Honeywell Model 700/800 Signal
Processor and Viewing Head
APPLICATION
The Honeywell Model 700ACSP and Model 700DCSP signal
processors are single-channel, fail safe, flame monitoring
systems when used In conjunction with the S70X/S80X
viewing heads. They offer easy setup, excellent discrimination,
and high reliability.
FEATURES
Viewing heads are interchangeable between the two signal
processor models. Any viewing head in the two families will
work with any of the signal processors.
Two signal processor models are available:
• Model 700ACSP Universal 85-265 VAC powered, plus
24VDC backup.
• Model 700DCSP 22-26VDC powered, plus 24VDC backup.
The two Model 700 signal processors are similar, with 12
push-buttons, a two-digit numeric display, and four LED status
indicators for operator interface. The only difference between
the two is that one accepts AC power and the other accepts
DC power. Both models also accept 24VDC backup power.
Most of the signal processor connections are made through
Phoenix plug-in connectors. Communication connections are
made through modular phone jacks located at the top of the
signal processors (Fig. 9).
Both signal processor models mount on a standard 35 mm
DIN rail. They snap into place and may be released from the
rail using a flat screwdriver.
There are two types of viewing heads-IR/flicker-sensitive and
UV-sensitive-with various features offered resulting in ten
different models. See Table 1 on page 2 for details.
The S702 and S706 viewing head housings are larger in
diameter than the S80X series, are made of aluminum, and
are secured with over-center latches to their mounting blocks
(Fig. 10). In contrast, the S802 and S806 viewing head
housings are smaller in diameter and are made of stainless
steel (Fig. 11). An 800 series viewing head is secured in its
mounting block by a friction twist-lock.
The IR/flicker sensitive viewing heads have a high-pass filter
that passes flicker frequencies above 33 Hz. The UV models
respond to the level of UV radiation-not UV flicker-so there
is no filter option.
Application .......................................................................
Features ...........................................................................
Specifications ...................................................................
Approvals .........................................................................
Installation ........................................................................
Operation ......................................................................... 11
Modbus Communication .................................................. 16
Troubleshooting ................................................................ 19
Maintenance .................................................................... 19
Safety Manual: 700 Signal Processor .............................. 35
USER MANUAL
Contents
1
1
2
3
3
66-2069EP-04
Table of Contents
loading

Summary of Contents for Honeywell 700

  • Page 1: Table Of Contents

    • Model 700ACSP Universal 85-265 VAC powered, plus 24VDC backup. • Model 700DCSP 22-26VDC powered, plus 24VDC backup. The two Model 700 signal processors are similar, with 12 push-buttons, a two-digit numeric display, and four LED status indicators for operator interface. The only difference between the two is that one accepts AC power and the other accepts DC power.
  • Page 2: Specifications

    HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Table 1. Available viewing head models and associated features. Pipe Fit Connection High 0.5 in. NPTM with 10-ft UVTron Frequency Aluminum Stainless Steel Model Connector (3 m) pigtail Sensor IR Sensor Filter 155Hz...
  • Page 3: Approvals

    HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD APPROVALS 700ACSP and 700DCSP Signal Processors S70X/S80X Viewing Heads (Connector series and Pipe fit CSA (C, US) series [PF]) CSA for CLASS I, DIV 2, GROUPS A, B, C, D & T4A SIL 3 “Fit for Use”...
  • Page 4 Fig. 2. If no backup battery is to be installed, the main power supply can be connected at +26V In the Model 700 signal processors the flame relay (RF A/B PWR and GND as shown in Fig. 2 or it can be connected to ON, OFF, COM) has two sets of FORM C (SPDT) contacts the +24V BATT input and GND.
  • Page 5 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD +26VDC AC POWER SUPPLY -t° .125 A APPROVED CHASSIS, 0-20 OR 4-20 MA EARTH, OR FOR INDICATOR OR SYSTEM GND INSTRUMENTATION 360 OHMS MAX TO VIEWING HEAD 24 V AC IN BACKUP BATTERY...
