Page 45 ® ABB i-bus Commissioning Note When setting dimming times of less than 32 seconds, note that they will be mapped to the nearest DALI fade time. The conversion is as follows: Turn on Fade time in s brightness acc. to EN 62386-102...
  • Page 46 ® ABB i-bus Commissioning Allow switching ON via brightness value (output Brightness value fct) Options: This parameter defines the output's behavior when switching on with a brightness value set via the Brightness value group object. • Yes: Switching on using the Brightness telegram is allowed.
  • Page 47 ® ABB i-bus Commissioning This parameter defines the brightness value for the Turn off brightness function, i.e. the brightness at which the output switches off when it receives an OFF telegram. Values set outside the thresholds (maximum brightness/minimal dimming value) are automatically adjusted to the maximum or minimum.
  • Page 48 ® ABB i-bus Commissioning Dim period to reach turn off brightness Options: Fixed fade time Can be changed via object "Flexible time for dimming/fade time" This group object defines whether the dimming time can be changed via KNX. • Fixed fade time: Dimming time is permanently set and cannot be changed via the KNX.
  • Page 49 ® ABB i-bus Commissioning Note When setting dimming times of less than 32 seconds, note that they will be mapped to the nearest DALI fade time. The conversion is as follows: Turn on Fade time in s brightness acc. to EN 62386-102...
  • Page 50 ® ABB i-bus Commissioning Allow switching off via dimming (output Relative dimming fct) Options: This parameter defines the behavior of the output when switching off during dimming. • Yes: Switch off using the Dim telegram is allowed. • No: Switch off using the Dim telegram is not allowed. The output dims to the minimal dimming value and stops there.
  • Page 51 ® ABB i-bus Commissioning Dim period to reach brightness value (output Brightness value fct) Options: Fixed fade time Can be changed via object "Flexible time for dimming/fade time" This group object defines whether the dimming time can be changed via KNX.
  • Page 52 ® ABB i-bus Commissioning Selection of Fixed fade time option: Dependent parameters: Dimming time (0 = jump to) Options: 0…2…65,535 s This parameter defines how long it takes to dim up to the set brightness value. This time only relates to the output's Brightness value telegram (8-bit).
  • Page 53 ® ABB i-bus Commissioning Dimming time for rel dimming 0...100% (Relative dimming fct) Options: 0.7 s 1.4 s … 5.7 s … 64 s 90.5 s This parameter defines the time in which a dimming process goes from 0...100%. This dimming time only affects dimming actions received via the Relative dimming group object.
  • Page 54: Output: State Parameter Window

    ® ABB i-bus Commissioning 3.2.3.1 X Output: State parameter window Settings for the status response of output X are made in this window. With the DG/S 2.64.1.1, the two DALI outputs are mutually independent and can each be parametrized differently.
  • Page 55 ® ABB i-bus Commissioning Enable Group object "Output x status byte" Options: Linked group object: Output X status byte This group object sends collective status signals to the output. • Yes: The (DALI output X) Status byte group object is enabled. It displays specific DALI output statuses, which can be helpful e.g.
  • Page 56 ® ABB i-bus Commissioning Enable Group object "Status switch" Options: Linked group object: Status switch • Yes: The (DALI output X) Status switch group object is enabled. It sends a 1-bit telegram on the KNX, signaling the current switch status.
  • Page 57 ® ABB i-bus Commissioning Enable Group object "Status brightness value" Options: Linked group object: Status brightness value The parameter defines how the current status of the DALI output brightness value is sent on the KNX. • Yes: The (DALI output X) Status brightness value group object is enabled for the brightness value.
  • Page 58 ® ABB i-bus Commissioning Value for different brightness states at DALI output Options: Average brightness of all lamps in the output Highest brightness of all lamps in the output Lowest brightness of all lamps in the output This parameter defines the status to be sent if DALI devices with different states are present on the output.
  • Page 59: Output: Fault Parameter Window

    ® ABB i-bus Commissioning 3.2.3.2 X Output: Fault parameter window This parameter window is used to define how output X reacts in the event of a fault. With the DG/S 2.64.1.1, the two DALI outputs are mutually independent and can each be parametrized differently.
  • Page 60 ® ABB i-bus Commissioning Acknowledge fault messages Enable Group object "Acknowledge fault messages/Status" Options: Linked group object: Acknowledge fault messages/Status This parameter enables the Acknowledge faults function and its required group object. • Yes: The Acknowledge faults function and its required group object are enabled.
  • Page 61 ® ABB i-bus Commissioning Enable Group object "Disable fault messages/Status" Options: Linked group object: Disable fault messages/Status This parameter enables the Disable fault messages/Status group object. At the same time, it makes the Disable fault messages function available. When messages are disabled, the faults are evaluated but not sent on the KNX.
  • Page 62 ® ABB i-bus Commissioning Enable Group object "DALI voltage fault" Options: Linked group object: DALI voltage fault This group object indicates a DALI voltage fault. The fault may be a surge, overload or short circuit. For more detailed information please see the Output X Status byte group object.
  • Page 63 ® ABB i-bus Commissioning Selection of Yes option: Dependent parameters: Send object value Options: On change On request After a change or on request • On change: The status is sent when a change occurs. • On request: The status is sent when a request occurs.
  • Page 64 ® ABB i-bus Commissioning Selection of Yes option: Dependent parameters: Send object value Options: On change On request After a change or on request • On change: The status is sent when a change occurs. • On request: The status is sent when a request occurs.
  • Page 65 ® ABB i-bus Commissioning Enable Group object "Number of faults statistic" Options: Linked group object: Number of faults statistic This group object consists of 4 bytes. The individual bytes contain the number of faults for the DALI output as a whole.
  • Page 66 ® ABB i-bus Commissioning Enable Group object "No of ballast faults" Options: Linked group object: Number of ballast faults • Yes: The group object is enabled. This group object indicates the number of faulty DALI devices on the output. In this case a fault means lamp or a ballast fault.
  • Page 67 ® ABB i-bus Commissioning Enable Group objects for additional fault message displays "Ballast number fault" "Switch up next ballast fault" Options: Linked group object: Ballast number fault Switch up next ballast fault This parameter enables two group objects. The first indicates the number of the faulty ballast. If there are several faults, the address of the next device with a fault can be displayed via the Switch up next ballast fault group object.
  • Page 68 ® ABB i-bus Commissioning Enable Group objects for additional fault message displays "Group number fault" "Switch up next group fault" Options: Linked group object: Group number fault Switch up next group fault • This parameter enables two group objects. The first indicates the number of the faulty group. If there are several faults, the address of the next group with a fault can be displayed via the Switch up next group fault group object.
  • Page 69: Output: Functions (Turn Off Brightness/Burn-In/Slave Offset/Partial Failure) Parameter Window

