Fujitsu AS*G07LECA Design & Technical Manual

Wall mounted type
Hide thumbs Also See for AS*G07LECA:

Quick Links

AIR CONDITIONER

Wall Mounted type

DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AS  G07LECA
AS  G09LECA
AS  G12LECA
AO  G07LEC
AO  G09LEC
AO  G12LEC
AS  G14LECA
AO  G14LEC
Table of Contents
loading

Summary of Contents for Fujitsu AS*G07LECA

  • Page 1: Air Conditioner

    AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS  G07LECA AS  G14LECA AS  G09LECA AS  G12LECA OUTDOOR AO  G07LEC AO  G14LEC AO  G09LEC AO  G12LEC...
  • Page 2 1. INDOOR UNIT WALL MOUNTED TYPE : ASG07LECA ASG09LECA ASG12LECA ASG14LECA DTR_AS049E_03 2011.03.23...
  • Page 3: Table Of Contents

    CONTENTS 1. INDOOR UNIT 1. FEATURE ........................01 - 01 2. WIRELESS REMOTE CONTROLLER ..........01 - 04 3. SPECIFICATIONS ....................01 - 06 4. DIMENSIONS ......................01 - 07 5. WIRING DIAGRAMS ..................01 - 10 6. CAPACITY TABLE .....................01 - 11 6-1.
  • Page 4: Indoor Unit

    FEATURE MODEL „ „ ASG07LECA / AOG07LEC ASG09LECA / AOG09LEC ASG12LECA / AOG12LEC AS  G07LECA AS  G14LECA ASG14LECA / AOG14LEC AS  G09LECA AS  G12LECA AO  G07LEC AO  G14LEC AO  G09LEC FEATURES AO  G12LEC „...
  • Page 5: Powerful Operation

    10°C HEAT Operation „ The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied Caution) • When the room temperature is higher than 10°C, “10°C HEAT” operation does not start. Operation starts and maintains the room temperature at 10°C when the temperature drops below 10°C.
  • Page 6 Air conditioner filter features „ Dirty Air Ion Deodorization Filter Apple-catechin Filter Clean Air Long-life Ion Apple- Deodorization Filter catechin Filter Easy maintenance „ Easy maintenance and always clean. Troublesome maintenance has been made easy. Since the front panel is easy to remove, maintenance is also easy. - (01 - 03) -...
  • Page 7: Wireless Remote Controller

    WIRELESS REMOTE CONTROLLER FEATURES „ „ Four kinds of timer setup  „ (On / Off / Program / Sleep) are possible. Four kinds of timers. Easy operation.  „ Easy to change transmission code (4 patterns) by button operation. ...
  • Page 8 FUNCTIONS „ „ Signal Transmitter 10 °C HEAT button MODE button ECONOMY button OUTDOOR UNIT LOW NOISE button ON TIMER button OFF TIMER button CLOCK ADJUST button POWERFUL button SET TEMP. button ( START/STOP button FAN button SWING button SET button SLEEP TIMER button CANCEL button RESET button...
  • Page 9: Specifications

    SPECIFICATIONS WALL MOUNTED Type INVERTER HEAT PUMP Model name AS  G07LECA AS  G09LECA AS  G12LECA AS  G14LECA Power source 230V~ 50Hz Available voltage range 198-264V~ 50Hz Cooling European energy label Heating 2.10 2.50 3.40 4.00 Rated BTU/h 7,200 8,500...
  • Page 10: Dimensions

    DIMENSIONS MODEL : ASG07LE, ASG09LE, ASG12LE „ „ (Unit : mm) - (01 - 07) -...
  • Page 11 MODEL : ASG14LE „ „ (Unit : mm) Outline of unit 353: Gas pipe ø2-65 ø2-65 for pipe inlet for pipe inlet 415: Liquid pipe - (01 - 08) -...
  • Page 12 INSTALLATION PLACE „ „ (Unit : mm) Outline of unit 48 or more 52 or more 100 or more 70 or more 1500 or more - (01 - 09) -...
  • Page 13: Wiring Diagrams

    WIRING DIAGRAMS MODEL : ASG07LE, ASG09LE, ASG12LE, ASG14LE „ „ - (01 - 10) -...
  • Page 14: Capacity Table

    CAPACITY TABLE 6-1. COOLING CAPACITY MODEL : ASG07LE „ „ 11.5 Indoor temperature °CDB °CWB °CDB 1.97 1.22 0.33 2.19 1.23 0.34 2.26 1.33 0.34 2.41 1.34 0.34 2.49 1.45 0.34 2.64 1.44 0.35 2.79 1.53 0.35 1.87 1.16 0.37 2.08 1.17 0.38...
  • Page 15: Heating Capacity