  • Page 6 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD +26VDC .125 A APPROVED 0-20 OR 4-20 MA FOR INDICATOR OR INSTRUMENTATION 360 OHMS MAX TO VIEWING CHASSIS, HEAD EARTH, OR SYSTEM GND 24 V DC POWER SUPPLY BACKUP BATTERY 250 MA...
  • Page 7 The PF model comes head, along with ITC/CIC rated raw cable are also available with 10 feet of Honeywell C330S cable. This cable is and listed below. The cable installation must conform to the recommended for all new installations.
  • Page 8 TERMINAL WHITE VH SIG BLACK VH SC VH +V GREEN VH GND SHIELD M34285C Fig. 3. Model 700 Viewing Head Cable With 1/2 in. NPT Fitting. GREEN VH SIG VH SC ORANGE VH +V VH GND METAL CONNECTOR RING VIEWING HEAD...
  • Page 9 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD b. Braided shield is on outside of ferrule, and pressed Connection of the Honeywell type C330S cable to the viewing against housing when assembled. head plug is shown in Fig. 7. Cable preparation should be c.
  • Page 10 Viewing Head Mounting The S70X viewing head lens will withstand 50 psi (3.4 bar) Honeywell offers a range of swivel mounts, both pipe thread or while the S80X lens will withstand 90 psi (6.2 bar), provided flange mounting for use with sight pipes or direct wind box the compression ring on the purge air adapter is tightened mounting.
  • Page 11: Operation

    S55XBE manual, 66-2064. (160°C). USB to RS422/RS485 Converter (COMMOD) - Protocol Swivel mounts, small (700-1, 700-2, 700-3) - All have 1/2 in. converter for use with external communication with a remote NPTM viewing head connections on one end with varying computer.
  • Page 12 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD combustion process as oxygen combines with hydrocarbons 1/2 in. swivel joint, which Honeywell can supply if one is not in the fuel in the blue part of the flame. The yellow part of available (refer to “Accessories”...
  • Page 13 Fig. 27. At LED will be illuminated and the flame relay will be power-up, the 700 signal processors display codes to tell the energized. operator what type of viewing head and what gain is being used.
  • Page 14 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD The two numeric digits on the Model 700 signal processor displayed. Refer to Fig. 25 for the setup flowchart. The FFRT normally display the incoming count during operation; that is, can be set at 1, 2 or 3 seconds. While the value is displayed, the number of pulses that arrive between self-check pulses.
  • Page 15 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD The FFRT (flame failure response time) and the 0/4-20mA The signal processor also adjusts the viewing head gain during output option must be manually setup after the automatic the BNR-ON and BNR-OFF data sampling sequence.
  • Page 16: Modbus Communication

    • 03 Holding register read signal processors. The RS-422 interface IC is a MAX489. The • 06 Preset single holding register ICs can drive up to quantity 32, Model 700 signal processors • 16 Preset multiple holding register on the same bus.
  • Page 17 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Table 4. MODBUS registers map. (Continued) Register Name Description Minimum Maximum 40084 ERRORCODE Error code (read/write) NOTE: writing a non zero number to this register is not allowed 40085 BAUD Baud rate setting (bits/second). Only affects RS-485 communication, not IRDA.
  • Page 18 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SIDE VIEW BOTTOM VIEW WIRE PRODUCT SIDE SIDE USB TO RS422/485 CONVERTER TDA(–) TDB(+) RJ11 CONVERTER COLOR TYPE A COLOR TYPE B DESCRIPTION MODULAR RDA(–) CONNECTOR CONNECTOR RDB(+) RDA (-) FROM PROCESSOR...
  • Page 19: Troubleshooting

    HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD TROUBLESHOOTING Lockout or Faulty VH Indication Since the flame count cannot go this high, the flame relay cannot be energized. The signal processor can be reset by If the viewing head produces any pulses during the last one...
  • Page 20 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 1/2 NPT FOR SIGHTING PIPE 1/2 NPT FOR SIGHTING PIPE HEX 1-1/2 (38) ACROSS FLATS HEX 1-1/2 (38) ACROSS FLATS 1-3/4 (45) DIA MOUNTING BLOCK 1/4 NPT FOR PURGE AIR 1-3/4 (45) DIA MOUNTING BLOCK...
