Before Performing Failure Diagnosis; Error Code List; List Of Error Codes For Errors Detected By The - Mitsubishi Electric AE-200A Service Handbook

Hide thumbs Also See for AE-200A:
Table of Contents
[V Troubleshooting]

[1] Before performing failure diagnosis

If the AE-200/AE-50/EW-50 is not operating normally, first check the following items.
(The following items are for the maximum system configuration. Just check the items for the applicable equipment.)
No.
Are the AE-200/AE-50/EW-50, PC, PLC, HUB, power supply unit, and other equipment and
1
air-conditioning units powered on?
Is a power cable or transmission line disconnected?
2
Is 100 to 240 VAC applied on the AC power cable of the AE-200/AE-50/EW-50?
3
Is 17 to 32 VDC applied on the M-NET transmission line?
4
Have the initial settings been configured for the AE-200/AE-50/EW-50 and each equipment?
5
Are the correct date and time set on the AE-200/AE-50/EW-50?
6
Is the required license number registered for each AE-200/AE-50/EW-50?
7
Is a LAN cable disconnected?
8
(Are the LAN cables compliant with the relevant standards?)
Is the IP address of each equipment set?
9
Is a terminal screws loose or a connector not inserted properly?
10
If you answered "No" for any of the above items, remove the cause for that item.
If there is no problem, refer to the following sections.

Error code list

[2]
1. List of error codes for errors detected by the AE-200/AE-50/EW-50
The following shows the error codes of errors detected by the AE-200/AE-50/EW-50.
Error code
Version combination error
0092
System configuration change warning
0093
"Charge" license not registered
0094
Warning - possibility of damaged metering
0095
device
Apportioned calculation data collection error
0097
External memory read/write error
6204
Communication error - Address duplicate
6600
Communication error - Polarity unsettled
6601
Communication error - Transmission processor
6602
hardware error
Communication error - Transmission line busy
6603
Communication error - Transmission processor
6606
communication error
Communication error - No ACK return
6607
Communication error - No return of response
6608
frame
Communication error - No response
6920
System abnormality - Attribute setting error
7106
System abnormality - Connection setting error
7109
Version error
7905
For details on the error codes, refer to "V [3] Troubleshooting and solutions depending on the equipment."
[Supplementary explanation] Error codes 0092 to 0095 and 0097 are for error occurrences of the AE-200 and are stored in the error
Item
Error description
history.
Error codes 6607 and 6608 are detected only by the AE-200/AE-50/EW-50 and are for error
occurrences of the AE-200/AE-50/EW-50 and are stored in the error history.
Unit where error occurred
46
Yes
No
Remarks
AE-200 only
AE-200 only
AE-200 only
AE-200 only
AE-200 only
Table of Contents
loading

This manual is also suitable for:

Ae-200eAe-50eEw-50eEw-50aAe-50a

Table of Contents