    ® ABB i-bus Commissioning 3.2.3.3 X Output: Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window Settings for output X (A and/or B) functions are made in this window. The functions have a priority order: • Forced operation/Block function • Partial failure function •...
  • Page 70 ® ABB i-bus Commissioning Enable Group object "Flexible time for dimming/fade time ..." Options: Linked group object: Flexible time for dimming/fade time ... This group object changes various dimming times via the KNX. It can affect various ballasts, groups and the output.
  • Page 71 ® ABB i-bus Commissioning • DALI format (1...15): The values received via the group object are interpreted by the gateway as a discreet numeric value, which is directly converted to the DALI value for the fade time. These values comply with the specified transition times according to the DALI standard. For example, the value 0 means immediate activation of the value, and 15 corresponds to 90.5...
  • Page 72 ® ABB i-bus Commissioning Enable Group object "Activate fct Turn off brightness" Options: Linked group object: Activate fct Turn off brightness On receipt of an OFF command from the Switch group object, the Turn off brightness function sets the lighting to a turn off brightness instead of switching it off (brightness value 0).
  • Page 73 ® ABB i-bus Commissioning Enable Group object "Rem burn-in time" Options: Linked group object: Rem burn-in time • Yes: The group object is enabled. It can send the remaining burn-in time for a group or ballast on the KNX. This is a coded group object which includes a ballast number and remaining burn-in time.
  • Page 74 ® ABB i-bus Commissioning Enable Group object "Burn-in lamps/Status" Options: Linked group object: Burn-in lamps/Status This parameter enables a group object which triggers burn-in for the whole output. However, burn-in must first be enabled in the ballast and group in the Functions parameter window. This group object also detects the burn-in status of the output provided at least one ballast is in burn-in mode, as this sets the status.
  • Page 75 ® ABB i-bus Commissioning Enable Group object "Slave offset/Status" Options: Linked group object: Activate Slave offset/Status • Yes: The group object is required in order to activate or deactivate the offset for the Slave function via the KNX. The group object affects all groups and ballasts on the output if they are set to Evaluate Group object "Activate Slave offset"...
  • Page 76 ® ABB i-bus Commissioning Enable function "Partial failure" Options: The Partial failure function allows lighting to be controlled regardless of a failed component. • Yes: The Partial failure function is enabled. Based on a defined number of failed lamps, other ballasts or groups can still be controlled via an external group object, Activate Partial failure/Status, or directly in the DALI output.
  • Page 77 ® ABB i-bus Commissioning Active em lighting event reported by em lighting converter Options: • Yes: An emergency lighting event will trigger the reaction to partial failure. The number of emergency lighting events is defined by the next parameter. •...
  • Page 78 ® ABB i-bus Commissioning Forward partial failure information The Partial failure function allows lighting to be controlled regardless of a failed component. The information can be forwarded internally or via an external group object. Internal to DALI output Options: •...
  • Page 79: Template Group X/Ballast X Parameter Window

    ® ABB i-bus Commissioning 3.2.4 X template group x/ballast x parameter window The group x/ballast x template parameter tab provides access to template parameter windows which can relate to any group or ballast on the DALI output. Whether they relate to the parametrization of a group or ballast in the template window or in an individual parameter window is selected when first parametrizing the groups or ballasts.
  • Page 80 ® ABB i-bus Commissioning Basic settings such as the dimming range and switching and dimming reaction of the DALI output or a group or ballast are made in this parameter window. Note References to a central telegram below mean a telegram received via one of the Output x group objects.
  • Page 81 ® ABB i-bus Commissioning Selected dimming curve Options: DALI (logarithmic) KNX (linear) The dimming curve is the basis for the logarithmic DALI characteristic. You can define whether the KNX setpoint and KNX status value refer to the DALI control value (x-axis) or luminous flux (y-axis).
  • Page 82 ® ABB i-bus Commissioning Maximum brightness value Options: 100% (255) 99% (252) … 1% (3) This parameter defines the maximum brightness value that the ballast or group can adopt. This value is stored in the DALI devices and thus applies for all functions. If a maximum brightness value is set which is below the minimal dimming value, the DG/S sets it to the minimum.
  • Page 83 ® ABB i-bus Commissioning Note The previous brightness value is saved with every OFF telegram unless the ballast, group or output is already switched off. If this is the case, the OFF state is not saved as the last brightness value on receipt of another OFF telegram.
  • Page 84 ® ABB i-bus Commissioning Dimming time (0 = jump to) Options: 0…2…65,535 s This parameter can be used to set a soft start by defining how long the output takes to dim up from 0% brightness to the turn on brightness when it receives an ON telegram. This time period refers to ON telegrams only (1 bit).
  • Page 85 ® ABB i-bus Commissioning Allow switch on via dimming (Relative dimming fct) Options: This parameter defines the ballast, group or output's behavior when switching on with dimming via the Relative dimming group object. • Yes: Switching on using the Dim telegram is allowed.
  • Page 86 ® ABB i-bus Commissioning Selection of Yes option: Dependent parameters Turn off brightness Options: 100% (255) 99% (252) … 30% (77) … 2% (5) 1% (3) This parameter defines the brightness value for the Turn off brightness function, i.e. the brightness at which the ballast, group or output switches off when it receives an OFF telegram.
  • Page 87 ® ABB i-bus Commissioning Note The Turn off brightness function can be applied to the whole DALI output, all ballasts and all groups. It must first be enabled in the X Output x functions parameter window along with the Activate fct Turn off brightness group object.
  • Page 88 ® ABB i-bus Commissioning Dimming time (0 = jump to) Options: 0…2…65,535 s This parameter can be used to set a soft stop. This defines how long it takes for the ballast or group to switch off from the current brightness on receipt of an OFF telegram. The dimming time still applies even if the Turn off brightness function is parametrized.
  • Page 89 ® ABB i-bus Commissioning Allow switching off via dimming (Relative dimming fct) Options: This parameter defines the behavior of the ballast or group when switching off during dimming. • Yes: Switch off using the Dim telegram is allowed. • No: Switch off using the Dim telegram is not allowed. The ballast or group dims to the minimal dimming value and stops there.
  • Page 90 ® ABB i-bus Commissioning Note Flexible dimming time is received via the Output x Flexible time for dimming/fade time group object and affects various output functions: • Dimming time for turn on/off value • Dimming time for brightness value •...
  • Page 91 ® ABB i-bus Commissioning Note When setting dimming times of less than 32 seconds, note that they will be mapped to the nearest DALI fade time. The conversion is as follows: Turn on Fade time in s brightness acc. to EN 62386-102...
  • Page 92: Status Template (Group X/Ballast X) Parameter Window

    ® ABB i-bus Commissioning 3.2.4.1 X Status template (group x/ballast x) parameter window This parameter window is a template for all ballasts or groups. If required, each ballast and group can also be individually parametrized. In this case, the parameter windows are the same as the template window but the parameter settings are applied to the individual ballast or group.
  • Page 93 ® ABB i-bus Commissioning Enable Group object "Status byte" Options: Linked group object: Output X status byte All ballast or group status messages can be requested via this group object provided that they have been set to After a change or on request or On request.
  • Page 94 ® ABB i-bus Commissioning Enable Group object "Status switch" Options: Linked group object: Status Switch • Yes: The (DALI output X) Status switch group object is enabled. It sends a 1-bit telegram on the KNX, signaling the current switch status.
  • Page 95 ® ABB i-bus Commissioning Enable Group object "Status brightness value" Options: Linked group object: Status brightness value The parameter defines how the current status of the DALI output brightness value is sent on the KNX. • Yes: The (DALI output x) Status brightness value group object is enabled for the brightness value.
  • Page 96 ® ABB i-bus Commissioning Send interim values on transfers (e.g. Dim up, scene transfer) Options: This parameter defines whether the brightness value status is only sent at the end of the brightness value transition or whether interim values are sent.
  • Page 97: Fault Template (Group X/Ballast X) Parameter Window