  • Page 21 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD RELAY CONNECTIONS RS-422 WIRING 35MM DIN RAIL 5-1/2 (139) APPROVED DIN RAIL RELEASE 2-29/32 (74) 3-1/4 (83) M34584A Fig. 12. Model 700DCSP Signal Processor. 66-2069EP—04...
  • Page 22 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD RELAY CONNECTIONS RS-422 WIRING MODEL 700AC 35MM DIN RAIL 5-1/2 (139) APPROVED DIN RAIL RELEASE 2-29/32 (74) 3-1/4 (83) M34851A Fig. 13. Model 700ACSP Signal Processor. 66-2069EP—04...
  • Page 23 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD BURNER FRONT PLATE 1 (25) NPT NIPPLE TOE S70X VIEWING HEAD 1/4 (6) NPT PURGE 700-1 SWIVEL MOUNT CONNECTION QUICK DISCONNECT CABLE CONNECTION (SUPPLIED) M34537A Fig. 14. Viewing Head Mounting Example. BURNER FRONT PLATE...
  • Page 24 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD HIGH FREQUENCY FLICKER ZONE DETECTOR IN GOOD SIGHTING POSITION (PARALLEL SIGHTING) BURNER NOZZLE CENTERLINE DETECTOR IN POOR SIGHTING POSITION LOW FREQUENCY FLICKER ZONE M33285B Fig. 16. IR Viewing Head Location UV VIEWING...
  • Page 25 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD NO. 2 FLAME NO. 1 FLAME ENVELOPE ENVELOPE VIEWING HEAD VIEWING HEAD BURNER NOZZLE BURNER NO. 1 NOZZLE NO. 2 HIGH FREQUENCY LOW FREQUENCY HIGH FREQUENCY IR ZONE ZONE (LESS THAN IR ZONE...
  • Page 26 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD RESTORING DEFAULT VALUES LOAD FACTORY PRESS LOAD FACTORY DEFAULTS DEFAULTS FOR 2 SECONDS 2 SECS DISPLAY SHOWS ‘PL’, IS THE PANEL LOCKED? MEANING THE PANEL IS LOCKED NORMAL OPERATION IS THE AUTO SET DISPLAY SHOWS ‘CF’,...
  • Page 27 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD AUTO SETUP BNR-ON PRESS BNR-ON SEQ FOR 2 SECONDS START/END 2 SECS DISPLAY SHOWS ‘PL’ IS THE PANEL LOCKED? UNTIL KEY RELEASED IS THE AUTO SET DISPLAY SHOWS ‘CF’, LIGHT LIT? MEANING CONFIRM...
  • Page 28 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD NOTE: AUTO SETUP - PAGE 2 (CONTINUED) PRESS RESET AT ANY TIME RESET DURING THIS PROCEDURE TO CANCEL AUTO SETUP DISPLAY BEGINS COUNTING DOWN FROM 59 SECONDS BNR-ON PRESS BNR-ON SEQ AGAIN TO END TAKING BURNER...
  • Page 29 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD NOTE: AUTO SETUP - PAGE 3 (CONTINUED) PRESS RESET AT ANY TIME RESET DURING THIS PROCEDURE TO CANCEL AUTO SETUP IS THE AUTO SETUP RATIO MAY BE ACCEPTABLE RATIO MARGINAL? 71% < RATIO < 81% DISPLAY ALTERNATES SHOWING ‘AC’...
  • Page 30 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING RELAY ON VALUE RELAY ON PRESS RELAY ON SET POINT DISPLAY SHOWS CURRENT FOR 2 SECONDS POINT RELAY SETTING 2 SECS INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DECREASE DISPLAY SHOWS ‘PL’...
  • Page 31 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING RATIO PERCENTAGE RATIO (%) PRESS, RATIO (%), DISPLAY SHOWS CURRENT RATIO OFF FOR 2 SECONDS RATIO SETTING IN PERCENT RATIO ON 2 SECS INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DECREASE DISPLAY SHOWS ‘PL’,...
