Siemens S7-1500 User Manual

Siemens S7-1500 User Manual

Cpu 1511t-1 pn (6es7511-1tk01-0ab0)
Hide thumbs Also See for S7-1500:
Table of Contents
loading

Summary of Contents for Siemens S7-1500

  • Page 2 ___________________ CPU 1511T-1 PN Preface (6ES7511-1TK01-0AB0) ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ Wiring S7-1500 CPU 1511T-1 PN Interrupts, error messages, ___________ diagnostics and system (6ES7511-1TK01-0AB0) alarms ___________________ Manual Technical specifications ___________________ Dimension drawing 09/2016 A5E36270833-AA...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
  • Page 5 This information is provided by the Siemens Industry Online Support in the Internet (http://www.siemens.com/automation/service&support). Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 6: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................7 Product overview ..........................11 Applications of the S7-1500 CPU ..................11 Principle of operation ......................16 Properties ..........................17 Operator controls and display elements ................21 2.4.1 Front view of the module with closed front panel ..............21 2.4.2...
  • Page 7: Documentation Guide

    Documentation guide The documentation for the SIMATIC S7-1500 automation system, the CPU 1516pro-2 PN based on SIMATIC S7-1500 and the SIMATIC ET 200MP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require.
  • Page 8 Documentation guide General information The function manuals contain detailed descriptions on general topics regarding the SIMATIC S7-1500 and ET 200MP systems, e.g. diagnostics, communication, motion control, Web server, OPC UA. You can download the documentation free of charge from the Internet (http://w3.siemens.com/mcms/industrial-automation-systems-simatic/en/manual-...
  • Page 9 ● Manuals, characteristics, operating manuals, certificates ● Product master data You can find "mySupport" - CAx data on the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products.
  • Page 10 You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the PROFINET network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
  • Page 11: Product Overview

    Product overview Applications of the S7-1500 CPU Area of application SIMATIC S7-1500 is the modular control system for a wide variety of automation applications in discrete automation. The modular and fanless design, simple implementation of distributed structures, and user- friendly operation make SIMATIC S7-1500 the economic and convenient solution for a variety of tasks.
  • Page 12 Product overview 2.1 Applications of the S7-1500 CPU Performance segments of the standard, compact, fail-safe and technology CPUs The CPUs can be used for smaller and mid-range applications, as well as for the high-end range of machine and plant automation.
  • Page 13 Product overview 2.1 Applications of the S7-1500 CPU Table 2- 3 Fail-safe CPUs Performance segment PROFIBUS PROFINET PROFINET PROFINET Work Processing interfaces IO RT/IRT IO RT inter- basic func- memory time for bit interfaces face tionality operations CPU 1511F-1 Fail-safe CPU for small 1.23 MB...
  • Page 14 Frequency output • Integrated technological functions All CPUs of SIMATIC S7-1500 support motion control functions. STEP 7 offers Motion Control instructions standardized according to PLCopen for configuring and connecting a drive to the CPU. S7-1500 Motion Control supports the following technology objects: ●...
  • Page 15 For effective commissioning, diagnostics and fast optimization of drives and controls, the SIMATIC S7-1500 controller family offers extensive trace functions for all CPU tags. In addition to drive integration, the SIMATIC S7-1500 has a PID compact closed-loop controller; easy-to-configure blocks allow automatic optimization of the controller parameters for optimized control quality.
  • Page 16: Principle Of Operation

    DIN rail is implemented in the rail of the S7-1500. The CPUs of the SIMATIC S7-1500 product series can be expanded centrally and in a modular fashion with signal modules. Space-saving expansion enables flexible adaptation to each application.
  • Page 17: Properties

    Product overview 2.3 Properties Properties Article number 6ES7511-1TK01-0AB0 View of the module The following figure shows a CPU 1511T-1 PN. Figure 2-1 CPU 1511T-1 PN Note Protective film Note that a protective film is attached to the display of the CPU when shipped from the factory.
  • Page 18 – Cams, cam track for position-dependent generation of switching signals – Measuring input for fast, accurate and event-dependent sensing of actual positions The technology CPUs of the SIMATIC S7-1500 also support the technology object: – Cam for specification of the synchronous function for camming Motion Control instructions based on PLCopen are available for programming the technology objects.
  • Page 19 ● Trace functionality: – The trace functionality supports troubleshooting and optimization of the user program. You can find additional information on the trace functionality in the Using the Trace and Logic Analyzer (http://support.automation.siemens.com/WW/view/en/64897128) function manual. ● Integrated system diagnostics: – The alarms for the system diagnostics are automatically created by the system and displayed on a PG/PC, HMI device, Web server or the integrated display.
  • Page 20 You can find information on the topic of "Shared device" in the PROFINET function manual (https://support.industry.siemens.com/cs/ww/en/view/49948856). – Configuration control You can find information on the topic of "Configuration control" in the S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. – Isochronous mode You can find information about the "Isochronous mode"...
  • Page 21: Operator Controls And Display Elements