    ® ABB i-bus Commissioning 3.2.4.2 X Fault template (group x/ballast x) parameter window Settings for the reaction of the ballast or group to KNX/DALI voltage or gateway supply voltage failure and recovery are made in this parameter window. Note The minimal dimming value and maximum brightness value (dimming thresholds) set for the DALI devices in the Ballast x and Group x parameter windows apply as basic settings for the ballast.
  • Page 98 ® ABB i-bus Commissioning Brightness on ballast voltage recovery (DALI Power-On Level) Options: Current KNX value 100% (255) 99% (252) … 1% (3) 0% (OFF) This parameter determines the reaction of a ballast, or all the ballasts in a group, on ballast supply voltage recovery.
  • Page 99 ® ABB i-bus Commissioning Brightness on KNX or DALI voltage failure (DALI System Failure Level) Options: Maximum brightness value (100%) Min. brightness value (1%) No change This parameter defines how the ballast or group ballasts react if the gateway cannot communicate via the KNX due to a KNX voltage failure, or if there is a DALI voltage failure (e.g.
  • Page 100 ® ABB i-bus Commissioning Brightness on ballast recovery in operation Options: Actual KNX target state Maximum brightness value (100%) Min. brightness value (1%) No change This parameter defines how a failed ballast reacts if it is has already been detected by the gateway and does not respond (has failed) and is detected by the gateway again.
  • Page 101 ® ABB i-bus Commissioning Brightness on KNX bus voltage recovery and download Options: Last value before failure Maximum brightness value (100%) Min. brightness value (1%) No change This parameter defines how the ballast/group ballasts react after a download, on KNX bus voltage recovery, or after light controller supply voltage recovery.
  • Page 102 ® ABB i-bus Commissioning Enable Group object "Lamp/ballast fault" Options: Linked group object: Lamp/ballast fault This group object indicates a fault in the ballast or group. The fault type (lamp or ballast) is parametrizable. • Yes: The group object is enabled.
  • Page 103 ® ABB i-bus Commissioning Note To detect a ballast fault correctly the gateway needs to monitor all DALI devices. Monitoring can be triggered either via the Detect ballasts group object or via the commissioning tool ® (i-bus Tool). There is no automatic detection, e.g. after a KNX bus voltage recovery or gateway supply voltage recovery.
  • Page 104: Functions Template (Group X/Ballast X) (Forced Operation/Block/Burn-In/Partial Failure) Parameter Window

    ® ABB i-bus Commissioning 3.2.4.3 X Functions template (group x/ballast x) (Forced operation/Block/Burn-in/Partial failure) parameter window Settings for ballast and DALI group functions are made in this window. Enable function Forced operation/Block Options: Forced operation 1 bit Forced operation 2 bit...
  • Page 105 ® ABB i-bus Commissioning Note Note that it is not possible to use broadcast commands when individual DALI devices or groups are subject to a forced operation or block, or are in active partial failure state, as these safety functions take priority over broadcast commands.
  • Page 106 ® ABB i-bus Commissioning Value Bit 1 Bit 0 Status Description If the Forced operation group object receives a telegram with the value 0 Enabled (binary 00) or 1 (binary 01), the group/ballast is enabled and can be controlled via various group objects.
  • Page 107 ® ABB i-bus Commissioning Selection of Forced operation 1 bit: Dependent parameters: Brightness value when switched on by force Options: 100% (255) 99% (252) … 1% (3) 0% (OFF) This parameter defines the brightness value used to switch on the ballast or group during activated forced operation.
  • Page 108 ® ABB i-bus Commissioning When Forced operation ends, the brightness value updated in the background is set. The ballast or group returns to the state it was in before forced operation. If an additional function was active, e.g. Staircase lighting or Slave, it will also be active after Forced operation. If the Staircase lighting function was activated before Forced operation, it goes into standby when Forced operation/Block is removed.
  • Page 109 ® ABB i-bus Commissioning Disable state on KNX bus voltage recovery Options: Not disabled Disabled State before KNX voltage failure This parameter defines the disable state after a KNX bus voltage recovery • Not disabled: The ballast/group is enabled after KNX bus voltage recovery and is no longer subject to the Block.
  • Page 110 ® ABB i-bus Commissioning Enable Lamp burn-in function object "Burn-in lamps" Options: Linked group object: Burn-in lamp This parameter enables the Burn-in function for a ballast or group. The function itself can be activated by ballast or group via the ballast x/group x Burn-in lamp group object, or for all ballast/groups together via the Output x group object Burn-in lamp/Status.
  • Page 111 ® ABB i-bus Commissioning Lamp burn-in time in hours [1…255] Options: 1…100…255 This parameter defines the time period for the Burn-in function. Until this time has elapsed, the ballast/group can only be operated at 100% and OFF on the DALI output, i.e. at every set brightness value other than 0%, the lamp is switched on at 100% brightness.
  • Page 112 ® ABB i-bus Commissioning Status of burn-in Options: Linked group object: Burn-in lamp/Status The gateway features an option to send the status of the Burn-in function on the KNX with the Burn-in lamp/Status group object. • No: No status message is sent for the Burn-in function.
  • Page 113 ® ABB i-bus Commissioning Factor in function Partial failure Options: • Yes: The Reaction on partial failure function is taken into account for the ballast or group. • No: The Reaction on partial failure function is not taken into account for the ballast or group.
  • Page 114: Slave Template (Group X/Ballast X) Parameter Window

    Using the Slave function, each individual group on the gateway can be integrated into constant lighting ® control implemented for example by an ABB i-bus light controller or KNX presence detector as a master. The operating state of the slave after a download or KNX bus voltage recovery can be parametrized.
  • Page 115 ® ABB i-bus Commissioning Note If the gateway receives a central switch, relative dimming or Brightness value telegram via a group object for the DALI output while Slave mode is running, the telegram is executed. The slave goes to standby. To respond to the master again the group has to receive an ON telegram via the Switch group object or be reactivated by the Activate fct Slave group object.
  • Page 116 ® ABB i-bus Commissioning Note Flexible dimming time is received via the Output x Flexible time for dimming/fade time group object and affects various output functions: • Dimming time for turn on/off value • Dimming time for brightness value •...
  • Page 117 ® ABB i-bus Commissioning Dimming time (0 = jump to) Options: 0…2…65,535 s This parameter defines the transition between the current and slave brightness, by setting how long it takes for the slave to dim to slave brightness. • 0 s: Jump to. The output immediately switches to the slave brightness value.
  • Page 118 ® ABB i-bus Commissioning Offset between slave and master Options: A brightness offset can be factored in between the master and slave. • Yes: An offset from the specified master brightness is taken into account for the slave. The Activate offset group object is also enabled.
  • Page 119 ® ABB i-bus Commissioning Evaluate Group object "Activate Slave offset" Enable object on "Output functions" page Options: • No: The Slave offset function is always active. • Yes: The Slave offset function can be activated/deactivated via the group object for the output.
  • Page 120 ® ABB i-bus Commissioning With active additional function. Reaction on..Switch on Options: No reaction Function switches to standby When the Slave function is activated, this parameter defines the reaction to an ON telegram on the Switch group object. •...
  • Page 121 ® ABB i-bus Commissioning ...Brightness value Options: No reaction Function switches to standby When the Slave function is activated, this parameter defines the reaction to a Brightness value telegram on the Brightness value group object. • No reaction: A Brightness value telegram is ignored.
  • Page 122 ® ABB i-bus Commissioning Reaction on KNX bus voltage recovery and download Options: Not activated Activated and in standby Activate and ON State before failure This parameter defines the state of the Slave function after a KNX bus voltage recovery or a download.
  • Page 123 ® ABB i-bus Commissioning Send status via object "Activate fct Slave/Status" Options: Linked group object: Activate fct Slave/Status • No: The status of the Activate Slave function is not transmitted on the KNX. • Yes: The Activate fct Slave/Status group object does not just activate or deactivate the Slave function.
  • Page 124: Staircase Lighting Template (Group X/Ballast X) Parameter Window