  • Page 32 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING FLAME FAILURE RESPONSE TIME (FFRT) FFRT 1/2/3 SEC PRESS, FFRT, DISPLAY SHOWS CURRENT OPTION FOR 2 SECONDS SETTING IN SECONDS 2 SECS INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DECREASE DISPLAY SHOWS ‘PL’,...
  • Page 33 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING ANALOG OUTPUT LEVELS (0-20/4-20 mA) 0-20 mA PRESS, 0-20 / 4-20 mA OPTION, DISPLAY SHOWS: 4-20 mA FOR 2 SECONDS ‘02’ FOR 0-20 mA OPTION ‘42’ FOR 4-20 mA 2 SECS...
  • Page 34 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING VIEWING HEAD GAIN ACCEPT PRESS ACCEPT RATIO / SET GAIN RATIO DISPLAY SHOWS CURRENT FOR 2 SECONDS SET GAIN GAIN SETTING 2 SECS INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DECREASE DISPLAY SHOWS ‘PL’...
  • Page 35: Safety Manual: 700 Signal Processor

    System Architecture Specific configuration of hardware and software elements in a system. (Average Probability Average Probability of Failure on Demand. In this case, regarding the 700 Signal Processor. of Failure on Demand) FIT (Failures in Time) A unit of measurement representing one failure per billion hours. 1,000,000,000 hours is approximately 114,155.25 years.
  • Page 36 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD As an added safety feature, the coil of the Flame Relay is signal. Each relay must be driven by an alternating signal of wired in series with a second pole of contacts on a Self Check the proper frequency and duty cycle from the processor.
  • Page 37 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 700AC or 700DC Signal Processor Proof Test Procedure Equipment 3. Use a light source to generate a flame on condition and, using a multimeter, ensure continuity between ‘RF A • Powered 700AC or 700DC correctly connected to a COM’...
  • Page 38: Safety Manual: S70X & 80X Viewing Head

    HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SAFETY MANUAL: S70X & 80X VIEWING HEAD S702, S706, S802, AND S806 Product Declaration FIT FOR USE IN A LOW DEMAND SAFETY APPLICATION. Models: S702, S702-PF, S706, S706-PF, S802, S806 λ λ...
  • Page 39 S70X and S80X Viewing Head Proof Test Procedure Equipment Tests 1. 700 or P532 Signal Processor connected to the S702, S706, S802, or S806 viewing head. 2. DC power supply for DC model signal processor and AC NOTE: S702 and S802 viewing heads must be power supply for AC model.
  • Page 40 HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Product Decommissioning a. Increase the gain and store the setting. Ensure the flamecount increased. When required, decommissioning of the S70X and S80X b. Decrease the gain and store the setting. Ensure the viewing heads should be performed in accordance with flamecount decreased.
  • Page 41 • Modelo 700DCSP Universal alimentado por 22-26V CC, além de um backup 24V CC. Os dois processadores de sinal Modelo 700 são semelhantes, com 12 botões, visor numérico de dois dígitos e quatro LEDs indicadores de status para interface com o operador. A única diferença entre os dois é...
  • Page 42 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Tabela 1. Modelos de sensores de chama disponíveis e recursos relacionados. Conexão em Tubo NPTM Filtro de Alta Invólucro de 0,5 pol. com cabo Sensor Frequência de Invólucro de Modelo Conector Pigtail de 3m (10 pés)
  • Page 43 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Dimensões Sensores de Chama S802/S806 (Série de Conectores) Consulte as Figuras 12 e 13. APROVAÇÕES Sensores de Chama S70X/S80X (Série de Conectores, Série de Conexão em Tubo [-PF]) CSA para CLASSE I, DIV 2, GRUPOS A, B, C, D e T4A 15-KA4BO-0197X SIL 3 "Apto para Uso"...
  • Page 44 Na entrada +26V PWR e seu GND associado, fusíveis convencionais 1A são usados por serem capazes de proteger O relé de chama dos processadores de sinal modelo 700 (RF contra 240V CA sendo aplicado por acidente (o que poderia A/B ON, OFF, COM) tem dois conjuntos de contatos FORM C acontecer se um modelo 700DCSP estiver instalado em um (SPDT) e o o relé...
