GE AF-650 GP Operating Instructions Manual
Hide thumbs Also See for AF-650 GP:
Table of Contents
GE
AF-650 GP
TM
General Purpose Drive
(230V to 50HP, 460/575V to 100HP)
Operating Instructions
Table of Contents
loading

Summary of Contents for GE AF-650 GP

  • Page 1 AF-650 GP General Purpose Drive (230V to 50HP, 460/575V to 100HP) Operating Instructions...
  • Page 2 Safety AF-650 GP Operating Instructions Safety WARNING Voltage (V) Minimum waiting time (minutes) HIGH VOLTAGE! 200 - 240 1/3 - 5HP 7.5 - 50HP Frequency converters contain high voltage when 380 - 480 1/2 - 10HP 15 - 100HP connected to AC mains input power. Installation, start up,...
  • Page 3 Safety AF-650 GP Operating Instructions...
  • Page 4: Table Of Contents

    Contents AF-650 GP Operating Instructions Contents 1 Introduction 1.1 Purpose of the Manual 1.2 Additional Resources 1.3 Product Overview 1.4 Internal Frequency Converter Controller Functions 1.5 Unit Sizes and Power Ratings 2 Installation 2.1 Installation Site Check List 2.2 Frequency Converter and Motor Pre-installation Check List 2.3 Mechanical Installation...
  • Page 5 Contents AF-650 GP Operating Instructions 3.6 Local-control Test 3.7 System Start Up 4 User Interface 4.1 Keypad 4.1.1 Keypad Layout 4.1.2 Setting Keypad Display Values 4.1.3 Display Menu Keys 4.1.4 Navigation Keys 4.1.5 Operation Keys 4.2 Back Up and Copying Parameter Settings 4.2.1 Uploading Data to the Keypad...
  • Page 6 Contents AF-650 GP Operating Instructions 9.1 Start Up and Operation 10 Specifications 10.1 Power-dependent Specifications 10.2 General Technical Data 10.3 Fuse Tables 10.3.1 Recommendations 10.3.2 CE Compliance 10.4 Connection Tightening Torques Index...
  • Page 7: Introduction

    Introduction AF-650 GP Operating Instructions 1 Introduction Illustration 1.1 Exploded View Unit Sizes 12-13, IP20 Keypad 10 Motor output terminals 96 (U), 97 (V), 98 (W) RS-485 serial bus connector (+68, -69) 11 Relay 1 (01, 02, 03) Analog I/O connector...
  • Page 8 Introduction AF-650 GP Operating Instructions Illustration 1.2 Exploded View Unit Sizes 2X and 3X, IP55/66 Keypad Relay 2 (04, 05, 06) Cover Lifting ring RS-485 serial bus connector Mounting slot Digital I/O and 24 V power supply Grounding clamp (PE)
  • Page 9: Purpose Of The Manual

    Introduction AF-650 GP Operating Instructions 1.1 Purpose of the Manual 1.4 Internal Frequency Converter Controller This manual is intended to provide detailed information for Functions the installation and start up of the frequency converter. Chapter 2 Installation provides requirements for...
  • Page 10 Introduction AF-650 GP Operating Instructions Area Title Functions • Mains input Three-phase AC mains power supply to the drive • Rectifier The rectifier bridge converts the AC input to DC current to supply inverter power • DC bus The frequency converter's...
  • Page 11: Unit Sizes And Power Ratings

    Introduction AF-650 GP Operating Instructions 1.5 Unit Sizes and Power Ratings Unit sizes IP20 / Open Chassis IP55 / Nema 12 and IP66 / Nema 4/4X Indoor Volts 200-240 1/3-3 HP 5 HP 7.5-10 HP 15-20 HP 25-30 HP 40-50 HP 1/3-5 HP 7.5-10 HP...
  • Page 12: Installation

    Installation AF-650 GP Operating Instructions 2 Installation 2.1 Installation Site Check List 2.3 Mechanical Installation • 2.3.1 Cooling The drive relies on the ambient air for cooling. Observe the limitations on ambient air temperature for optimal operation • To provide cooling airflow, mount the unit to a solid flat surface or to the optional back plate •...
  • Page 13: Lifting

    Installation AF-650 GP Operating Instructions 2.3.2 Lifting • Check the weight of the unit to determine a safe lifting method • Ensure that the lifting device is suitable for the task • If necessary, plan for a hoist, crane, or forklift with the appropriate rating to move the unit •...
  • Page 14: Electrical Installation