    ® ABB i-bus Commissioning 3.2.4.5 X Staircase lighting template (group x/ballast x) parameter window This parameter window is enabled if the Enable additional function parameter in X groups or X ballasts p. 77 is set to Staircase lighting. 122 2CDC507164D0201 | DG/S x.64.1.1...
  • Page 125 ® ABB i-bus Commissioning The gateway has a Staircase lighting function which can trigger or stop individual groups or ballasts via individual Switch telegrams. As the function and the parameter window for the group and the ballast are identical, only the group is referred to below.
  • Page 126 ® ABB i-bus Commissioning Brightness value of staircase lighting Options: 100% (255) 99% (252) … 1% (3) 0% (0) This parameter defines brightness when the Staircase lighting function is running. This is the brightness value which is set after a dimming up phase and before dimming down (advance warning phase).
  • Page 127 ® ABB i-bus Commissioning Staircase lighting time Options: 0…300…65,535 s This parameter sets the staircase lighting time, i.e. how long the group is controlled with the staircase lighting brightness. The dimming up and dimming down times are not included. •...
  • Page 128 ® ABB i-bus Commissioning Note When setting dimming times of less than 32 seconds, note that they will be mapped to the nearest DALI fade time. The conversion is as follows: Turn on Fade time in s brightness acc. to EN 62386-102...
  • Page 129 ® ABB i-bus Commissioning Dim period to reach basic brightness Options: 0…2…65,535 s This parameter is used to set a dimming transition to the basic brightness for the staircase lighting. Note When setting dimming times of less than 32 seconds, note that they will be mapped to the nearest DALI fade time.
  • Page 130 ® ABB i-bus Commissioning Extend staircase lighting on repeated switch on Options: Yes - restart staircase lighting time (retrigger) Yes - Extend staircase lighting time up to max 2 x (pumping up) Yes - Extend staircase lighting time up to max 3 x (pumping up)
  • Page 131 ® ABB i-bus Commissioning Factor in turn off brightness when switching off Enable par. "Switch off at turn off brightness" on "Group x/ballast x" Options: Turn off brightness can be activated/deactivated via the KNX using the Activate fct Turn off brightness group object.
  • Page 132 ® ABB i-bus Commissioning Note The Turn off brightness function can be applied to the whole DALI output, all ballasts and all groups. It must first be enabled in the X Output x functions parameter window along with Activate fct Turn off brightness group object.
  • Page 133 ® ABB i-bus Commissioning ...Recall scene Options: No reaction Function switches to standby When the Slave function is activated, this parameter defines the reaction to a scene recall. • No reaction: A scene recall is ignored. • Function switches to standby: A scene recall ends the Staircase lighting function; the group executes the recall.
  • Page 134 ® ABB i-bus Commissioning Reaction on activation via object "Activate fct Staircase lighting" Options: Activated and in standby Activate and ON This parameter defines the state of the Staircase lighting function after it has been activated by the Activate fct Staircase lighting group object.
  • Page 135 ® ABB i-bus Commissioning Send status via object "Activate fct Staircase lighting/Status" Options: Linked group object: Activate fct Staircase lighting/Status • No: The status of the Activate staircase lighting function is not transmitted on the KNX. • Yes: The Activate fct Staircase lighting/Status group object does not just activate or deactivate the Staircase lighting function.
  • Page 136: Groups Or X Ballasts Parameter Window

    ® ABB i-bus Commissioning 3.2.5 X groups or X ballasts parameter window This window is where groups or ballasts are enabled for use on the DALI output. As a group and a ballast are equivalents on the DALI output, they have the same functions and parameter windows. The group parameter window and its properties are described below.
  • Page 137 ® ABB i-bus Commissioning Selection of Yes option: Dependent parameter window: x groups Group x parameter window Name (max 40 characters) Options: Each group or ballast can be assigned a name consisting of up to 40 characters. The name is stored in the ETS database, and also stored in the gateway by downloading the ®...
  • Page 138 ® ABB i-bus Commissioning Enable additional function Options: None Slave Staircase lighting Linked group object: Activate fct Slave Activate fct Staircase lighting This parameter defines an additional function for the group or ballast. At the same time, it enables a corresponding parameter window where the additional function can be parametrized.
  • Page 139 ® ABB i-bus Commissioning Note The additional functions Slave and Staircase lighting can adopt three operating states: Additional function is not active: The additional function has been deactivated via a telegram with value 0 received on the function's Enable additional function group object. In this state, the group/ballast behaves normally.
  • Page 140 ® ABB i-bus Commissioning Note The advantages of using the template for parametrization are: • A clearly organized, compact ETS parameter interface (one template parameter window rather than 64 individual ones) • All groups and ballasts react in the same way (the same properties apply to all groups/ballasts, e.g.
  • Page 141: Groups/Group X Or X Ballasts/Ballast X / Status Parameter Window

    ® ABB i-bus Commissioning 3.2.5.1 X groups/Group x or X ballasts/Ballast x / status parameter window Settings for the status response of the ballast or group are made in this parameter window. Users can choose to parametrize the Status function individually by group/ballast or to adopt the parameters from the Status template.
  • Page 142: Groups/Group X Or X Ballasts/Ballast X / Fault Parameter Window

    ® ABB i-bus Commissioning 3.2.5.2 X groups/Group x or X ballasts/Ballast x / fault parameter window Settings for the reaction of the ballast or group to KNX/DALI voltage or gateway supply voltage failure and recovery are made in this parameter window.
  • Page 143 ® ABB i-bus Commissioning Parameter settings Options: Individual Apply from template This parameter defines whether the group/ballast settings are taken from the template or individually set. • Individual: The group/ballast is individually parametrized. Corresponding parameters for the group/ballast are shown. The content of the individual parameters is the same as that in the Fault template parameters.
  • Page 144: Groups/Group X Or X Ballasts//Ballast X / Functions (Forced Operation/Block/Burn-In/Partial Failure) Parameter Window

    ® ABB i-bus Commissioning 3.2.5.3 X groups/Group x or X ballasts//ballast x / functions (Forced operation/Block/Burn-in/Partial failure) parameter window Settings for ballast and group functions are made in this window. Users can choose to parametrize the Functions function individually by group/ballast or to adopt the parameters from the Functions template.
  • Page 145 ® ABB i-bus Commissioning Parameter settings Options: Individual Apply from template This parameter defines whether the group/ballast settings are taken from the template or individually set. • Individual: The group/ballast is individually parametrized. Corresponding parameters for the group/ballast are shown. The content of the individual parameters is the same as that in the Functions template parameters.
  • Page 146: Groups/Group X Or X Ballasts/Ballast X / Slave Parameter Window