  • Page 45 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 +26VDC AC POWER SUPPLY -t° .125 A APPROVED CHASSIS, TERRA. 0-20 OU 4-20 MA OU GND DO SISTEMA PARA INDICADOR OR INSTRUMENTAÇÃO 360 OHMS MAX PARA SENSOR DE CHAMA BATERIA DE...
  • Page 46 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 +26VDC .125 A APPROVED 0-20 OU 4-20 MA PARA INDICADOR OU INSTRUMENTAÇÃO 360 OHMS MÁX CHASSIS, TERRA PARA SENSOR OU GND DO DE CHAMA SISTEMA BATERIA ALIMENTAÇÃO DE BACKUP 24 V...
  • Page 47 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Conector e Montagem Elétrica do AVERTISSEMENT Sensor de Chama RISQUE D'EXPLOSION Sensores de chama devem ser ligados aos respectivos NE PAS DEBRANCHER TANT QUE LE CIRCUIT EST terminais localizados na parte inferior dos processadores de SOUS TENSION, A MOINS QU'lL NE S'AGISSE sinal 700DCSP, P531 e P532.
  • Page 48 PRETO VH SC VERMELHO VH +V VERDE VH GND BLINDAGEM MP34285C Fig. 3. Cabo do Sensor de Chama Modelo 700 com conexão NPT de 1/2 pol. VH SIG VH SC VERDE VH +V LARANJA VH GND ANEL CONECTOR DE METAL...
  • Page 49 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 4. Desencape os outros fios, como mostrado na Fig. 5. b. Blindagem de malha trançada encontra-se fora da virola e é pressionada contra o invólucro quando A conexão do cabo Honeywell C330S ao conector do sensor montado.
  • Page 50 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 de chama não esteja conectado. Isso é útil na solução de classificação de serviço contínuo de 160°C (320°F), bem problemas. como um niple Ultem NPTM de 1/2 pol. (número de peça R-...
  • Page 51 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 linha de centro do queimador. O uso de uma rótula de ajuste Acoplador com trava (R-518-CL13-HTG) - Usado com permite o ajuste do posicionamento, quando for conveniente acopladores com trava isolante R-518-PT13 e R-518-PT13L.
  • Page 52 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 OPERAÇÃO com o detector de IR. (Consulte a seção anterior "Detector IR".) A intensidade mais elevada UV ocorre perto da origem da chama (Fig. 17). Além disso, a zona de maior intensidade Detector IR da radiação UV não se sobrepõe às zonas adjacentes ou...
  • Page 53 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Indicadores LED e Visor do Painel Frontal na parte traseira do sensor de chama deve ser razoável. Para versões -PF (conexão em tubo), não há LEDs. Logo, o • LED ON SEQ/AUTO SET (verde): instalador deve observar o sinal de chama no processador de —...
  • Page 54 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Relay On Setpoint • Botão ACCEPT RATIO/SET GAIN: — Permite o usuário definir o ganho do sensor de chama Os dois dígitos numéricos no processador de sinal Modelo em conjunção com os botões INCREASE, 700 normalmente exibem a medição durante sua operação;...
  • Page 55 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Configuração Automática de Configurando FFRT (Tempo de Resposta de Falha da Chama) Setpoints Para acessar o setpoint FFRT, pressione e segure o botão Com esse recurso, os processadores de sinal Modelo 700 FFRT 1/2/3 SEC OPTION por 2 segundos até...
  • Page 56 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 proporção é armazenada, e o AUTO SET LED é ligado. Se Tabela 3. Configurações Padrão do S70X/S80X RESET é pressionado, o visor retorna para a medição, os dois AUTO SETUP LEDs são desligados e os setpoints Relay on setpoint anteriores são usados.
  • Page 57 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 OBSERVAÇÃO: O Protocolo padrão deve ser alterado para Quatro funções Modbus são suportadas: comunicação Modbus ser utilizada. Ele pode • 01 Leitura de bobina de saída ser ajustado para Modbus usando a seguinte •...