    Product overview 2.4 Operator controls and display elements Operator controls and display elements 2.4.1 Front view of the module with closed front panel The figure below shows the front view of the CPU 1511T-1 PN. ① LEDs for the current operating mode and diagnostics status of the CPU ②...
  • Page 22 2 hazardous areas. Before you remove or fit the front panel, always switch off the power supply to the S7-1500 automation system in hazardous area zone 2. The CPU maintains its operating mode.
  • Page 23: Front View Of The Module Without Front Panel

    Product overview 2.4 Operator controls and display elements 2.4.2 Front view of the module without front panel The figure below shows the operator controls and connection elements of the CPU 1511T-1 PN. ① LEDs for the current operating mode and diagnostics status of the CPU ②...
  • Page 24: Rear View Of The Module

    Product overview 2.5 Mode selector 2.4.3 Rear view of the module The following figure shows the connection elements on the rear of the CPU 1511T-1 PN. ① Shield contact surface ② Plug-in connection for power supply ③ Plug-in connection for backplane bus ④...
  • Page 25: Wiring

    Wiring Pin assignment This section provides information on the pin assignment of the individual interfaces and the block diagram of the CPU 1511T-1 PN. 24 V DC supply voltage (X80) The connector for the power supply is plugged in when the CPU ships from the factory. The following table shows the pin assignment for a 24 V DC power supply.
  • Page 26 PROFINET ports Reference You can find additional information on the topics of "Connecting the CPU" and "Accessories/spare parts" in the S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Assignment of the MAC addresses The CPU 1511T-1 PN has a PROFINET interface with two ports. The PROFINET interface itself has a MAC address, and each of the two PROFINET ports has its own MAC address.
  • Page 27 Wiring 3.1 Pin assignment The table below shows how the MAC addresses are assigned. Table 3- 1 Assignment of the MAC addresses Assignment Labeling MAC address 1 PROFINET interface X1 Front, lasered • (visible in STEP 7 for accessible devices) Right side, lasered •...
  • Page 28 Wiring 3.1 Pin assignment Block diagram The following figure shows the block diagram of the CPU 1511T-1 PN. ① Display PN X1 P1 R PROFINET interface X1 Port 1 ② RUN/STOP/MRES mode selector PN X1 P2 R PROFINET interface X1 Port 2 ③...
  • Page 29: Interrupts, Error Messages, Diagnostics And System Alarms

    You can find additional information on the topic of "Interrupts" in the STEP 7 online help. You can find additional information on the topic of "Diagnostics" and "System alarms" in the Diagnostics (http://support.automation.siemens.com/WW/view/en/59192926) function manual. Status and error display of the CPU Key statement The following figure shows the LED displays of the CPU 1511T-1 PN.
  • Page 30 Interrupts, error messages, diagnostics and system alarms 4.1 Status and error display of the CPU Meaning of the RUN/STOP, ERROR and MAINT LEDs The CPU 1511T-1 PN has three LEDs to signal the current operating status and diagnostics status. The following table shows the meaning of the various combinations of colors for the RUN/STOP, ERROR and MAINT LEDs.
  • Page 31 Interrupts, error messages, diagnostics and system alarms 4.1 Status and error display of the CPU Meaning of LINK RX/TX LED Each port has a LINK RX/TX LED. The table below shows the various "LED scenarios" of ports for the CPU 1511T-1 PN. Table 4- 2 Meaning of the LEDs LINK TX/RX LED...
  • Page 32: Technical Specifications