    Installation AF-650 GP Operating Instructions 2.4 Electrical Installation This section contains detailed instructions for wiring the drive. The following tasks are described. • Wiring the motor to the drive output terminals • Wiring the AC mains to the drive input terminals •...
  • Page 15: Requirements

    For your safety, comply with the following requirements. temperature requirements. • GE recommends that all power connections be • Electronic controls equipment is connected to made with a minimum 75° C rated copper wire. hazardous mains voltage. Extreme care should be •...
  • Page 16: Leakage Current (>3,5Ma)

    Installation AF-650 GP Operating Instructions • 2.4.2.2 Grounding Using Shielded Cable Use the clamps provided with on the equipment for proper ground connections Earthing (grounding) clamps are provided for motor wiring • Do not ground one drive to another in a “daisy (see Illustration 2.6).
  • Page 17: Ac Mains Connection

    Installation AF-650 GP Operating Instructions • 2.4.5 Control Wiring Follow motor manufacturer wiring requirements Illustration 2.7 represents mains input, motor, and earth • Isolate control wiring from high power grounding for basic frequency converters. Actual configu- components in the frequency converter.
  • Page 18: Control Terminal Types

    Installation AF-650 GP Operating Instructions 2.4.5.2 Control Terminal Types Terminal description Default Terminal Parameter setting Description Illustration 2.10 and shows the removable frequency converter connectors. Terminal functions and default Digital inputs/outputs settings are summarized in Table 2.2. 12, 13 +24V DC 24V DC supply voltage.
  • Page 19: Wiring To Control Terminals

    Installation AF-650 GP Operating Instructions 2.4.5.4 Using Screened Control Cables Terminal description Default Terminal Parameter setting Description Correct screening Serial communication The preferred method in most cases is to secure control and serial communication cables with screening clamps Integrated RC-Filter for provided at both ends to ensure best possible high cable screen.
  • Page 20: Control Terminal Functions

    The switches are accessible when the Keypad has Terminal 37 Safe Stop Function been removed (see Illustration 2.13). Note that The AF-650 GP and is available with safe stop functionality some option cards available for the unit may via control terminal 37. Safe stop disables the control...
  • Page 21 Installation AF-650 GP Operating Instructions Standards before using this function. Depending on the Use of safe stop on terminal 37 requires that the user application a mechanical brake may be required. satisfies all provisions for safety including relevant laws, •...
  • Page 22 Installation AF-650 GP Operating Instructions Illustration 2.15 Installation to Achieve a Stopping Category 0 (EN 60204-1) with Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1). Safety device Cat. 3 (circuit interrupt device, possibly Inverter with release input) Door contact...
  • Page 23: Serial Communication

    Installation AF-650 GP Operating Instructions 2.4.6 Serial Communication Connect RS-485 serial communication wiring to terminals (+)68 and (-)69. • Screened serial communication cable is recommended • See 2.4.2 Earth (Grounding) Requirements for proper grounding Illustration 2.16 Serial Communication Wiring Diagram For basic serial communication set-up, select the following Protocol type in O-30 Protocol.
  • Page 24: Start Up And Functional Testing

    Start Up and Functional Tes... AF-650 GP Operating Instructions 3 Start Up and Functional Testing 3.1 Pre-start 3.1.1 Safety Inspection WARNING HIGH VOLTAGE! If input and output connections have been connected improperly, there is potential for high voltage on these terminals.
  • Page 25: Start Up Check List

    Start Up and Functional Tes... AF-650 GP Operating Instructions 3.1.2 Start Up Check List CAUTION Before applying power to the unit, inspect the entire installation as detailed in Table 3.1. Check mark those items when completed. ☑ Inspect for Description •...
  • Page 26: Applying Power To The Frequency Converter

    Start Up and Functional Tes... AF-650 GP Operating Instructions 3.2 Applying Power to the Frequency Converter WARNING Select language and press [OK]. Then enter the motor data in parameters P-02, P-03, P-06, P-07, HIGH VOLTAGE! F-04 and F-05. The information can be found on Frequency converters contain high voltage when the motor nameplate.
  • Page 27: Auto Tune