  • Page 58 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 BOILER BNR 1 BNR 2 BNR 3 BNR 4 BNR 5 BNR 6 ADDRESS BNR 1 BNR 2 BNR 3 BNR 4 ADDRESS BOILER 3 CONTROLE MESTRE MODBUS OBSERVAÇÕES: UM CONVERSOR PODE SER NECESSÁRIO PARA COMUNICAÇÕES COM O CONTROLE MESTRE MODBUS.
  • Page 59 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 SOLUÇÃO DE PROBLEMAS Indicação de Bloqueio ou Falha do dados, exibe "EE" e carrega os padrões de fábrica. O RELAY ON SETPOINT é definido para 31. Como a medição de chama não pode ir tão alto, o relé...
  • Page 60 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 1/2 NPT PARA TUDO DE VISUALIZAÇÃO 1/2 NPT PARA TUDO DE VISUALIZAÇÃO CHAVE SEX. 1-1/2 (38) CHAVE SEX. 1-1/2 (38) BASE MONTAGEM DIÂM. 1-3/4 (45) 1/4 NPT PARA AR DE PURGA BASE MONTAGEM DIÂM.
  • Page 61 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 CONEXÕES DE RELÉ FIAÇÃO RS-422 TRILHO DIN 35MM 5-1/2 (139) APPROVED LIBERAÇÃO DO TRILHO DIN 2-29/32 (74) 3-1/4 (83) MP34584 Fig. 12. Processador de Sinal Modelo 700DCSP. 66-2069EP—04...
  • Page 62 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 CONEXÕES DE RELÉ FIAÇÃO RS-422 MODEL 700AC TRILHO DIN 35MM 5-1/2 (139) APPROVED LIBERAÇÃO DO TRILHO DIN 2-29/32 (74) 3-1/4 (83) MP34851 Fig. 13. Processador de Sinal Modelo 700ACSP. 66-2069EP—04...
  • Page 63 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 PLACA FRONTAL DO QUEIMADOR NIPLE TOE 1 (25) NPT SENSOR DE CHAMA S70X CONEXÃO AR DE PURGA 1/4 (6) NPT RÓTULA DE AJUSTE 700-1 CONEXÃO DE RÁPIDO DESENGATE (FORNECIDO) MP34537 Fig.
  • Page 64 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 ZONA DE TREMULAÇÃO DE ALTA FREQUÊNCIA SENSOR EM BOA POSIÇÃO (PARALELO À CHAMA) EIXO DO BICO DO QUEIMADOR SENSOR EM POSIÇÃO DESFAVORÁVEL ZONA DE TREMULAÇÃO DE BAIXA FREQUÊNCIA MP33285 Fig. 16. Posicionamento do Sensor de Chama IR ZONA DE RADIAÇÃO UV...
  • Page 65 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Nº 2 ZONA Nº 1 ZONA DA CHAMA DA CHAMA SENSOR DE CHAMA SENSOR DE CHAMA N° 1 BICO DE QUEIMADOR N° 2 BICO DE QUEIMADOR ZONA DE IR DE ALTA...
  • Page 66 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 RESTAURAÇÃO DE VALORES PADRÃO LOAD PRESSIONE LOAD FACTORY DEFAULTS FACTORY (CARREGAR PADRÕES DE FÁBRICA) DEFAULTS POR 2 SEGUNDOS 2 SEG O VISOR EXIBE 'PL', QUE SIGNIFICA QUE O PAINEL ESTÁ...
  • Page 67 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 AUTO SETUP BNR-ON PRESSIONE BNR-ON SEQ POR 2 SEGUNDOS START/END 2 SEG O VISOR EXIBE 'PL' ATÉ A O PAINEL ESTÁ BLOQUEADO? TECLA SER LIBERADA Não O VISOR EXIBE 'CF',...
  • Page 68 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 OBSERVAÇÃO: AUTO SETUP - PÁGINA 2 PRESSIONE RESET A QUALQUER (CONTINUAÇÃO) MOMENTO DURANTE ESSE PROCESSO RESET PARA CANCELAR O AUTO SETUP (CONFIGURAÇÃO AUTOMÁTICA ) O VISOR COMEÇA A CONTAGEM REGRESSIVA DE...