    Technical specifications 6ES7511-1TK01-0AB0 General information Product type designation CPU 1511T-1 PN Hardware function version FS03 Firmware version V2.0 Engineering with STEP 7 TIA Portal can be configured/integrated as of version Configuration control Via data record Display Screen diagonal (cm) 3.45 cm Operator controls Number of buttons Mode selector...
  • Page 33 Technical specifications 6ES7511-1TK01-0AB0 Load memory Plug-in (SIMATIC memory card), max. 32 GB Buffering Maintenance-free CPU processing times For bit operations, typ. 60 ns For word operations, typ. 72 ns For fixed-point arithmetic, typ. 96 ns For floating-point arithmetic, typ. 384 ns CPU blocks Number of elements (total) 2000;...
  • Page 34 Technical specifications 6ES7511-1TK01-0AB0 Counters, timers and their retentivity S7 counters Quantity 2048 Retentivity Adjustable • IEC counters Quantity Unlimited (limited only by work memory) Retentivity Adjustable • S7 timers Quantity 2048 Retentivity Adjustable • IEC timers Quantity Unlimited (limited only by work memory) Retentivity Adjustable •...
  • Page 35 Technical specifications 6ES7511-1TK01-0AB0 Process image partitions Number of process image partitions, max. Hardware configuration Number of distributed IO systems 32; a distributed IO system is understood to mean the integration of distributed I/O via PROFINET or PROFIBUS communication mod- ules as well as the connection of I/O via AS-i master modules or links (e.g.
  • Page 36 Technical specifications 6ES7511-1TK01-0AB0 Protocols PROFINET IO controller PROFINET IO device SIMATIC communication Open IE communication Web server Media redundancy PROFINET IO controller Services PG/OP communication • S7 routing • Isochronous mode • Open IE communication • • Yes; as MRP redundancy manager and/or MRP •...
  • Page 37 Technical specifications 6ES7511-1TK01-0AB0 Update time with RT 250 µs to 128 ms for send clock of 250 µs • 500 µs to 256 ms With send clock of 500 µs • 1 ms to 512 ms With send clock of 1 ms •...
  • Page 38 Technical specifications 6ES7511-1TK01-0AB0 PROFINET IO controller Services PG/OP communication • S7 routing • Isochronous mode • Open IE communication • • Yes; as MRP redundancy manager and/or MRP • client; max. number of devices in the ring: 50 Yes; requirement: IRT MRPD •...
  • Page 39 Technical specifications 6ES7511-1TK01-0AB0 SNMP LLDP Web server HTTP Yes; standard and user-defined sites HTTPS Yes; standard and user-defined sites OPC UA OPC UA server Yes; Data Access (Read, Write, Subscribe), Runtime license required Application authentication • Available Security Policies: None, Security Policies •...
  • Page 40 Technical specifications 6ES7511-1TK01-0AB0 Status/modify Status/modify tag Tags Inputs/outputs, bit memory, DB, peripheral in- puts/outputs, timers, counters Number of tags, max. 200; per job Of which are status tags, max. • 200; per job Of which are modify tags, max. • Forcing Forcing, tags Peripheral inputs/outputs...
  • Page 41 Technical specifications 6ES7511-1TK01-0AB0 Controller Yes; universal PID controller with integrated op- PID_Compact • timization Yes; PID controller with integrated optimization PID_3Step • for valves Yes; PID controller with integrated optimization PID temp • for temperature Counting and measuring High-speed counter •...
  • Page 42 Weight, approx. 430 g General technical specifications You can find information on the general technical specifications, such as standards and approvals, electromagnetic compatibility, protection class, etc., in the S7-1500, ET 200MP System Manual (http://support.automation.siemens.com/WW/view/en/59191792). CPU 1511T-1 PN (6ES7511-1TK01-0AB0) Manual, 09/2016, A5E36270833-AA...
  • Page 43: A.1 Dimensional Drawing Of The Cpu 1511T-1 Pn

    Dimension drawing Dimensional drawing of the CPU 1511T-1 PN This section contains the dimensional drawing of the module on the mounting rail, as well as a dimensional drawing with the front panel open. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Dimensional drawings of the CPU 1511T-1 PN Figure A-1 Dimensional drawing of the CPU 1511T-1 PN, front and side view...
  • Page 44 Dimension drawing A.1 Dimensional drawing of the CPU 1511T-1 PN Figure A-2 Dimensional drawing of the CPU 1511T-1 PN, side view with front panel open CPU 1511T-1 PN (6ES7511-1TK01-0AB0) Manual, 09/2016, A5E36270833-AA...

Table of Contents