    ® ABB i-bus Commissioning 3.2.5.4 X groups/Group x or X ballasts/Ballast x / slave parameter window This parameter window is visible if the additional function Slave has been enabled in X Slave template (group x/ballast x) parameter window, p. 112.
  • Page 147 ® ABB i-bus Commissioning Source (slave is controlled via) Options: Object "slave brightness value" Group 1 … Group 16 Ballast 1 … Ballast 64 This parameter defines whether the Slave receives its brightness value via the Brightness value of slave group object via KNX from another KNX device (e.g.
  • Page 148 ® ABB i-bus Commissioning Note Note that any ballast or group number can be used as a master. Programmers must ensure that the group or ballast is correctly connected to the output. If a ballast is assigned to a DALI group, it cannot be individually controlled and therefore nor can it be used as a master.
  • Page 149: Groups/Group X Or X Ballasts/Ballast X / Staircase Lighting Parameter Window

    ® ABB i-bus Commissioning 3.2.5.5 X groups/Group x or X ballasts/Ballast x / staircase lighting parameter window This parameter window is visible if the additional function Staircase lighting has been enabled in X Staircase lighting template (group x/ballast x) parameter window, p. 122.
  • Page 150 ® ABB i-bus Commissioning Parameter settings Options: Individual Apply from template This parameter defines whether the group/ballast settings are taken from the template or individually set. • Individual: The group/ballast is individually parametrized. Corresponding parameters for the group/ballast are shown. The content of the individual parameters is the same as that in the group x/ballast x template parameters.
  • Page 151: Lighting Converter Parameter Window

    ® ABB i-bus Commissioning 3.2.6 X lighting converter parameter window This window is where the emergency lighting converters are enabled for use on the DALI output. It is also used to set the emergency lighting properties and tests which affect all the emergency lighting converters on the output.
  • Page 152 ® ABB i-bus Commissioning Allow emergency lighting tests (em lighting converters must support this) Options: • Yes: The automatic emergency lighting test function is enabled. In the Emergency light x parameter window for each emergency lighting converter you can define whether that converter is included in the test.
  • Page 153 ® ABB i-bus Commissioning Enable fct Automatic emergency lighting test Object "Synch auto emergency lighting tests" Options: Linked group object: Synchronize auto emergency lighting tests • Yes: The gateway sends the start request for the automatic emergency lighting test to the emergency lighting converter.
  • Page 154 ® ABB i-bus Commissioning Danger In both cases, the emergency light no longer fulfils its safety function and remains off. For this reason, use this function with great care. It can be helpful to use Inhibit/rest mode during the construction phase when the power supply is often switched off, to prevent the emergency lighting battery from constantly charging/discharging and thus conserve the emergency light.
  • Page 155 ® ABB i-bus Commissioning Enable addressed Group objects "Trigger em lighting test (addr)" Options: Yes, KNX format DPT_CTC Yes, DGN/S1.16.1 format Linked group object: Trigger em lighting test addr (CTC) Trigger em lighting test addr (DGN/S) • No: No addressed group object for the output is enabled to start an emergency lighting test.
  • Page 156 ® ABB i-bus Commissioning "Em lighting test result (addr)" Options: Linked group object: Em lighting test result (addr) (2 byte) • Yes: The Em lighting test status (addr) group object is enabled. This sends the test result for the emergency lighting test on the KNX.
  • Page 157: Lighting Converter/Emergency Light Template Parameter Window

    ® ABB i-bus Commissioning 3.2.6.1 X lighting converter/Emergency light template parameter window This parameter window is enabled if the Enable DALI emergency lighting converter parameter is set to Yes in the X DALI configuration parameter window. The template window has a major advantage in that the settings made here relate to all emergency lighting converters, so each converter on the DALI output reacts in the same way.
  • Page 158 ® ABB i-bus Commissioning Brightness value in emergency mode Options: 100% (255) 99% (252) … 1% (3) This parameter defines the brightness value adopted in emergency mode. The value set by this parameter is stored in the emergency lighting converter and therefore remains available even if there is no connection to the gateway.
  • Page 159 ® ABB i-bus Commissioning Prolong Time at end of emergency lighting operation Options: 0…127 min This parameter defines in minutes how long the emergency light remains on at this brightness value when emergency mode ends, before it is re-enabled for KNX telegrams.
  • Page 160 ® ABB i-bus Commissioning Automatically calculate period of partial duration test with rated time Options: The period for the partial duration test is independent of whether the test is triggered automatically, or manually via a group object. • Yes: The gateway reads the rated duration of the battery from the emergency lighting converter and uses this to calculate how long the partial duration test should run for (test time = 10% of rated duration).
  • Page 161 ® ABB i-bus Commissioning Emergency lighting converter reacts on object "Inhibit/rest mode" Options: • Yes: The Activate emergency lighting Inhibit/rest mode group object is evaluated so that the emergency lighting converter receives the rest/inhibit command via the gateway. This means it is possible to deactivate the emergency lighting function so as to conserve the battery charge e.g.
  • Page 162 ® ABB i-bus Commissioning Automatic emergency lighting test Note The automatic emergency lighting test (test sequence) is an optional function of the DALI standard for emergency lighting converters to EN 62386-202. Therefore, check in advance whether the emergency lighting converter has the capability to run an automatic test. Otherwise the test can only be triggered via the higher-level controller.
  • Page 163 ® ABB i-bus Commissioning Include in automatic duration/partial duration test Options: • Yes: The emergency lighting converter runs the automatic duration/partial duration test. The cycle time for repeating the test can be set in the next parameter. • No: The emergency lighting converter does not run any automatic duration/partial duration tests.
  • Page 164 ® ABB i-bus Commissioning Selection of Duration and partial duration test: Dependent parameters: Duration test every n tests Options: 2…12…100 With alternating duration and partial duration tests, this parameter defines how often the test is a duration test. There are three parameters below which can be used to enable group objects for each emergency lighting converter;...
  • Page 165 ® ABB i-bus Commissioning Selection of Yes, DGN/S1.16.1 format with status: Dependent parameters: Send object value Options: On change On request After a change or on request • On change: The status is sent when a change occurs. • On request: The status is sent when a request occurs.
  • Page 166 ® ABB i-bus Commissioning "Emergency lighting converter status" Options: Linked group object: "Emergency lighting converter status" (2 byte) • Yes: The Emergency lighting converter status group object is enabled. This sends the status of the emergency lighting converter on the KNX.
  • Page 167: Lighting Converter/Emergency Light X Parameter Window

    ® ABB i-bus Commissioning 3.2.6.2 X lighting converter/Emergency light x parameter window Settings for an emergency lighting converter test on emergency lights with individual batteries are made in this window. Tests are automatically triggered by the converter, or by a higher level controller via the KNX and the gateway.
  • Page 168: Scenes Parameter Window

