Panasonic CU-8ME1XPK Installation Manual

Urban multi heat recovery inverter series
Hide thumbs Also See for CU-8ME1XPK:

INSTALLATION MANUAL

PACKAGED AIR CONDITIONER
Model No.
(Urban Multi Heat recovery inverter series)
CU-8ME1XPK
CU-10ME1XPK
REFRIGERANT
R407C
Table of Contents
loading

Summary of Contents for Panasonic CU-8ME1XPK

  • Page 1: Installation Manual

    INSTALLATION MANUAL PACKAGED AIR CONDITIONER Model No. (Urban Multi Heat recovery inverter series) CU-8ME1XPK CU-10ME1XPK REFRIGERANT R407C...
  • Page 2: Table Of Contents

    Connecting the refrigerant piping ........... 4 This installation manual concerns UM heat recovery of the Selection of piping material ............4 Panasonic “CU-∗∗ME1XPK” series. These units are designed for Example of connection ..............5 outdoor installation and used for cooling and heatpump Leak test and vacuum drying ............
  • Page 3: Standard Supplied Accessories

    Technical specifications (1) Standard supplied accessories (see figure10) General CU-8ME1XPK CU-10ME1XPK CU-∗∗ME1XPK 8/10 Nominal cooling capacity (2) (kW) 22.4 28.0 Nominal heating tie-wrap (1) capacity (3) (kW) 25.0 31.5 Nominal input cooling/heating (4) (kW) 9.43/8.66 11.8/11.0 gas side attached pipe (2)
  • Page 4: Main Components

    2. Lift the unit preferably with a crane AIN COMPONENTS and 2 belts(1) of at least 8m long. For main components and function of the main components, refer 3. When lifting the unit with a crane, always use protectors(2) to to the Engineering Data Book.
  • Page 5: Connecting The Refrigerant Piping

    Connecting the refrigerant piping 5. Protection against contamination when installing pipes - Take measures to prevent foreign materials like moisture and contamination from mixing into the system. 1. Installation of refrigerant piping is possible as front connection, side connection and bottom connection. Place Installation period Protection method...
  • Page 7: Leak Test And Vacuum Drying

    - This outdoor unit is factory charged with refrigerant and Leak test and vacuum drying depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant. The units were checked for leaks by the manufacturer. - Charge the refrigerant to the liquid pipe in its liquid state. Since Confirm that the valves are firmly closed before pressure test or R407-C is a mixed refrigerant, its composition changes if vacuuming.
  • Page 8: Internal Wiring - Parts Table

    K1R ....Magnetic relay (K2M) (A1P) Phase and Recommended Transmission Voltage K1R ....Magnetic relay (Y5S) (A3P) frequency fuses line section K2R, 3R .... Magnetic relay (M1F) (A1P) CU-8ME1XPK 3N~50Hz 380-415V 35 A 0.75~1.25mm K2R ....Magnetic relay (Y6S) (A3P) CU-10ME1XPK 3N~50Hz 380-415V 35 A 0.75~1.25mm...
  • Page 9: Examples

    Sequential start Examples Make the outdoor unit cable connections shown below. System example (refer to figure 5) The outdoor unit PC board (A1P) is factory set at “Sequential start available”. 1 field power supply 2 main switch 3 earth leak detector 4 fuse 5 HR box 6 indoor unit...
  • Page 10: Before Operation

    EFORE OPERATION Operation check - Temperature regulating operation check 1. Perform the cross wiring - cross piping check as described in Checks before initial start-up “ ” attached on the rear of the upper front CAUTIONS ON OPERATION panel. 2. Set the unit to “ ” mode using the cool/heat selector (heatpump units only) or the indoor remote controller.
  • Page 11: Caution For Refrigerant Leaks

    How to operate stop valves (refer to figure 11) Maximum concentration level 1. To open The maximum charge of refrigerant and the calculation of the 1. Remove the cap (1) and turn the shaft (2) counterclockwise with maximum concentration of refrigerant is directly related to the hexagon socket screw keys (JIS B 4648 nominal size 6 mm and humanly occupied space in to which it could leak.
  • Page 12 4. Dealing with the situations where the result exceeds the maximum concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system. Please consult your Panasonic supplier.
  • Page 13 3VA11386-1B EM01A145 (0110) HT...

This manual is also suitable for:

Cu-10me1xpk