    6-2. HEATING CAPACITY MODEL : ASG07LE „ „ 11.8 Indoor temperature (°CDB) (°CDB) (°CWB) 2.25 0.99 2.19 1.01 2.14 1.03 2.09 1.05 2.03 1.07 2.56 1.02 2.50 1.04 2.43 1.06 2.37 1.08 2.31 1.11 2.93 1.05 2.86 1.07 2.79 1.10 2.72 1.12 2.65...
  • Page 16: Fan Performance

    FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION Note: Fan speed : High MODEL : ASG07LE, ASG09LE, ASG12LE „ „ Operation mode : FAN Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Center Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Right &...
  • Page 17 Note: Fan speed : High MODEL : ASG14LE „ „ Operation mode : FAN Unit : m/s TOP VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Center Unit : m/s TOP VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Right & Left Unit : m/s SIDE VIEW VERTICAL FLAP : Upward...
  • Page 18: Air Flow

    7-2. AIR FLOW MODEL : ASG07LE, ASG09LE, ASG12LE „ „ Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1400 1200 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1440 1200 QUIET - (01 - 15) -...
  • Page 19 MODEL : ASG14LE „ „ Cooling „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1400 1230 1000 QUIET Heating „ Number of Fan speed rotations Air flow (r.p.m.) HIGH 1400 1230 1050 QUIET - (01 - 16) -...
  • Page 20: Operation Noise

    OPERATION NOISE 8-1. NOISE LEVEL CURVE MODEL : ASG07LE „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 High High NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 Quiet Quiet 1,000 2,000...
  • Page 21 MODEL : ASG12LE „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 High NC-40 NC-40 High NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 Quiet Quiet 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 22: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT - (01 - 19) -...
  • Page 23: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model name ASG07LE ASG09LE ASG12LE ASG14LE Voltage 230~ Power supply Frequency Max. operating current Connection cable 1.0-1.5 *1)Wiring Spec. Limited wiring length *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) - (01 - 20) -...
  • Page 24: Safety Devices

    SAFETY DEVICES Model ASG07LE Protection form ASG09LE ASG12LE ASG14LE Circuit protection Current fuse (PCB) 3.15A 250V Terminal protection Current (thermal) fuse 3A 250V °C OFF Fan motor protection Thermal protector program °C ON - (01 - 21) -...
  • Page 25: External Input & Output

    EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CN303 Control input See external input/output settings CN304 Operation status output for details. 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) „ „ The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
  • Page 26 When function setting is "Forced stop" mode „ Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity Parts (Optional) „ Parts name Model name External connect kit UTY-XWZX UTY-XCBXE (for AS  G07/09/12LE) Communication box kit UTY-XCBXZ1 (for AS ...
  • Page 27: External Output

    11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT „ „ An air conditioner operation status signal can be output. Circuit diagram example „ Indoor control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *10 m Signal Optional parts Field supply...
  • Page 28: Function Setting

    FUNCTION SETTING 12-1. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “FUNCTION SETTING”...
  • Page 29: Function Details

    FUNCTION DETAILS „ „ Compact wall Functions mounted 1) Filter sign 2) Cooler room temperature correction 3) Heater room temperature correction 4) Auto restart Indoor room temperature sensor switching function 6) Remote controller signal code 7) External input control 1) Filter sign The indoor unit has a sign to inform the user that it is time to clean the filter.
  • Page 30 4) Auto restart Enable or disable automatic system restart after a power outage. (  ... Factory setting) Setting description Function number Setting value  * Auto restart is an emergency function such as for power failure etc. Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
  • Page 31 REMOTE CONTROLLER SIGNAL CODE SETTING „ „ Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) Press the START/STOP button until only the clock is displayed on the remote controller display.
  • Page 32: Optional Parts

    OPTIONAL PARTS Exterior Parts name Model No. Summary Unit control is performed by Wired remote wired remote controller. UTY-RNNYM controller *Optional communication kit is necessary for the installation. Unit control is performed by Simple remote simple remote controller. UTY-RSNYM controller *Optional communication kit is necessary for the installation.
  • Page 33: Outdoor Unit

    2. OUTDOOR UNIT SINGLE TYPE : AOG07LEC AOG09LEC AOG12LEC AOG14LEC DTR_AO072E_02 2011.03.03...
  • Page 34 CONTENTS 2. OUTDOOR UNIT 1. SPECIFICATIONS ....................02 - 01 2. DIMENSIONS ......................02 - 02 3. REFRIGERANT CIRCUIT ................02 - 04 4. WIRING DIAGRAMS ..................02 - 05 5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE ..............
  • Page 35: Specifications