    ® ABB i-bus Commissioning 3.2.7 X scenes parameter window The DALI gateway has 16 scenes per output. These correspond to DALI scenes. Each scene can be assigned to any ballasts and/or groups on the output. These are referred to as scene members below.
  • Page 169 ® ABB i-bus Commissioning DALI scene x: KNX scene number Options: 1…64 Scene not in use Linked parameter window: X scenes/Scene x This parameter links a DALI scene to a KNX scene. This allows all 64 possible KNX scene numbers to be used for the 16 DALI scenes.
  • Page 170: Scenes/Scene X Parameter Window

    ® ABB i-bus Commissioning 3.2.7.1 X scenes/Scene x parameter window This parameter window is visible if DALI scene x is assigned to a KNX scene in the X scenes parameter window. The properties of the scenes and their members are parametrized in this window. A scene member can be any ballast or group on the DALI output.
  • Page 171 ® ABB i-bus Commissioning • Jump to: When a scene is recalled, the scene members are switched on immediately at the set brightness value of the scene. • 0.7 s…90.5 s: When a scene is recalled, all the lighting scene members are dimmed from their current brightness value to the set brightness value within this time.
  • Page 172 ® ABB i-bus Commissioning Note Even if the scene values are not overwritten after a download, the scene members have to be selected in order to tell the gateway which ballasts or groups are members of the scene. Note When a download occurs, the parametrized scene values are usually transferred to the gateway. Note that if no change has been made in the ETS application, ETS does not transfer these values again when a partial ETS download occurs.
  • Page 173: Group Objects

    ® ABB i-bus Commissioning Group objects This chapter covers the group objects featured in the DALI Gateway DG/S 1.64.1.1 and DG/S 2.64.1.1. As the DALI outputs and their functions, parameters and group objects are identical, only DALI output A is described below.
  • Page 174: Summary Of Group Objects

    ® ABB i-bus Commissioning 3.3.1 Summary of group objects Datapoint Flags Function Name Type Length (DPT) In operation General 1.002 1 bit Disable manual operation/Status General 1.003 1 bit Gateway supply voltage fault General 1.005 1 bit Acknowledge gateway supply voltage fault General 1.015...
  • Page 175 ® ABB i-bus Commissioning Datapoint Flags Function Name Type Length (DPT) 1153 Synchronize auto emergency lighting tests Output A 1.010 1 bit Trigger em lighting test addr (DGN/S) Output A Non DPT 2 byte 1154 Trigger em lighting test (addr)
  • Page 176 ® ABB i-bus Commissioning Datapoint Flags Function Name Type Length (DPT) 230, 1344 Lamp/ballast fault Output A - Ballast x 1.005 1 bit 1355 … Forced operation 1 bit Output A - Ballast x 1.003 1 bit 231, 1345 Forced operation 2 bit Output A - Ballast x 2.001...
  • Page 177: Group Objects General

    ® ABB i-bus Commissioning 3.3.2 Group objects General Function Group object name Data type Flags In operation General 1 bit C, R, T DPT 1.002 Dependent on parameter Enable Group object "In operation" This group object is enabled if the Enable Group object "In operation" parameter is set to Yes in the General parameter window, p.28.
  • Page 178 ® ABB i-bus Commissioning Function Group object name Data type Flags Request status values General 1 bit C, W DPT 1.017 Dependent on parameter Enable Group object "Request status values" This group object is enabled if the Request status values parameter is set to Yes in the General parameter window, p. 28.
  • Page 179: Output A Group Objects

    ® ABB i-bus Commissioning 3.3.3 Output A group objects This section describes the group objects for DALI output A. The same objects are available on the second output of the 2-fold DALI Gateway DG/S 2.64.1.1, but named accordingly as output B objects.
  • Page 180 ® ABB i-bus Commissioning Function Group object name Data type Flags Trigger DALI addressing Output A 1 bit C, W DPT 1.003 Dependent on parameter None This group object is always enabled. If the gateway receives a telegram with the value 1 on this group object, one-time DALI addressing is triggered. All DALI devices without a DALI address receive one.
  • Page 181 ® ABB i-bus Commissioning Function Group object name Data type Flags Flexible time for dimming/fade time Output A 1 byte C, W (DALI format (0…15)) DPT 20.602 Dependent on parameter Object format of flexible time for dimming/fade time This group object is enabled if the Enable Group object "Flexible time for dimming/fade time..." parameter is set to Yes in the X Output: Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window, p.
  • Page 182 ® ABB i-bus Commissioning Function Group object name Data type Flags Flexible time for dimming/fade time Output A 2 byte C, W (time 100 ms) DPT 7.004 Dependent on parameter Object format of flexible time for dimming/fade time This group object is enabled if the Enable Group object "Flexible time for dimming/fade time..." parameter is set to Yes in the X Output: Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window, p.
  • Page 183 ® ABB i-bus Commissioning Function Group object name Data type Flags Flexible time for dimming/fade time Output A 2 byte C, W (time 1s) DPT 7.002 Dependent on parameter Object format of flexible time for dimming/fade time This group object is enabled if the Enable Group object "Flexible time for dimming/fade time..." parameter is set to Yes in the X Output: Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window, p.
  • Page 184 ® ABB i-bus Commissioning Function Group object name Data type Flags Switch Output A 1 bit C, W DPT 1.001 Dependent on parameter None This group object switches all the DALI devices connected to the DALI output on or off at the brightness values defined in the X Output parameter window, p.
  • Page 185 ® ABB i-bus Commissioning Function Group object name Data type Flags Relative dimming Output A 4 bit C, W DPT 3.007 Dependent on parameter None The Relative dimming telegram for all DALI devices connected to the DALI output is received via this group object. These are BRIGHTER, DARKER and STOP telegrams.
  • Page 186 ® ABB i-bus Commissioning Function Group object name Data type Flags Status switch addressed Output A 2 byte C, R, T non DPT Dependent on parameter Enable Group object "Status switch addressed" This group object is enabled if the Enable Group object "Status switch addressed" parameter is set to Yes in the X Output: State parameter window, p.
  • Page 187 ® ABB i-bus Commissioning Function Group object name Data type Flags Status brightness addressed Output A 2 byte C, R, T non DPT Dependent on parameter Enable Group object "Status brightness addressed" This group object is enabled if the Enable Group object "Status brightness addressed" parameter is set to Yes in the X Output: State parameter window, p.
  • Page 188 ® ABB i-bus Commissioning Function Group object name Data type Flags Lamp fault Output A 1 bit C, R, T DPT 1.005 Dependent on parameter Enable Group object "Lamp fault" This group object is enabled if the Enable Group object "Lamp fault" parameter is set to Yes in the X Output: Fault parameter window, p.
  • Page 189 ® ABB i-bus Commissioning Function Group object name Data type Flags Fault addressed Output A 2 byte C, R, W, T 237,600 Dependent on parameter Enable Group object "Fault addressed" This group object is enabled if the Enable Group object "Fault addressed" parameter is set to Yes in the X Output: Fault parameter window, p.
  • Page 190 ® ABB i-bus Commissioning Function Group object name Data type Flags Number of faults statistic Output A 4 byte C, R, T Non DPT Dependent on parameter Enable Group object "Number of faults statistic" This group object is enabled if Enable Group object "Number of faults statistic" is set to Yes in X Output: Fault parameter window, p.
  • Page 191 ® ABB i-bus Commissioning Function Group object name Data type Flags Ballast number fault Output A 1 byte C, R, T DPT 5.010 Dependent on parameter Enable Group object for additional fault message displays "Ballast number fault" "Switch up next ballast fault"...
  • Page 192 ® ABB i-bus Commissioning Function Group object name Data type Flags Switch up next group fault Output A 1 bit C, W DPT 1.008 Dependent on parameter Enable Group object for additional fault message displays "Group number fault" "Switch up next group fault"...
  • Page 193 ® ABB i-bus Commissioning Function Group object name Data type Flags Status Partial failure active Output A 1 bit C, R, T DPT 1.010 Dependent on parameter Enable function "Partial failure" This group object is enabled if the Enable function "Partial failure" parameter is set to Yes in the X Output: Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window, p.
  • Page 194 ® ABB i-bus Commissioning Function Group object name Data type Flags 8-bit scene Scene 1…16 1 byte C, W DPT 18.001 Dependent on parameter Enable DALI scenes This group object is enabled if the Enable DALI scenes parameter is set to Yes in the X DALI configuration parameter window, p.
  • Page 195 ® ABB i-bus Commissioning Function Group object name Data type Flags Rem. burn-in time addressed Output A 3 byte C, R, T Non DPT Dependent on parameter Enable Group object "Rem burn-in time" This group object is enabled if the Enable Group object "Rem burn-in time" parameter is set to Yes in the X Output: Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window, p.
  • Page 196 ® ABB i-bus Commissioning Function Group object name Data type Flags Synchronize auto emergency lighting Output A 1 bit C, W, T tests DPT 1.010 Dependent on parameter Enable fct Automatic emergency lighting test Object "Synch auto emergency lighting tests"...
  • Page 197 ® ABB i-bus Commissioning Function Group object name Data type Flags Trigger em lighting test (addr) Output A 2 byte C, W, T DPT_CTC Dependent on parameter Trigger em lighting test (addr) This group object is enabled if the Trigger em lighting test (addr) parameter is set to Yes in the X lighting converter parameter window, p.
  • Page 198 ® ABB i-bus Commissioning Function Group object name Data type Flags Em lighting test status (addr) Output A 2 byte C, R, W, T non DPT (ACTS) Dependent on parameter Em lighting test status (addr) This group object is enabled if the Em lighting test status (addr) parameter is set to Yes in the X lighting converter parameter window, p.
  • Page 199 ® ABB i-bus Commissioning Function Group object name Data type Flags Em lighting test result Output A 4 byte C, R, W, T non DPT (FEOT) Dependent on parameter Em lighting test result (addr) This group object is enabled if the Em lighting test result (addr) parameter is set to Yes in the X lighting converter parameter window, p.
  • Page 200 ® ABB i-bus Commissioning Function Group object name Data type Flags Activate emergency lighting Output A 1 bit C, W, T Inhibit/rest mode DPT 1.010 Dependent on parameter Enable function Inhibit/rest mode object "Activate Inhibit/rest mode" This group object is enabled if the Enable function Inhibit/rest mode object "Activate Inhibit/rest mode" parameter is set to Yes in the X lighting converter parameter window, p.
  • Page 201: Group X/Ballast X Group Objects