    Start Up and Functional Tes... AF-650 GP Operating Instructions 3.4 Auto Tune 3.6 Local-control Test CAUTION Auto tune is a test procedure that measures the electrical characteristics of the motor to optimize compatibility MOTOR START! between the drive and the motor.
  • Page 28: System Start Up

    Start Up and Functional Tes... AF-650 GP Operating Instructions NOTE 3.1 Pre-start through 3.6 Local-control Test in this chapter conclude the procedures for applying power to the drive, basic programming, set-up, and functional testing. 3.7 System Start Up The procedure in this section requires user-wiring and application programming to be completed.
  • Page 29: User Interface

    User Interface AF-650 GP Operating Instructions 4 User Interface 4.1.1 Keypad Layout 4.1 Keypad The Keypad is divided into four functional groups (see Illustration 4.1). The Keypad is the combined display and keys on the front of the unit. The Keypad is the user interface to the frequency converter.
  • Page 30: Setting Keypad Display Values

    User Interface AF-650 GP Operating Instructions 4.1.2 Setting Keypad Display Values 4.1.3 Display Menu Keys The display area is activated when the frequency converter Menu keys are used for menu access for parameter set-up, receives power from mains voltage, a DC bus terminal, or toggling through status display modes during normal an external 24V supply.
  • Page 31: Navigation Keys

    User Interface AF-650 GP Operating Instructions 4.1.4 Navigation Keys 4.1.5 Operation Keys Navigation keys are used for programming functions and Operation keys are found at the bottom of the Keypad. moving the display cursor. The navigation keys also provide speed control in local (hand) operation. Three drive status indicator lights are also located in this area.
  • Page 32: Uploading Data To The Keypad

    User Interface AF-650 GP Operating Instructions WARNING menu settings, fault log, alarm log, and other monitoring functions UNINTENDED START! • Using H-03 Restore Factory Settings is generally When drive is connected to AC mains, the motor may start recommended at any time. The drive, motor, and any driven equipment •...
  • Page 33: About Frequency Converter Programming

    About Frequency Converter P... AF-650 GP Operating Instructions 5 About Frequency Converter Programming Parameter Data Set Fundamental Parameters 5.1 Introduction The drive is programmed for its application functions using parameters. Parameters are accessed by pressing either [Quick Menu] or [Main Menu] on the Keypad. (See 4 User Interface for details on using the Keypad function keys.)
  • Page 34 About Frequency Converter P... AF-650 GP Operating Instructions F-53 Maximum Reference. Set maximum internal AN-10 Terminal 53 Low Voltage. Set minimum drive reference to 60Hz. (This sets the maximum external voltage reference on Terminal 53 at 0V. drive speed at 60Hz. Note that 50/60Hz is a (This sets the minimum input signal at 0V.)
  • Page 35 About Frequency Converter P... AF-650 GP Operating Instructions AN-14 Terminal 53 Low Ref./Feedb. Value. Set minimum speed reference on Terminal 53 at 20Hz. (This tells the drive that the minimum voltage received on Terminal 53 (0V) equals 20Hz output.) Illustration 5.1 Wiring Example for External Device Providing 0-10V Control Signal AN-15 Terminal 53 High Ref./Feedb.
  • Page 36: Control Terminal Programming Examples

    About Frequency Converter P... AF-650 GP Operating Instructions 5.3 Control Terminal Programming Scroll to parameter group E-0# Digital Inputs and press [OK] Examples Scroll to E-01 Terminal 18 Digital Input. Press [OK] Control terminals can be programmed. to access function choices. The default setting Start is shown.
  • Page 37: Parameter Data Check

    About Frequency Converter P... AF-650 GP Operating Instructions Parameter International North American default parameter default parameter value value E-24 Function Relay No operation No alarm AN-15 Terminal 53 High Ref./Feedb. Value AN-50 Terminal 42 No operation Speed 4-20mA Output H-04 Auto-Reset...
  • Page 38: Parameter Menu Structure

    About Frequency Converter P... AF-650 GP Operating Instructions 5.6 Parameter Menu Structure Establishing the correct programming for applications often requires setting functions in several related parameters. These parameter settings provide the drive with system details for the drive to operate properly.
  • Page 39: Main Menu Structure

    About Frequency Converter P... AF-650 GP Operating Instructions...
  • Page 40 About Frequency Converter P... AF-650 GP Operating Instructions...
  • Page 41 About Frequency Converter P... AF-650 GP Operating Instructions...
  • Page 42: Remote Programming With Dct-10

