Automation platform
Hide thumbs Also See for COM600:

Quick Links

Power Products
Station Automation COM600
Product Guide
Table of Contents
loading

Summary of Contents for ABB COM600

  • Page 1 Power Products Station Automation COM600 Product Guide...
  • Page 2: Table Of Contents

    9. Substation integration ....9 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    The automation platform with both simple control programs and more so- its logic processor makes COM600 a flexible phisticated applications like load shedding or implementation platform for substation-level fault isolation and network restoration.
  • Page 4: Application

    Ethernet switch TCP/IP protocols Serial protocols (IEC 61850, DNP3, (DNP3, Modbus ® Modbus SPA) ® REM 543 RTU/PLC RTU/PLC REF 542plus REF 542plus DPU2000R NON-ABB NON-ABB REF615 REF615 REF 543 Fig. 2 Overview of a utility substation using Station Automation COM600...
  • Page 5: Parameter Setting

    NON-ABB REF615 REF615 REF 543 Fig. 3 Overview of an industrial system using Station Automation COM600 The single line diagram can be configured different serial protocols. For example 3 SPA to include an indication for the local/remote + 1 IEC 101 protocol or 2 SPA + 1 IEC 103 +1 selection switch.
  • Page 6: Event And Alarm Lists

    8 Ethernet switch Ethernet switch Fig. 4 Application example the web HMI of COM600 limiting the number disturbance records are saved in the stand- of visible parameters to the ones that are ard COMTRADE format. In-depth analysis considered important for the user. Changes in is enabled using ABB’s Wineve software or...
  • Page 7 Station Automation 1MRS756764 B COM600 Product version: 3.4 Fig. 5 COM600 web HMI showing persisting and fleeting alarms Fig. 6 COM600 Data historian...
  • Page 8: Logic Processor

    The optional data of all bus breakers, if one of the breakers historian functionality offers means of stor- fails to clear the fault. COM600 collects any ing, analyzing and presenting process data. analog or binary IED data using standard...
  • Page 9: Substation Integration

    COM600 provides connectivity to a range minimizing device configuration and set-up of ABB systems. The connectivity to ABB’s times. The engineering in COM600 is done by low voltage motor control center MNS iS is selecting the connectivity package for the IED provided using an OPC server in COM600.
  • Page 10: Communication Redundancy

    IEDs. tions. IEC 62439/PRP-based communication requires that COM600 is equipped with the Using the Station Automation Builder 600 optional LAN card and that the IEDs used (SAB600) tool provided with COM600 on- support PRP.
  • Page 11: Technical Data

    Station Automation 1MRS756764 B COM600 Product version: 3.4 13. Technical data Table 1. Dimensions Description Value Width 214 mm (243 mm with mounting kit) Height 122,4 mm (129.4 mm with mounting kit) Depth 313 mm Weight 6.8 kg Table 2. Power supply...
  • Page 12 Station Automation 1MRS756764 B COM600 Product version: 3.4 Table 6. Inspection of mechanical structure Description Standard Markings and mechanical structure According to IEC 60255-5, -6 Degree of protection by enclosure According to IEC 60529 Clearance and creepage distances According to IEC 60255-5 Table 7.
  • Page 13 Station Automation 1MRS756764 B COM600 Product version: 3.4 Electrostatic discharge test According to IEC 61000-4-2, IEC 60255-22-2 • Contact discharge 6 kV • Air discharge 8 kV Radio frequency field immunity According to IEC 61000-4-3 and IEC 60255-22-3 10 V/m (80% amp.mod.) f=80...1000 MHz 10 V/m (pulse mod.) f=900...
  • Page 14 Station Automation 1MRS756764 B COM600 Product version: 3.4 Table 11. Environmental tests Description Standard Dry heat test According to IEC 60068-2-2 Test values: • 96 h at +55ºC • 4 h at +70ºC Cold test According to IEC 60068-2-1 Test values: • 96 h at -10ºC • 4 h at -25ºC Damp heat test, cyclic According to IEC 60068-2-30 Test values: • 6 cycles (12+12h) at...
  • Page 15 Station Automation 1MRS756764 B COM600 Product version: 3.4 Seismic test According to IEC 60255-21-3 test method B • biaxial multi-frequency random seismic test 2 x gn in horizontal direction, 1 x gn in vertical direction Table 13. EMC compliance Complies with the EMC directive 2004/108/EC...
  • Page 16 Station Automation 1MRS756764 B COM600 Product version: 3.4 Table 17. IEDs with connectivity packages supporting COM600 610 series IEDs Feeder Protection REF610 Motor Protection REM610 Voltage Protection REU610 615 series IEDs Feeder Protection Relay REX 521 SPAJ 140 series relays...
  • Page 17: Tools

    COM600 and the IEDs. The connectivity pack- finalized projects are updated from SAB600 ages for ABB’s protection and control IEDs to COM600 at site or remotely provided that a enable an efficient configuration of COM600. secure Ethernet connection is available.
  • Page 18: Ordering

    Slave protocols One slave protocol Two slave protocols None Optional software Data historian Logic processor Data historian and Logic processor None Version Version 3.4 Requires Web HMI and Internet Explorer 6.0 or later Fig. 12 Ordering key for Station Automation COM600...
  • Page 19: References

    You will find the latest relevant information on the COM600 unit on the product page. The download area on the right hand side of the web page contains the latest product Fig.
  • Page 20 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation ABB Inc. Distribution Automation 655 Century Point Lake Mary, Florida, U.S.A. Phone 407-732-2000 407-732-2335 www.abb.com/substationautomation...