    ® ABB i-bus Commissioning 3.3.4 Group x/Ballast x group objects As the lighting groups (groups) and individual DALI devices (ballasts) have the same functions and group objects, this chapter describes them jointly. The object names are distinguished by the term 'group' or 'ballast'.
  • Page 202 ® ABB i-bus Commissioning Function Group object name Data type Flags 48, 59… Status byte Output A - Group x 2 byte C, R, T 224, 235… Output A - Ballast x Non DPT Dependent on parameter Use group x Use ballast x This group object is always enabled if a group or ballast is in use.
  • Page 203 ® ABB i-bus Commissioning Function Group object name Data type Flags 49, 60… Switch Output A - Group x 1 bit C, W 225, 236… Output A - Ballast x DPT 1.001 Dependent on parameter Use group x Use ballast x This group object switches the group or individual lamps (ballasts) on or off at the brightness value set in X template group x/ballast x parameter window, p.
  • Page 204 ® ABB i-bus Commissioning Function Group object name Data type Flags 52, 63… Brightness value Output A - Group x 1 byte C, W 228, 239… Output A - Ballast x DPT 5.001 Dependent on parameter None This group object receives a brightness value for the corresponding group x or ballast x. Any burn-in time currently running has a higher priority, so under certain circumstances individual devices can only adopt a brightness of 100% or OFF.
  • Page 205 ® ABB i-bus Commissioning Function Group object name Data type Flags 54, 65… Lamp/ballast fault Output A - Group x 1 bit C, R, T 230, 241… Output A - Ballast x DPT 1.005 Dependent on parameter Enable Group object "Fault"...
  • Page 206 ® ABB i-bus Commissioning Function Group object name Data type Flags 55, 66… Forced operation 1 bit Output A - Group x 1 bit DPT 1.003 C, R, T 231, 242… Forced operation 2 bit Output A - Ballast x 2 bit DPT 2.001...
  • Page 207 ® ABB i-bus Commissioning Function Group object name Data type Flags 56, 67… Burn-in lamp Output A - Group x 1 bit C, R, W, T 232, 243… Output A - Ballast x DPT 1.010 Dependent on parameter Enable Lamp burn-in function object "Burn-in lamps"...
  • Page 208 ® ABB i-bus Commissioning Function Group object name Data type Flags 57, 68… Activate fct Staircase lighting Output A - Group x 1 bit C, W 233 244 Output A - Ballast x DPT 1.003 This group object is enabled if the additional function Staircase lighting is enabled in X Staircase lighting template (group x/ballast x) parameter window, p.
  • Page 209 ® ABB i-bus Commissioning Function Group object name Data type Flags 58, 69… Brightness value of slave Output A - Group x 1 byte C, W, T 234 245 Output A - Ballast x DPT 5.001 This group object is enabled if the additional function Slave is enabled in X Slave template (group x/ballast x) parameter window, p.
  • Page 210: Lighting Converter X Group Objects

    ® ABB i-bus Commissioning 3.3.5 Lighting converter x group objects As soon as an emergency lighting test is enabled in the X lighting converter parameter window, the Trigger em lighting test group object for converter x is enabled. The following emergency lighting tests can be triggered for the emergency lighting converter via this group object: •...
  • Page 211 ® ABB i-bus Commissioning Function Group object name Data type Flags 928, 931… Trigger em lighting test (DGN/S) Output A - Emergency light x 1 byte C, W Non DPT This group object is enabled if an Emergency light x is enabled in X lighting converter/Emergency light template parameter window, p.
  • Page 212 ® ABB i-bus Commissioning Function Group object name Data type Flags 928, 931… Trigger em lighting test/Status Output A - Emergency light x 1 byte C, R, W, T (DGN/S) Non DPT This group object is enabled if an Emergency light x is enabled in X lighting converter/Emergency light template parameter window, p.
  • Page 213 ® ABB i-bus Commissioning Function Group object name Data type Flags 929, 932… Em lighting test result Output A - Emergency light x 6 byte C, R, T DPT_CTR This group object is enabled if there is an Emergency light x enabled in X lighting converter/Emergency light template parameter window, p.
  • Page 214 ® ABB i-bus Commissioning Function Group object name Data type Flags 930, 933… Emergency lighting converter status Output A - Emergency light x 2 byte C, R, T DPT_CS This group object is enabled if there is an Emergency light x enabled in the X lighting converter/Emergency light template parameter window, p.155 and the Enable Group objects "Emergency lighting converter status"...
  • Page 215: Planning And Application