    About Frequency Converter P... AF-650 GP Operating Instructions 5.7 Remote Programming with DCT-10 GE has a software program available for developing, storing, and transferring drive programming. The DCT-10 allows the user to connect a PC to the drive and perform live programming rather than using the Keypad.
  • Page 43: Application Set-Up Examples

    Application Set-Up Examples AF-650 GP Operating Instructions 6 Application Set-Up Examples Parameters Function Setting 6.1 Introduction AN-12 Terminal 4mA* The examples in this section are intended as a quick 53 Low Current reference for common applications. AN-13 Terminal 20mA* 53 High Current •...
  • Page 44 Application Set-Up Examples AF-650 GP Operating Instructions Parameters Function Setting E-01 Terminal 18 [8] Start Digital Input E-02 Terminal 19 [10] Digital Input Reversing* E-05 Terminal 32 [16] Preset Parameters Digital Input ref bit 0 Function Setting E-06 Terminal 33...
  • Page 45 Application Set-Up Examples AF-650 GP Operating Instructions Parameters Function Setting S p e e d AN-10 Terminal R e f e r e n c e 53 Low Voltage 0.07V* AN-11 Terminal 10V* 53 High Voltage S t a r t ( 1 8 )
  • Page 46 Application Set-Up Examples AF-650 GP Operating Instructions Parameters CAUTION Function Setting Thermistors must use reinforced or double insulation to meet PELV insulation requirements. H-20 Motor Feedback Loss Function [1] Warning Parameters H-21 Motor 100RPM Function Setting Feedback Speed Error F-10 Electronic...
  • Page 47 Application Set-Up Examples AF-650 GP Operating Instructions In the upper right corner of the keypad 2 numbers are Parameters shown – like 1(1). The number outside the parenthesis is Function Setting the active set-up and the number inside the parenthesis is the set-up which will be edited.
  • Page 48 Application Set-Up Examples AF-650 GP Operating Instructions Parameters Function Setting E-01 Terminal 18 Digital Input [8] Start* E-03 Terminal 27 [23[ Set-up Digital Input select bit 0 * = Default Value Notes/comments: GE 30mm HOA Cat# (1) 104PSG34B & (3) CR104PXC1...
  • Page 49: Status Messages

    Status Messages AF-650 GP Operating Instructions 7 Status Messages 7.1 Status Display 7.2 Status Message Definitions Table When the drive is in status mode, status messages are The next three tables define the meaning of the status generated automatically from within the drive and appear message display words.
  • Page 50 Status Messages AF-650 GP Operating Instructions Operation status Operation status Ctrl. Ramp Control Ramp was selected in SP-10 Line Freeze ref. Freeze Reference was chosen as a function for failure. a digital input (parameter group E-0#). The • The mains voltage is below the value set corresponding terminal is active.
  • Page 51 Status Messages AF-650 GP Operating Instructions Operation status Ramping The motor is accelerating/decelerating using the active Ramp. The reference, a limit value or a standstill is not yet reached. Ref. high The sum of all active references is above the reference limit set in H-75 Warning Reference High.
  • Page 52: Warnings And Alarms

    Warnings and Alarms AF-650 GP Operating Instructions 8 Warnings and Alarms 8.1 System Monitoring 8.3 Warning and Alarm Displays The drive monitors the condition of its input power, output, and motor factors as well as other system performance indicators. A warning or alarm may not necessarily indicate a problem internal to the drive itself.
  • Page 53: Warning And Alarm Definitions

    Warnings and Alarms AF-650 GP Operating Instructions 8.4 Warning and Alarm Definitions defines whether a warning is issued prior to an alarm, and whether the alarm trips the unit or trip locks the unit. Description Warning Alarm/Trip Alarm/Trip Parameter Lock...
  • Page 54 Warnings and Alarms AF-650 GP Operating Instructions Description Warning Alarm/Trip Alarm/Trip Parameter Lock Reference Overload of Digital Output Terminal 29 E-00 Digital I/O Mode, E-52 Terminal 29 Mode Ovrld X30/6-7 Ext. Supply (option) Earth Fault 2 Pwr. card supply 24 V supply low 1.8 V supply low...
  • Page 55: Fault Messages