  • Page 69 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 AUTO SETUP OBSERVAÇÃO: (CONFIGURAÇÃO AUTOMÁTICA) - PRESSIONE RESET A QUALQUER MOMENTO PÁGINA 3 (CONTINUAÇÃO) DURANTE ESSE PROCESSO RESET PARA CANCELAR O AUTO SETUP (CONFIGURAÇÃO AUTOMÁTICA ) A CONFIGURAÇÃO AUTOMÁTICA DE A PROPORÇÃO PODE SER...
  • Page 70 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 CONFIGURAÇÃO DO VALOR DO RELAY ON RELAY ON PRESSIONE RELAY ON SET O VISOR EXIBE A ATUAL POINT POR 2 SEGUNDOS CONFIGURAÇÃO DO RELÉ POINT 2 SEG INCREASE USE AS TECLAS INCREASE OU DECREASE PARA AJUSTAR A CONFIGU- RAÇÃO...
  • Page 71 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 CONFIGURAÇÃO DE PORCENTAGEM DE RATIO RATIO (%) PRESSIONE RATIO (%) VISOR EXIBE A CONFIGU- RATIO OFF POR 2 SEGUNDOS RAÇÃO ATUAL DE RATIO EM RATIO ON PORCENTAGEM 2 SEG INCREASE...
  • Page 72 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 CONFIGURANDO O FFRT (TEMPO DE RESPOSTA DE FALHA DE CHAMA) FFRT PRESSIONE FFRT POR O VISOR EXIBE A CONFIGU- 1/2/3 SEC 2 SEGUNDOS RAÇÃO ATUAL EM SEGUNDOS OPTION 2 SEG...
  • Page 73 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 CONFIGURAÇÃO DE NÍVEIS DE SAÍDA ANALÓGICA (0-20/4-20 mA) 0-20 mA PRESSIONE 0-20/4-20 mA O VISOR EXIBE: 4-20 mA OPTION POR 2 SEGUNDOS ‘02’ PARA 0-20 mA OPTION ‘42’ PARA 4-20 mA...
  • Page 74 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 CONFIGURAÇÃO DE GANHO DO SENSOR DE CHAMA ACCEPT PRESSIONE ACCEPT RATIO / SET RATIO O VISOR EXIBE A ATUAL GAIN POR 2 SEGUNDOS CONFIGURAÇÃO DE GANHO SET GAIN 2 SEGS...
  • Page 75 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 MANUAL DE SEGURANÇA: PROCESSADOR DE SINAL 700 Declaração de Produto 700ACSP e 700DCSP PARA USO EM APLICAÇÕES DE SEGURANÇA DE BAIXA DEMANDA. Modelos: 700ACSP e 700DCSP λ λ λ Modelos 700AC >99%...
  • Page 76 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 • O Relé de Chama será desenergizado quando o Além disso, um outro recurso de segurança é que o relé não processador de sinal for ligado e detectar uma condição de pode ser ativado por um sinal simples continuamente alto ou defeito.
  • Page 77 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Procedimento de Teste de Verificação dos Processadores de Sinal 700AC e 700DC Equipamento haja continuidade entre 'RF A COM' e 'RF A ON', e entre 'RF B COM' e 'RF B ON'.
  • Page 78 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 MANUAL DE SEGURANÇA: SENSOR DE CHAMA S70X E 80X Declaração de Produto S702, S706, S802 e S806 PARA USO EM APLICAÇÕES DE SEGURANÇA DE BAIXA DEMANDA. Modelos: S702, S702-PF, S706, S706-PF, S802, S806 λ...
  • Page 79 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 Função de Segurança do S702, S706, Intervalo de Teste de Verificação dos S802 e S806 Sensores de Chama S70X e S80X Os sensores de chama S702, S706, S802 e S806 não O teste de verificação precisa ser conduzido a cada 1 a 5...
  • Page 80 PROCESSADOR DE SINAL E SENSOR DE CHAMA HONEYWELL MODELO 700/800 3. Cubra a extremidade do sensor de chama com sua mão b. Reduza o ganho e armazene a configuração. e assegure-se de que o processador de sinal indique Certifique-se de que a medição de chama seja uma medição de chama "zero".