    If automatic DALI addressing is not allowed, there are three alternative options for implementing addressing with the DALI gateway: • ® ® i-bus Tool for ABB i-bus KNX device diagnostics and commissioning • Press and hold (> 5 seconds) the push button on the DALI gateway •...
  • Page 216: Lamp And Ballast Monitoring

    ® ABB i-bus Planning and application Lamp and ballast monitoring The gateway can broadcast the fault state of the output's DALI lighting on the KNX. A control panel or control center can evaluate and display this information. Required repair measures or corresponding maintenance cycles can be initiated.
  • Page 217: Exchange Of Dali Devices

    ® ABB i-bus Planning and application Exchange of DALI devices If a DALI device fails in an existing DALI installation where DALI addresses are assigned without any gaps, a DALI device in the as-delivered state with factory settings (without DALI addressing) can be used as a replacement, avoiding the need for re-commissioning.
  • Page 218: Function Circuit Diagrams And Priorities

    ® ABB i-bus Planning and application Function circuit diagrams and priorities The function tables show the effect of various KNX commands when a function is parametrized. The following should be noted here. Note Priorities in the gateway from highest to lowest: 1.
  • Page 219 ® ABB i-bus Planning and application The following table shows how the reaction when the Staircase lighting function is parametrized. Staircase lighting function Operating situation Active Dimming-down time Group objects Inactive Standby Dimming-up Staircase lighting Run time time time (turn off brightness)
  • Page 220 ® ABB i-bus Planning and application The following table shows the reaction to incoming telegrams when the Slave function is parametrized. Additional function Slave Operating situation Inactive Active in standby Active and ON (running) Group objects (Activate fct (Activate slave mode = 1)
  • Page 221: Dali Dimming Curve

    ® ABB i-bus Planning and application DALI dimming curve 4.5.1 DALI (logarithmic) curve The DALI dimming curve does not apply for emergency lighting converters, so the curve transformation function is not used on them. The DALI dimming curve is adjusted to the sensitivity of the human eye. This results in a logarithmic characteristic curve for the luminous flux which is perceived by the human eye as a linear brightness sequence.
  • Page 222 ® ABB i-bus Planning and application This produces the following DALI characteristic: KNX value 85 126 144 170 195 210 220 229 235 241 246 250 255 A´ KNX value [%] 98 100 DALI value (lamp power) 85 126 144 170 195 210 220 229 235 241 246 250 254...
  • Page 223: Knx (Linear) Curve

    ® ABB i-bus Planning and application 4.5.2 KNX (linear) curve Selecting the KNX (linear) curve in the gateway maps the brightness value received by the KNX directly to the lamp power (Y value). There is no linear transformation. The KNX brightness value received by the gateway is mapped directly to the lamp power. The logarithmic dimming curve calculates the DALI value, so that for the KNX there is linear mapping between the KNX value and the lamp power.
  • Page 224 ® ABB i-bus Planning and application This produces the black curve and the following DALI characteristic: KNX value 100 120 150 170 180 220 230 255 KNX value [%] Luminous flux [%] Logi DALI value 126 136 161 194 207 220 227 235 239 241 249 250 254...
  • Page 225: Time Sequences In The Gateway

    ® ABB i-bus Planning and application Time sequences in the gateway 4.6.1 DALI fade times The fade time has 16 settings (0 to 15). Fade time is specified as the time required to change the lamp power from the current brightness value to the required target brightness. If a lamp is switched off, the preheat and ignition time are excluded from the fade time.
  • Page 226: Timed Progression Of The Staircase Lighting Function

    ® ABB i-bus Planning and application 4.6.2 Timed progression of the staircase lighting function The DALI gateways feature the additional function Staircase lighting. This can be independently parametrized for each ballast and group. As the function is identical for groups and ballasts, only the group function is described below.
  • Page 227 ® ABB i-bus Planning and application Reaction to Switch telegram when staircase lighting is running If the dimming time is yet to start and the gateway receives an OFF telegram for the group, dimming down starts immediately. If the group is currently dimming down, dimming down continues if an OFF telegram is received.
  • Page 228 ® ABB i-bus Planning and application 226 2CDC507164D0201 | DG/S x.64.1.1...
  • Page 229: Appendix

    ® ABB i-bus Appendix Appendix 8-bit scene code table (group object 33) This code table indicates the telegram code for an 8-bit scene in hexadecimal and binary code for the first 16 scenes. Note There are 16 scenes available in the DALI. However, the gateway makes it possible to assign a DALI scene to any KNX scene, which can then be used to recall it via KNX.
  • Page 230 ® ABB i-bus Appendix The following extended table indicates the telegram code for an 8-bit scene in hexadecimal and binary code for all 64 scenes. Normally when recalling or storing a scene, an 8-bit value must be sent.  ...
  • Page 231: Fault Addressed "Request" (No. 21) Code Table

    ® ABB i-bus Appendix Fault addressed "Request" (no. 21) code table The 2-byte group object Fault addressed makes all the information about a ballast or group available on the KNX. The information is requested when a 2-byte telegram with a set bit 7 in the Low byte is received on the Fault addressed group object.
  • Page 232: Fault Addressed "Feedback" (No. 21) Code Table

    ® ABB i-bus Appendix Fault addressed "Feedback" (no. 21) code table The 2-byte group object Fault addressed makes all the information about a ballast or group available on the KNX. The same group object is used to request the information, see Fault addressed "Request" (no.
  • Page 233 ® ABB i-bus Appendix                                    ...
  • Page 234: Scope Of Delivery

    ABB i-bus Appendix Scope of delivery ® The ABB i-bus KNX DALI Gateway DG/S 1.64.1.1 and DG/S 2.64.1.1 are supplied with the following components. Please check your delivery against the list below: • 1x DG/S 1.64.1.1 or DG/S 2.64.1.1 MDRC •...
  • Page 235: Ordering Details

    MW 4 DG/S 2.64.1.1 DALI Gateway, Basic, 2f, MDRC, 2CDG110199R0011 94285 0 0.18 MW 4 ® Other DALI Gateways in the ABB i-bus range DLR/S 8.16.1M 67656 4 DALI Light Controller, MDRC, MW 6 2CDG110101R0011 0.26 DLR/A 4.8.1.1 DALI Light Controller, SM...
  • Page 236: Notes

    ® ABB i-bus Appendix Notes 234 2CDC507164D0201 | DG/S x.64.1.1...
  • Page 237 ® ABB i-bus Appendix Notes DG/S x.64.1.1 | 2CDC507164D0201 235...
  • Page 238 ® ABB i-bus Appendix Notes 236 2CDC507164D0201 | DG/S x.64.1.1...
  • Page 240 Fax: +49 (0)6221 701 724 With regard to purchase orders, the agreed particulars shall prevail. ABB AG shall not be liable E-mail: [email protected] for any consequences arising from errors or incomplete information in this document. Further information and local contacts: We reserve all rights in this document and in the www.abb.com/knx...

Table of Contents