An Example Of A System To Which An Ma Remote Controller Is Connected - Mitsubishi Electric CMB-PW202V-J Service Handbook

Table of Contents
[ II Restrictions ]

[3] An Example of a System to which an MA Remote Controller is connected

1. System with one outdoor unit (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
TB3
M1 M2
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) When the number of the connected indoor units is as
shown in the table below, one or more transmission
boosters (sold separately) are required.
To connect two transmission boosters, connect them in
parallel. (Observe the maximum number of connectable
indoor units that are listed in the specifications for each
outdoor unit.)
When the P200 and P250 mod-
els are not included in the con-
nected indoor units
When the P200 and P250 mod-
els are included in the connect-
ed indoor units
HWE09070
L1
L2
OC
BC
00
00
TB02
TB7
M1 M2
S
M1 M2 S
Group
A1 B2
MA
Number of transmission
booster (sold separately) re-
quired
1 unit
2 units
27 - 50 units
21 - 39 units
40 - 50 units
L3
Group
IC
00
TB5
TB15
M1 M2
S
1 2
A1 B2
MA
L12
IC
00
TB5
TB15
M1 M2
S
1 2
A1 B2
A1 B2
MA
MA
4) Automatic address setup is not available if start-stop in-
put(CN32, CN51, CN41) is used for a group operation of
indoor units. Refer to section "[5] 2. Manual address set-
up for both indoor and outdoor units" in the R2 service
handbook.
5) To connect two or more LOSSNAY units to a system, re-
fer to the next section "[5] 2. An example of a system with
one outdoor unit to which 2 or more LOSSNAY units are
connected" in the R2 service handbook.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L1 +L2+L3+L4 200m [656ft]
L1 +L2+L3+L11+L12+L13 200m [656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
-
Maximum overall line length
(0.3 to 1.25mm
m1 200m [656ft]
m2+m3 200m [656ft]
m4+m5 200m [656ft]
- 20 -
Interlock operation with
the ventilation unit
L4
Group
LC
IC
00
00
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A1 B2
A1 B2
RC
MA
L13
Group
IC
IC
00
00
TB5
TB15
TB5
M1 M2
M1 M2
S
1 2
S
A1 B2
MA
m3
2
[AWG16] or larger)
2
[AWG22 to 16])
TB15
1 2
GB
Table of Contents
loading

Table of Contents