  • Page 2 ___________________ Preface ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ Wiring S7-1500/ET 200MP DI 16x230VAC BA Digital Input ___________________ Module Address space (6ES7521-1FH00-0AA0) ___________________ Diagnostic alarms Manual ___________________ Technical specifications ___________________ Dimensional drawing 09/2016 A5E03485975-AD...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Purpose of the documentation This manual supplements the S7-1500/ET 200MP (https://support.industry.siemens.com/cs/ww/en/view/59191792) system manual. Functions that relate in general to the systems are described in this system manual. The information provided in this manual and in the system/function manuals supports you in commissioning the systems.
  • Page 5 In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
  • Page 6: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................7 Product overview ..........................11 Properties ..........................11 Wiring ..............................13 Address space ............................14 Address space ........................14 Diagnostic alarms ..........................18 Status and error displays ....................... 18 Technical specifications ........................20 Dimensional drawing ..........................
  • Page 7: Documentation Guide

    Documentation guide The documentation for the SIMATIC S7-1500 automation system, the CPU 1516pro-2 PN based on SIMATIC S7-1500 and the SIMATIC ET 200MP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require.
  • Page 8 You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/68052815). Manual Collection S7-1500/ET 200MP The Manual Collection contains the complete documentation on the SIMATIC S7-1500 automation system and the ET 200MP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (https://support.industry.siemens.com/cs/ww/en/view/86140384).
  • Page 9 ● Manuals, characteristics, operating manuals, certificates ● Product master data You can find "mySupport" - CAx data on the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products.
  • Page 10 You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the PROFINET network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
  • Page 11: Product Overview

    Product overview Properties Article number 6ES7521-1FH00-0AA0 View of the module Figure 2-1 View of the DI 16x230VAC BA module Properties The module has the following technical properties: ● 16 digital inputs; electrically isolated in groups of 4 ● Rated input voltage 120/230 V AC ●...
  • Page 12 Other components The following component can be ordered separately: Front connectors, including potential jumpers and cable ties You can find additional information on accessories in the S7-1500/ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. DI 16x230VAC BA Digital Input Module (6ES7521-1FH00-0AA0) Manual, 09/2016, A5E03485975-AD...
  • Page 13: Wiring

    This section contains the block diagram of the module and outlines various wiring options. You can find information on wiring the front connector, creating a cable shield, etc. in the Wiring section of the S7-1500/ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Note Do not insert the potential jumpers included with the front connector!
  • Page 14: Address Space

    Address space Address space The module can be configured differently in STEP 7; see following table. Depending on the configuration, additional/different addresses are assigned in the process image of the inputs. The letters "a to d" are printed on the module - "EB a", for example, stands for module start address input byte a.
  • Page 15 Address space 4.1 Address space Address space for configuration as DI 16x230VAC BA The following figure shows the address space allocation for the configuration as 16-channel module. You can freely assign the start address for the module. The addresses of the channels are derived from the start address.
  • Page 16 Address space 4.1 Address space Value status (Quality Information, QI) The meaning of the value status depends on the submodule involved. For the 1st submodule (=basic submodule), the value status is not relevant. For the 2nd to 4th submodule (=MSI submodule), the value status 0 indicates that the basic submodule parameters have not yet been assigned (not ready).
  • Page 17 You can find information on the module-internal shared input/shared output (MSI/MSO) function in the section Module-internal shared input/shared output (MSI/MSO) of the function manual PROFINET with STEP 7 V13 (https://support.industry.siemens.com/cs/ww/en/view/49948856). DI 16x230VAC BA Digital Input Module (6ES7521-1FH00-0AA0) Manual, 09/2016, A5E03485975-AD...
  • Page 18: Diagnostic Alarms

    Diagnostic alarms Status and error displays LED displays The figure below shows the LED displays (status and error displays) of the DI 16x230VAC BA. Figure 5-1 LED displays of the module DI 16x230VAC BA DI 16x230VAC BA Digital Input Module (6ES7521-1FH00-0AA0) Manual, 09/2016, A5E03485975-AD...
  • Page 19 Diagnostic alarms 5.1 Status and error displays Meaning of the LED displays The following table explains the meaning of the status and error displays. RUN and ERROR LED Table 5- 1 Status and error displays RUN and ERROR Meaning Remedy ERROR Voltage missing or too low at backplane bus Switch on the CPU and/or the system pow-...
  • Page 20: Technical Specifications

    Technical specifications Technical specifications of the DI 16x230VAC BA 6ES7521-1FH00-0AA0 General information Product type designation DI 16x230VAC BA Hardware functional status FS01 Firmware version V2.0.0 FW update possible • Product function I&M data Yes; I&M0 to I&M3 Engineering with STEP 7 TIA Portal can be configured/integrated V12 / V12 as of version STEP 7 can be configured/integrated as of version V5.5 SP3 / -...
  • Page 21 Technical specifications 6ES7521-1FH00-0AA0 Input delay (for rated value of input voltage) For standard inputs Configurable • 25 ms with "0" to "1", max. • 25 ms with "1" to "0", max. • For interrupt inputs Configurable • for technological functions Configurable •...
  • Page 22 Technical specifications 6ES7521-1FH00-0AA0 Permitted potential difference Between different circuits 250 V AC between the channels and the back- plane bus; 500 V AC between the channels Isolation Isolation tested with 3100 V DC Ambient conditions Ambient temperature during operation Horizontal mounting position, min. 0 °C Horizontal mounting position, max.
  • Page 23: Dimensional Drawing

    Dimensional drawing The dimensional drawing of the module on the mounting rail, as well as a dimensional drawing with open front cover, are provided in the appendix. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Figure A-1 Dimensional drawing of the DI 16x24VAC BA module DI 16x230VAC BA Digital Input Module (6ES7521-1FH00-0AA0) Manual, 09/2016, A5E03485975-AD...