    Warnings and Alarms AF-650 GP Operating Instructions Description Warning Alarm/Trip Alarm/Trip Parameter Lock Reference Rect. low temp. New spare parts New Type Code Table 8.1 Alarm/Warning Code List Troubleshooting: Check the supply voltage and supply (X) Dependent on parameter currents to the drive.
  • Page 56 Warnings and Alarms AF-650 GP Operating Instructions Troubleshooting WARNING/ALARM 12, Torque limit Compare the output current shown on the The torque has exceeded the value in F-40 Torque Limiter Keypad with the drive rated current. (Driving) or the value in F-41 Torque Limiter (Braking).
  • Page 57 Warnings and Alarms AF-650 GP Operating Instructions ID-50 SW ID Power Card Check the sensors on the heatsink and control card. ID-60 Option Mounted ALARM 29, Heatsink temp ID-61 Option SW Version (for each option slot) The maximum temperature of the heatsink has been ALARM 16, Short circuit exceeded.
  • Page 58 Check E-56 Term X30/6 Digi Out Check for loose or missing wiring (OPCGPIO). It may be necessary to contact your GE supplier or service For X30/7, check the load connected to X30/7 or remove department. Note the code number for further trouble- short-circuit connection.
  • Page 59 Warnings and Alarms AF-650 GP Operating Instructions ALARM 53, Auto tune motor too big WARNING 66, Heatsink temperature low The motor is too big for the Auto tune to operate. The drive is too cold to operate. This warning is based on the temperature sensor in the IGBT module.
  • Page 60 Warnings and Alarms AF-650 GP Operating Instructions ALARM 83, Illegal option combination ALARM 246, Power card supply The mounted options are not supported to work together. This alarm is only for 6x unit size drive. It is equivalent to Alarm 46. The report value in the alarm log indicates...
  • Page 61: Basic Troubleshooting

    Basic Troubleshooting AF-650 GP Operating Instructions 9 Basic Troubleshooting 9.1 Start Up and Operation See Alarm Log in Table 4.1. Symptom Possible Cause Test Solution Missing input power See Table 3.1. Check the input power source. Missing or open fuses or circuit...
  • Page 62 Basic Troubleshooting AF-650 GP Operating Instructions Symptom Possible Cause Test Solution Motor rotation limit Check that H-08 Reverse Lock is Program correct settings. programmed correctly. Active reversing signal Check if a reversing command is Deactivate reversing signal. Motor running in wrong...
  • Page 63: Specifications

    Specifications AF-650 GP Operating Instructions 10 Specifications 10.1 Power-dependent Specifications Mains Supply 3 x 200 - 240 VAC AF-650 GP Typical Shaft Output [kW] 0.25 0.37 0.75 Typical Shaft Output [HP] at 208V Unit Size IP20 Unit Size IP55, 66...
  • Page 64 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 200 - 240V AC AF-650 GP 7.5HP 10HP 15HP High/ Normal Load Typical Shaft Output [kW] Typical Shaft Output [HP] at 208V Unit Size IP20 Unit Size IP55, 66 Output current Continuous 24.2...
  • Page 65 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 200 - 240V AC AF-650 GP 20 HP 25 HP 30 HP 40 HP 50 HP High/ Normal Load Typical Shaft Output [kW] 18.5 18.5 Typical Shaft Output [HP] at 208V...
  • Page 66 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 380 - 480V AC AF-650 GP 0.37 0.75 Typical Shaft Output [kW] Typical Shaft Output [HP] at 460V Unit Size IP20 Unit Size IP55, IP66 Output current Heavy duty (HD) 160% for 1 minute Shaft output [kW] 0.37...
  • Page 67 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 380 - 480V AC AF-650 GP 15 HP 20 HP 25 HP 30 HP High/ Normal Load Typical Shaft output [kW] 18.5 18.5 22.0 22.0 30.0 Typical Shaft Output [HP] at...
  • Page 68 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 380 - 480V AC AF-650 GP 40 HP 50 HP 60 HP 75 HP 100 HP High/ Normal Load Typical Shaft output [kW] Typical Shaft Output [HP] at 460V Unit Size IP20...
  • Page 69 Specifications AF-650 GP Operating Instructions For fuse ratings, see 10.3.1 Fuses 1) Heavy duty (HD) = 160% torque during 60 sec., Light duty (LD) = 110% torque during 60 sec. 2) American Wire Gauge. 3) Measured using 5 m screened motor cables at rated load and rated frequency.
  • Page 70 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 525 - 600V AC AF-650 GP 15 HP 20 HP 25 HP 30 HP 40 HP High/ Normal Load Typical Shaft Output [kW] 18.5 18.5 Typical Shaft Output [HP] at 575V...
  • Page 71 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 525 - 600V AC AF-650 GP 50 HP 60 HP 75 HP 100 HP High/ Normal Load* Typical Shaft Output [kW] Typical Shaft Output [HP] at 575V Unit Size IP IP55, IP66...
  • Page 72 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 525 - 690V AC AF-650 GP 15 HP 20 HP 25 HP 30 HP Heavy Duty/Light Duty Typical Shaft output at 550V 18.5 18.5 [kW] Typical Shaft output at 575V [HP] Typical Shaft output at 690V 18.5...
  • Page 73 Specifications AF-650 GP Operating Instructions Mains Supply 3 x 525 - 690V AC AF-650 GP 40 HP 50 HP 60 HP 75 HP 100 HP Heavy Duty/Light Duty* Typical Shaft output at 550V [kW] Typical Shaft output at 575V [HP]...
  • Page 74: General Technical Data