    SPECIFICATIONS Type INVERTER HEAT PUMP Model name AO  G07LEC AO  G09LEC AO  G12LEC AO  G14LEC Power sourse 230V~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current Cooling 1,720 1,830 1,800 Airflow rate Heating 1,510 1,600 1,660 Type×Q'ty Propeller fan×1...
  • Page 36: Dimensions

    DIMENSIONS MODEL : AOG07LE, AOG09LE, AOG12LE „ „ (Unit : mm) INSTALLATION PLACE „ „ When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides. the back, side(s), and top. back, side with the installation of more than one unit.
  • Page 37 MODEL : AOG14LE „ „ (Unit : mm) INSTALLATION PLACE „ „ When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides. the back, side(s), and top. back, side with the installation of more than one unit.
  • Page 38: Refrigerant Circuit

    REFRIGERANT CIRCUIT MODEL : AOG07LE, AOG09LE, AOG12LE, AOG14LE „ „ Heat exchanger 3-Way ( INDOOR ) valve 2-Way valve Muffler 4-Way valve Strainer Expansion valve Heat exchanger Strainer ( OUTDOOR ) Cooling Heating Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8"...
  • Page 39: Wiring Diagrams

    WIRING DIAGRAMS MODEL : AOG07LE, AOG09LE „ „ - (02 - 05) -...
  • Page 40 MODEL : AOG12LE, AOG14LE „ „ - (02 - 06) -...
  • Page 41: Capacity Compensation Rate For Pipe Length

    CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE MODEL : AOG07LE, AOG09LE „ „ Pipe length (m) COOLING 0.872 0.910 Û 1 0.961 0.886 0.925 Indoor unit is upper than 0.979 0.965 0.890 0.929 outdoor unit. 0.992 0.983 0.969 0.893 0.933 Height...
  • Page 42 MODEL : AOG12LE „ „ Pipe length (m) COOLING 0.858 0.868 Û 1 0.929 0.872 0.882 Indoor unit is upper than 0.960 0.933 0.876 0.885 outdoor unit. 0.992 0.964 0.937 0.879 0.889 Height difference H 1.000 0.972 0.944 0.887 0.896 1.000 0.972 0.944...
  • Page 43 MODEL : AOG14LE „ „ Pipe length (m) COOLING 0.893 0.909 Û 1 0.955 0.908 0.924 Indoor unit is upper than 0.975 0.959 0.912 0.928 outdoor unit. 0.992 0.979 0.963 0.916 0.931 Height difference H 1.000 0.987 0.970 0.923 0.939 1.000 0.987 0.970...
  • Page 44: Additional Charge Calculation

    ADDITIONAL CHARGE CALCULATION MODEL : AOG07LE, AOG09LE „ „ Refrigerant type R410A Refrigerant amount Refrigerant charge „ Total pipe length 15 or less 20 (MAX) 20g/m Additional charge MODEL : AOG12LE „ „ Refrigerant type R410A Refrigerant amount Refrigerant charge „...
  • Page 45: Air Flow

    AIR FLOW MODEL : AOG07LE, AOG09LE „ „ Cooling „ Number of rotations Air flow (r.p.m.) 1720 1011 Heating „ Number of rotations Air flow (r.p.m.) 1510 MODEL : AOG12LE „ „ Cooling „ Number of rotations Air flow (r.p.m.) 1830 1076 Heating...
  • Page 46 MODEL : AOG14LE „ „ Cooling „ Number of rotations Air flow (r.p.m.) 1800 1058 Heating „ Number of rotations Air flow (r.p.m.) 1660 - (02 - 12) -...
  • Page 47: Operation Noise

    OPERATION NOISE 8-1. NOISE LEVEL CURVE MODEL : AOG07LE „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 48 MODEL : AOG12LE „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency,Hz Octave band center frequency,Hz MODEL : AOG14LE...
  • Page 49: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT - (02 - 15) -...
  • Page 50: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model name AO  G07LE AO  G09LE AO  G12LE AO  G14LE Voltage 230 ~ Power supply Frequency *1) Max operating current 10.5 Starting Current Main Fuse (Circuit breaker) Current *2) Wiring Spec.: Power Cable *3) Limited wiring length : *1) The maximum current is the total current of indoor unit and outdoor unit.
  • Page 51: Safety Devices

    SAFETY DEVICES Model Protection form AO  G07LE AO  G09LE AO  G12LE AO  G14LE Current fuse 20A/250V Circuit protection (MAIN PRINTED 5A/250V CIRCUIT BOARD) Thermal protection OFF : 100 °C Fan motor protection program ON : 95 °C Terminal protection program OFF:110°C...