    Specifications AF-650 GP Operating Instructions 10.2 General Technical Data Mains supply: Supply Terminals (6-Pulse) L1, L2, L3 Supply Terminals (12-Pulse) L1-1, L2-1, L3-1, L1-2, L2-2, L3-2 200-240V ±10% Supply voltage 380-480V ±10% Supply voltage 525-600V ±10% Supply voltage 525-690V ±10%...
  • Page 75 Specifications AF-650 GP Operating Instructions Digital inputs: Programmable digital inputs 4 (6) Terminal number 18, 19, 27 , 29 , 32, 33, Logic PNP or NPN Voltage level 0 - 24V DC Voltage level, logic'0' PNP < 5V DC Voltage level, logic'1' PNP >...
  • Page 76 Specifications AF-650 GP Operating Instructions Pulse/encoder inputs: Programmable pulse/encoder inputs Terminal number pulse/encoder 29, 33 / 32 , 33 Max. frequency at terminal 29, 32, 33 110kHz (Push-pull driven) Max. frequency at terminal 29, 32, 33 5kHz (open collector) Min. frequency at terminal 29, 32, 33...
  • Page 77 Specifications AF-650 GP Operating Instructions Control card, USB serial communication: USB standard 1.1 (Full speed) USB plug USB type B “device” plug Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
  • Page 78 EN 61800-3, EN 61000-6-1/2, EMC standards, Immunity EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6 See section on special conditions in the AF-650 GP Design Guide. Please see www.geelectrical.com/drives for more information. Protection and Features: • Electronic thermal motor protection against overload.
  • Page 79: Fuse Tables

    NOTE The recommendations given do not cover Branch circuit protection for UL. Short-circuit protection: GE recommends using the fuses/Circuit Breakers mentioned below to protect service personnel and property in case of component break-down in the drive. Over current protection: The drive provides overload protection to limit threats to human life, property damage and to avoid fire hazard due to overheating of the cables in the installation.
  • Page 80: Ce Compliance

    10.3.2 CE Compliance Fuses or Circuit Breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following. The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V, or 600V depending on the drive voltage rating.
  • Page 81 Specifications AF-650 GP Operating Instructions AF-650 GP 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level [HP] IP20 / Open Chassis gG-16 gG-25 PKZM0-25 gG-20 gG-32 gG-50 gG-63 PKZM4-50 gG-80 gG-125 NZMB1-A100 gG-125 gG-150 NZMB2-A200 aR-160...
  • Page 82 Specifications AF-650 GP Operating Instructions AF-650 GP 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level [HP] IP55 / Nema 12 and IP66 / Nema 4 gG-20 gG-32 PKZM0-25 gG-50 gG-80 PKZM4-63 gG-80 gG-100 NZMB1-A100 gG-125...
  • Page 83 Specifications AF-650 GP Operating Instructions AF-650 GP 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level [HP] IP20 / Open Chassis gG-10 gG-25 PKZM0-25 gG-16 gG-32 gG-35 gG-63 PKZM4-50 gG-63 gG-125 NZMB1-A100 gG-100 gG-150 NZMB2-A200 aR-250...
  • Page 84 Specifications AF-650 GP Operating Instructions AF-650 GP 3-phase Recommended fuse size Recommended max fuse Recommended circuit breaker Max trip level [HP] IP21 / Nema 1 and IP55 / Nema 12 and IP66 / Nema 4 gG-25 gG-32 gG-63 gG-40 gG-80...
  • Page 85 Specifications AF-650 GP Operating Instructions Recommended max. fuse AF-650 GP Ferraz- Ferraz- SIBA Littel fuse Power Shawmut Shawmut Type RK1 Type RK1 Type CC Type RK1 0.33-0.5 5017906-005 KLN-R-05 ATM-R-05 A2K-05-R 5017906-010 KLN-R-10 ATM-R-10 A2K-10-R 5017906-016 KLN-R-15 ATM-R-15 A2K-15-R 5017906-020...
  • Page 86 Specifications AF-650 GP Operating Instructions Recommended max. fuse AF-650 GP Ferraz- Ferraz- Bussmann Littel fuse Shawmut Shawmut JFHR2 Type JFHR2 JFHR2 0.33-0.5 FWX-5 HSJ-6 FWX-10 HSJ-10 FWX-15 HSJ-15 FWX-20 HSJ-20 FWX-30 HSJ-30 FWX-50 HSJ-50 FWX-60 HSJ-60 FWX-80 HSJ-80 20-25 FWX-125...
  • Page 87 Specifications AF-650 GP Operating Instructions Recommended max. fuse Ferraz- Ferraz- AF-650 GP SIBA Littel fuse Shawmut Shawmut [HP] Type RK1 Type RK1 Type CC Type RK1 0.5-1 5017906-006 KLS-R-6 ATM-R-6 A6K-6-R 5017906-010 KLS-R-10 ATM-R-10 A6K-10-R 5017906-020 KLS-R-20 ATM-R-20 A6K-20-R 5017906-025...
  • Page 88 Specifications AF-650 GP Operating Instructions Recommended max. fuse AF-650 GP Bussmann Bussmann Bussmann Bussmann Bussmann Bussmann [HP] Type RK1 Type J Type T Type CC Type CC Type CC KTS-R-5 JKS-5 JJS-6 FNQ-R-5 KTK-R-5 LP-CC-5 KTS-R-10 JKS-10 JJS-10 FNQ-R-10 KTK-R-10...
  • Page 89: Connection Tightening Torques

    Specifications AF-650 GP Operating Instructions Recommended max. fuse Ferraz- Ferraz- Bussmann Bussmann Bussmann SIBA LittelFuse AF-650 GP Max. Shawmut Shawmut E52273 E4273 E4273 E180276 E81895 prefuse E163267/E2137 E2137 RK1/JDDZ J/JDDZ T/JDDZ RK1/JDDZ RK1/JDDZ RK1/JDDZ J/HSJ 30 A KTS-R-30 JKS-30 JKJS-30...
  • Page 90: Index

    Index AF-650 GP Operating Instructions Current Index Limit...................... 24 Rating....................9, 53 A53......................17 A54......................17 Current.................... 7, 47 Link......................52 Input....................7, 14 Mains..................6, 7, 11, 14 Derating....................53, 9 Waveform..................6, 7 Digital Alarm Log..................29, 27 Input....................
  • Page 91 Index AF-650 GP Operating Instructions IEC 61800-3..................... 14 Navigation Keys..............30, 46, 26, 28 Induced Voltage..................12 Noise Isolation................12, 22 Initialisation.................... 29 Input Current....................14 Open Loop..................17, 30 Disconnect..................14 Operation Keys..................28 Power............12, 14, 22, 49, 58, 7, 21 Signal....................
  • Page 92 Index AF-650 GP Operating Instructions Safety Inspection.................. 21 Voltage Level..................72 Screened Control Cables..............16 Serial Communication..6, 11, 15, 16, 28, 29, 46, 47, 48, 49, 20, Warning And Alarm Definitions..............50 Set Up....................... 27 And Alarm Displays................. 49 Setpoint....................
  • Page 93 GE company. AF-650 GP is a trademark of the General Electric Company. 41 Woodford Avenue Plainville, CT 06062 www.geelectrical.com/drives...

Table of Contents